Zhuhai Wanlida Electrical
Automation Co., Ltd.
http://www.zhwld.com
User’s manual of MTPR-830Hc transformer differential
protection device
Prepared by: Qiu Lei
Proofed by: He Wenhui
Approved by:Lin Cunli
Document No.: WLD [K]-JY-313-2018 Version No.: V1.03.01
Date of publication: June, 2018
Copyright: Zhuhai Wanlida Electrical Automation Co., Ltd.
Note: Our Company reserves the right to modify this manual. For any inconsistency between
the product and this manual, please contact us for relevant services.
Technical support hotline: 0756-3395398 Fax: 0756-3395111
Foreword
F o r e w o r d
1. Model description
The structure type of MTPR-830Hc series protection is Hc, transformer differential
protection device.
2. Standards referenced
General specification for static protection, security and automatic equipment
DL 478-2010
Technical code for relaying protection and security automatic equipment
GB/T 14285-2006
Protective relay and automatic equipment design rules of power equipment
GB50062-2008
Transformer substation correspondence network and system DL/T 860.5-2006
Intelligent substation technology norms Q/GDW 383 -2009
Intelligent substation relay protection technical specifications Q/GDW_441-2010
IEC61850 engineering application model Q/GDW 396-2010
3. Caution
The appearance should be inspected before power is applied, to ensure that the panel is OK
without scratch, the screws are tightened, the device is grounded firmly, all screws of
plug-ins are tightened and in good contact.
When power is applied, the “Run” indicator on the panel should flash, protection and
measuring data are displayed on the LCD in cycle.
Operating circuit inside the device is only applicable to DC power supply, if AC power is
used, it should be applied with rectifier and filter.
It is prohibited to plug or unplug the plug-ins, in order to avoid damage to the device.
It is prohibited to do digital output test when the device is running with primary equipments.
2
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
1. Product description
1.1 Scope of application
MTPR-830Hc transformer differential protection device can protect various down step and
up step three-winding transformers and other transformers in substation under 110KV.
1.2 Function and specification
1.2.1 Protective function
Differential instantaneous over-current protection
Complex percentage restraint differential protection
Differential over-current alarm
CT failure alarm and block function
Body protection
1.2.2 Auxiliary function
Harmonic spectrum analysis
Phase display
Fault recorder
Self-checking fault alarm of device
Remote calling and modification of protection’s settings
One way (or two ways) programmable output of 4~20mA
Network print
Virtual correspondent node remote test
1.2.3 Monitoring function
Remote binary quantity: the device has 20-way binary input.
1.2.4 Communication capability
With industrial Ethernet port and standard RS485 multipoint communication port. Supports
MODBUS、IEC-60870-5-103(RS485 communication mode)、IEC-61850-5-104(Industrial
Ethernet communication mode) standard communication protocol and a new generation of
substation’s communication standard IEC 61850.
Supports single and dual network communication, it is fully qualified for network
redundancy and backup
1.2.5 GPS clock synchronization function
The device is able to receive GPS clock second synchronization or IRIG-B through RS485
differential voltage, and it can be done with monitoring system to accomplish GPS precise
clock synchronization or Ethernet-based SNTP synchronization.
1.2.6 Device specifications
32-bit POWERPC microprocessor
3
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
Real-time multi-task operating system and C++ program techniques, realizing online
programming
320*240 LCD display, easy for inspection
One or two ways 4~20mA DC quantity output, which can be set flexibly as any
corresponding electric quantity (such as I~IV side current, etc.)
Having the perfect harmonic analysis function
Integrating perfect metering functions and Metrology Function
Support network printing function, include two ways: real-time print and artificial print
Support virtual correspondent node remote test, including remote communication to
correspondent node, event to correspondent node, can online testing, it is convenient for
debugger to debug the device on-site.
Excellent hardware interchangeability, user maintenance is easily and it reduced quantity of
spare parts
Protection output relays can be configured flexibly for user convenience
Using a 6U, 19/3” standard enclosure in a rear plug-in structure. the device can be installed in
site on a switchboard or combined in a centralized manner
1.2.7 Main technical specifications
Rated data
Power supply: DC/AC 86~265V
Operating voltage: DC 220V or DC 110V
AC voltage: 100/ 3 V or 100V
AC current: 5A or 1A
Frequency: 50Hz
Power consumption
DC circuit: <10W (normal operation). <15W (protection operation)
AC voltage circuit: <0.5VA/phase
AC current circuit: <1VA/phase (In = 5A). <0.5VA/phase (In = 1A).
Overload capability
Protective current circuit: 2In, continuous operation
10In, allowing 10s
40In, allowing 1s
Range and error of setting value
Maximum range of setting value:
Current element: 0.1In~20In
Timing element: 0.00s~100.00s
Error of setting value:
Current and voltage setting value: ≤±3% of setting value
Angle setting value: ≤±2°
Whole-group operation time (including relay’s intrinsic time): Intrinsic operating
4
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
time of current instantaneous over-current protection: not greater than 40ms at 1.2
times the setting value
Measuring accuracy
AC current: Class 0.2
SOE resolution: ≤2ms
Pulse width of pulse quantity: ≥10ms
4~20mA DC quantity output: ≤±1%
Capacity of trip/closing output contact
Can be connected to DC 250V, 8A for prolonged periods.
GSP clock synchronization error
Clock synchronization error≤2ms
Environmental conditions
Ambient temperature:
Operating:-20℃~+55℃.
Storage:-25℃~+70℃, rainproof and snow-proof rooms with relative humidity not
greater than 80%, ambient air free of acid, alkaline or other corrosive and explosive gas. No
excitation quality is applied at the limits, the device shall not have any irreversible change.
After temperature restoration, the device shall operate properly.
Relative humidity:
The average relative humidity of the most humid month shall not be greater than 90%,
the average minimum temperature of this month not lower than 25℃ and there shall be no
surface condensation. at the highest temperature of +40℃, the average maximum humidity
shall not exceed 50%.
Atmospheric pressure: 80kPa~110kPa (below relative altitude of 2KM)
1.2.8 Hardware structure
The device uses a 6U, 19/3” standard enclosure, with aluminum alloy casing and installed by
overall embedding. The display panel is mounted in the front, and the other plug-in modules are
rear mounted. From the rear view, I/O, the power, CPU and AC plug-in modules are from the left
to the right.
External dimensions and boring diagram
5
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
Structural and dimensional diagram Boring diagram for installation
Devices fabricated on-screen steps: first release on-screen stents unfastening screws, remove
the stents. Install the device on the screen from the front and push until close to the fixed plate.
Install the stent 2, and then stent 1, and then use fastening screw to insertion hole from rear of
stent1, and then screwed into stent 2 and tighten screw. The stents from up and down are installed
in the same way. Use grounding screws to connect grounding line.
6
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
2. Function of device
2.1 Differential instantaneous over-current protection
Operating criterion:│Idif│>Isd
N
In which, Idif=|∑Ii|
i=1
(N is the number of transformer winding,Ii is rated frequency component of same
name phase current).
I sd --- Differential instantaneous over-current setting. Set according to the maximum
unbalance current and magnetizing inrush current. When escaping external fault. This protection
provides hard strap control function. Soft strap can control the ON or OFF of the protection. When
serious short-circuit fault occurs in the transformer, differential current will increase sharply.
When the current exceeds the setting value, protection operates instantaneously to protect
transformer.
D i f f e r e n t i a l i n s t a n t a n e o u s
c o n t r o l w o r d O N
H a r d p l a t e
f u n c t i o n O F F &
D if f e r e n t i a l p r o t e c t i o n
p la t e c lo s e d ≥
I d a ≥ I s d & P r o t e c t io n o u tp u t
I d b ≥ I s d
≥
I d c ≥ I s d
Figure 2-1 Differential instantaneous over-current protection operation diagram
2.2 Complex percentile restraint differential protection
The same as with the differential instantaneous protection, this protection also provides hard
strap control function. Soft strap can control the on or off of the protection.
This protection uses Three Segments Polyline Percentage Differential principle. The
operating formula is as follows:
1. When Ires < Ir1, Id≥Id0
2. When Ir1<Ires < Ir2,Id – Id0≥Kres1 * ( Ires - Ir1)
3. When Ires >Ir2,Id – Id0 – Kres1 (Ir2 - Ir1)≥Kres2 *(Ires –Ir2)
If any of the above conditions is met, and harmonic does not retain,percentage differential
protection operates.
Among the formula:Id is differential current,Id0 is setting value of differential threshold
current,Ires is restraint current,Ir1 is the restraint current of turning-point1,Ir2 is the restraint
current of turning-point 2, Kres1 is percentage coefficient 1,Kres2 is percentage coefficient 2.
Operating current:Id =∣I1+I2+I3+I4∣
Restraint current:Ires = | |Id|-|I1|-|I2|-|I3|-|I4| |
In the formula:I1, I2, I3, I4 are secondary current of side 1,2,3,4 CT of the transformer (the
7
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
equivalent current according to transformer wiring method after correction). The current
transformers of the two sides are wired in Y mode and points to transformer. The device can adjust
the current amplitude and phases of the two sides by setting unbalance coefficient and wiring
mode.
Percentage differential protection can make sure when external short-circuit occurs;
protection will not operate; while protection is high sensitive to internal fault.
I d
I d 0
I r 1 I r 2 I r e s
Figure 2-2 Differential operation curve
Through control word, protection can choose whether to block through CT failure.
Harmonic restraint: three-phase cross restraint is applied, when the following formula is met,
protection will operate:
Ih<Kxb×Id
Ih ――― 2nd order harmonic quantity of differential current
Kxb――― secondary harmonic restraint coefficient, set according to the magnetizing inrush
current when escaping no-load closing of the transformer.
2.3 Differential over-current alarm
Max{I da, I db, I dc}>I set
Which I set is the differential over-current setting, and it is settable, when differential exceeds
the setting, the device will send off differential over-current alarm after 10s delay.
2.4 CT failure alarm and block function
When in normal operation,the sum of three phase current of each side is zero. When one
phase CT failure occurs, the sum of three phase current is not zero. To distinguish from ground
fault, the following should be judged:
1) Among three phase current, the minimum one is zero.
2) The maximum phase current is more than zero and less than CT failure block current.
When detecting CT failure, block percentage differential protection according to on/off set by
control words and delay sending alarm signal, and show the time of failure. CT failure detection
function can be on/off according to control words. Differential instantaneous over-current
protection is not locked by CT failure。
8
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
2.5 Body protection
Body protection of this device has body heavy gas, voltage regulation heavy gas and pressure
release(there is a standby non-electric quantity),it corresponding operating terminals directly trip
through the hardware of the device.
Body heavy gas, voltage regulation heavy gas, pressure release, body light gas, voltage
regulation light gas and oil low signal are connected to the device through binary input. The
device send Alarm signal. High temperature(high oil temperature)protection and lost of cooling
control power can set delay. Lost of cooling control power has long delay and short delay. Long
delay corresponds to high temperature signal not presents, short delay corresponds to high
temperature signal presents. The operation diagram of lost of cooling control power is as follows:
N o h ig h te m p e ra tu re
s ig n a l
C o o lin g c o n tro l p o w e r
lo ss s ig n a l &
L o n g t im e
C o o lin g c o n tro l p o w e r d e la y
lo ss c o n tro l w o rd O N
P ro te c tio n o u tp u t
H ig h te m p e ra tu re s ig n a l S h o rt t im e
d e la y
C o o lin g c o n tro l p o w e r
lo s s s ig n a l &
C o o lin g c o n tro l p o w e r
lo ss c o n tro l w o rd O N
Figure 2-3 Lost of cooling control power operation diagram
2.6 Fault recorder
See the communication coding table for the protection voltage and current waveform data
collected by the recording unit.
2.7 Network print
Device supports network printing function, can print remote control information, SOE
information and the setting parameter list. The printer IP address must been set rightly on the
device (the network segment of printer must be as same as that of device IP addresses), then
connect a printer, put on "real-time report print ", it can print the current remote control
information or SOE information when device is connected to the background (including remote
communication shift, protection action), and can print the current SOE information when device is
not connected to the background. In addition, when press the "ok" button in the "print report" or
"print setting value" menu, it can print the all setting parameter or the all report information,
including action value.
2.8 Virtual correspondent node remote test
The function is used to complete the communication node remote test of the device, do not
need to access the actual analog electric quantity or the input quantity. Specific operation as
follows, connect to the background, In the remote test menu, operate the “virtual input test” and
the “virtual SOE test” menu in the “remote test” menu, press the "OK" button after the
modification of various settings, then by observing the background pop-up warning window or the
9
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
change of the corresponding value, to determine whether the device communication node is right.
It is convenient for debugger to debug the device on-site. When you are in the mode of remote test,
the all protect must be off.
2.9 GPS clock synchronization
The GPS clock synchronization signal is input as rs485 differential voltage, the device is able
to receive GPS clock second synchronization. If there is GPS signal, there will be flashing
on the bottom of cycle menu. Otherwise won’t.
The principle of GPS clock synchronization: The second pulse or minute pulse act with the
monitoring system, the time base with second precision is sent by monitoring system, when the
GPS second differential signal arrives, the time base is unified and the milliseconds are cleared.
The device is able to receive GPS clock second synchronization or IRIG-B through RS485
differential voltage, and it can be done with monitoring system to accomplish GPS precise clock
synchronization or Ethernet-based SNTP synchronization.
2.10 Overhaul status
When the device put into overhaul plate, remote sign, remote measure can uploading
background computer. But the device can’t remote control by background computer. The SOE
event、Alarm event、Trip event, etc also can’t uploading background computer.
3. Setting of parameters and setting values of the device
3.1 System parameters
Parameter Range Description
Settings of setting value zone number(Setting Zone No.)
Setting value zone
0-7 Set step:1(factory default 0)
number(Setting Zone No.)
Communication settings(Comm. Setting)
Set step :1 (factory default 1)
NET Protocol 0-2
(0-Quit;1-IEC104;2-IEC61850)
Set step :1 (factory default 0)
RS485 Protocol 0-2
(0-Quit;1-IEC103;2-MODBUS)
RS485 address(RS485
1-99 Set step:1(factory default 1)
Address)
RS485 baud rate(RS485 Set step:1(factory default 2)0:2.4KB;1:4.8KB;
0-5
Baudrate) 2:9.6KB;3:19.2KB;4:38.4KB;5:115.2KB;
IP address(IP Address) It has four One section set step:1(factory default 192.168.0.252)
SNTP Address (SNTP sections. The
One section set step:1(factory default 192.168.0.253)
Address) range of
10
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
Parameter Range Description
KW default value(KW every section
One section set step:1(factory default 12.8.6.1)
Default) is
Printer IP address(Printer IP) 0-255 One section set step:1(factory default 192.168.0.254)
Setting of basic parameters(B. Parameters)
I side Rating Current(In) 0-1 Set step: 1 (factory default 0) 00: 5A. 01: 1A
II side Rating Current(In) 0-1 Set step: 1 (factory default 0) 00: 5A. 01: 1A
III side Rating Current(In) 0-1 Set step: 1 (factory default 0) 00: 5A. 01: 1A
IV side Rating Current(In) 0-1 Set step: 1 (factory default 0) 00: 5A. 01: 1A
For harmonic calculation, select the corresponding
reference quantity:
Harmonic Channel 0-12 0:exit from harmonic calculation function
1:Ia1,2:Ib1,3:Ic1,4:Ia2,5:Ib2,6:Ic2,7:Ia3,8:Ib3,
9:Ic3,10:Ia4,11:Ib4,12:Ic4
0: External transform,1: Y/Y/Y/△-11,2: Y/Y/△/△-11,
3: Y/△/△/△-11,4: Y/Y/Y/△-1,5: Y/Y/△/△-1,
6: Y/△/△/△-1,7: Y/Y/Y/Y-12,8: △/△/Y/Y-11
Transformer Mode 00-08
(factory default 0,when choose Y/Y/Y/Y-12 wiring
mode,the program will act as 11 o’clock mode so as to
eliminate zero sequence influence)
Wave Record 00-01 Set step:1(factory default 0)00:Off;01:On
Hard word on/off 00-01 Set step:1(factory default 0)00:Off;01:On
Benchmark Side 00-01 Set step:1(factory default 0) 00:L-V Side;01: H-V Side
Remote communication ack
10-100ms Set step: 1 (factory default 40ms)
time (input ack time)
Real-time print report
0-1 Set step: 1 (factory default 0) 00:exit;01:on
on/off(auto print report)
Display Mode 0-1 Set step: 1 (factory default 0) 00:Diagram;01:Analog
D/A channel setting(D/A Setting)
Select DA1~2 to output corresponding reference
quantities:
1:Ia1,2:Ib1,3:Ic1,4:Ia2,5:Ib2,6:Ic2,
7:Ia3,8:Ib3,9:Ic3,10:Ia4,11:Ib4,12:Ic4
DA1~2 Channel Selection 0-12 Rating 5A:
Current reference quantity: 0-6A corresponding to
4mA-20mA,
Rating 1A:
Current reference quantity: 0-1.2A corresponding to
11
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
Parameter Range Description
4mA-20mA,
DA1~2 Adjustment Factor 0.5-1.5 Adjust D/A channel 1~2(4-20mA) parameters
Channel factor setting(Channel Coeff.)
Set step:0.001(factory default 1)
Channel data 1~12 0.5- 5 Channel data 1-12 are corresponded to the channel factor
of analog quantity 1-12.
balance coefficient setting
balance coefficient of side 1 0-5.00 Set step:0.01(factory default 1)
balance coefficient of side 2 0-5.00 Set step:0.01(factory default 1)
balance coefficient of side 3 0-5.00 Set step:0.01(factory default 1)
balance coefficient of side 4 0-5.00 Set step:0.01(factory default 1)
In which,balance coefficient K b is used to remove the influence of unbalance current. The
specific calculation is as follows:
1. Calculate first rated current of each of the transformer I 1n
I Sn1n = 3U n
which, Sn is the maximum rated capacity of the transformer,U n is the rated voltage of each
side of the transformer(The actual operating voltage should be subject to).
2. Calculate secondary rated current of each side of the transformer I 2n
I I1n2n = Kcon KCT
which,K CT is CT ratio of each side,K con is CT secondary wring coefficient(Y wring side of
the transformer is 3 ,△ wring side is 1).
3. It should be referenced to I side,calculate each side balance coefficient Kb,m of the
transformer(side m)
K I 2n,1 U n,m K CT ,m K con,1b,m = = I 2n,m U n,1 K CT ,1 K con,m
which,Un,1 , KCT ,1 , Kcon,1 are rated voltage, CT ration and CT secondary wring
coefficient of side I,U n ,m , KCT,m, Kcon,m are respectively rated voltage, CT ration and
CT secondary wring coefficient of side M
12
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
3.2 List of setting values
Setting value Range Description
Differential instantaneous
over-current protection 1/0 1/0:on/off(factory default: off)
(Instant Diff.)
Percentage differential protection
1/0 1/0:on / off (factory default: off)
(Percent Diff.)
Differential current over-current alarm
1/0 1/0:on / off (factory default: off)
(Diff. C Over-Limit)
CT Failure Alarm 1/0 1/0:on / off (factory default: off)
CT Failure Lock 1/0 1/0:on / off (factory default: off)
High temperature protection
1/0 1/0:on / off (factory default: off)
(High Temperature)
Lost of cooling control power
1/0 1/0:on / off (factory default: off)
(Cooling Lost)
Mutation startup (Abrupt Current)
Starting current Startup Current 0.10-10.00A Set step:0.01A(factory default 10A)
Differential instantaneous over-current protection (Instant Diff.)
Differential instantaneous
0.10-100A Set step:0.01A(factory default 10A)
over-current setting(Inst. Current
Percentage differential protection (Percent Diff.)
Percentage differential threshold
0.10-100A Set step:0.01A(factory default 10A)
current Percent Diff. Sill)
Percentage differential restraint
turning-point point1 0.10-100A Set step:0.01A(factory default 10A)
(Per. Res. Inflex. 1)
Percentage differential restraint
turning-point2 0.10-100A Set step:0.01A(factory default 10A)
(Per. Res. Inflex. 2)
Percentage restraint coefficient1
0.10-1.00 Set step:0.01(factory default 1.00)
(Restraint Coef. 1)
Percentage restraint coefficient2
0.10-1.00 Set step:0.01(factory default 1.00)
(Restraint Coef. 2)
Secondary harmonic restraint
0.10-1.00 Set step:0.01(factory default 1.00)
coefficient (Sec.Res.Coef.)
13
Protection on/off word
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
Differential over-current alarm (Diff. C Over limit)
Differential over-current setting
0.1-100A Set step:0.01A(factory default 10A)
(Diff. C OL Value)
CT failure alarm/block (CT Failure)
Block current
0.1-100A Set step:0.01A(factory default 10A)
(Overload Current)
Delay setting (Time Set) 0.10-100.00s Set step:0.01s(factory default 15s)
High temperature protection (High Temperature)
Delay setting (Time Set 0-9999s Set step: 1s(factory default 20s)
Lost of cooling control power (Cooling Lost)
Long Delay setting Long Time Set 0-9999s Set step: 1s(factory default 20s)
Short Delay setting Short Time Set 0-9999s Set step: 1s(factory default 20s)
Note the choice of secondary rated current(In):
I1n
Subject to secondary rated current of each side of the transformer I 2n = K Kcon2, note that CT
CT secondary wring coefficient of each side of the transformer K con is different. For example,
Subject to the higher voltage side of the transformer, when calculate secondary rated current of the
higher voltage side of the transformer(Y wring side), it should multiply 3 .
4. Description of binary input, output and analog quantity
4.1 Monitoring of analog quantities
Analog quantities can be monitored under the [Current Data], menu in the [Run States] menu,
press the ““, ““ keys to flip over. The factory precision of the device has been calibrated. The
protection current is calibrated at double the rated current and the measuring current at a single
rated current. The list is as follows:
Analog quantity
Analog quantity name Test method
terminal
1 side protection phase Add double the rating, displayed deviation not
Terminals D01, D02
A current (Ia1) exceed 1%
1 side protection phase Add double the rating, displayed deviation not
Terminals D03, D04
B current (Ib1) exceed 1%
1 side protection phase Add double the rating, displayed deviation not
Terminals D05, D06
C current (Ic1) exceed 1%
2 side protection phase Add double the rating, displayed deviation not
Terminals D07, D08
A current (Ia2) exceed 1%
2 side protection phase Add double the rating, displayed deviation not
Terminals D09, D10
B current (Ib2) exceed 1%
14
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
Analog quantity
Analog quantity name Test method
terminal
2 side protection phase Add double the rating, displayed deviation not
Terminals D11, D12
C current (Ic2) exceed 1%
3 side protection phase Add double the rating, displayed deviation not
Terminals D13, D14
A current (Ia3) exceed 1%
3 side protection phase Add double the rating, displayed deviation not
Terminals D15, D16
B current (Ib3) exceed 1%
3 side protection phase Add double the rating, displayed deviation not
Terminals D17, D18
C current (Ic3) exceed 1%
4 side protection phase Add double the rating, displayed deviation not
Terminals D19, D20
A current (Ia4) exceed 1%
4 side protection phase Add double the rating, displayed deviation not
Terminals D21, D22
B current (Ib4) exceed 1%
4 side protection phase Add double the rating, displayed deviation not
Terminals D23, D24
C current (Ic4) exceed 1%
4.2 Monitoring of binary input
Binary input can be monitored under the [Binary input] menu in the [Run States] menu, press
the ““, ““ keys to flip over.
Binary input Binary input name Test method
terminal
B01 Common terminal of binary input - External power supply of 220V or 110V DC
(Should be connected to DC220V can be applied, connect the negative terminal
or DC110V to terminal B01, positive terminal to terminal
negative terminal of external power B02~B21, in [Binary input] menu in the
supply) [Run States], the status of binary input can be
B02 Body heavy gas signal seen.
B03 Voltage regulation heavy gas signal The device also has a 24V DC supply, if
B04 Pressure release signal it is used, terminal B22 can be connected to
B05 Standby non-electric quantity terminal B02~B21, in [Binary input] menu
signal in the [Run States], the status of binary input
B06 Body light gas signal can be seen.
B07 Voltage regulation light gas signal Connect the positive terminal to terminal
B08 Oil temperature high A12(+KM), negative terminal to terminal
B09 Oil low signal A05(TWJ),A04(HWJ),in [Binary input] menu
B10 Lost of cooling control power in the [Run States], the status of binary input
B11 Input 10 can be seen.
15
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
B12 Input 11 Please note about the binary input voltage
B13 Input 12 upon ordering, it is set to DC220V by default.
B14 Input 13
B15 Input 14
B16 Input 15
B17 Input 16
B18 Input 17
B19 Input 18
B20 Differential protection plate
B21 Overhaul
B22 Positive terminal of internal 24V
power supply
A10 Body heavy gas trip connect the negative terminal to terminal
A11 Voltage regulation heavy gas trip A16, positive terminal to terminal A10~A13,
A12 Pressure release trip in [Binary input] menu in the [Run States],
A13 Standby non-electric quantity trip the status of binary input can be seen.
4.3 Monitoring of binary output
Binary output can be monitored under the [Binary output] menu, press the ““, ““ keys to
flip over.
Binary output terminals Binary output name Test method
B23-B24 Trip Signal
B23-B25 Alarm Signal
B17-B18 Differential trip side 1
B19-B20 Differential trip side 2
Select open and close menu, use “+”, “-”
B21-B22 Differential trip side 3
key to operate and test the corresponding
B23-B24 Differential trip side 4
terminals. B29-B30 and B31-B32 are
Differential trip side
B25-B26 common open terminals that should close.
standby
B27-B28 Output 6
B29-B30 Output 7
B31-B32 Output 8
16
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
5. Operation instructions
5.1 Control panel of device
320*240 matrix LCD (The LCD will go off after a period of absence of keyboard operation. the
LCD will be illuminated automatically when any key is pressed or in case of protection trip or
alarm.)
Signal indicator: run, communication, trip, alarm, fault (of the device), Backup, remote.
Key pad: , , , , Cancel, -, +, Enter, Revert
5.2 Instructions for use of key pad and LCD display
During the device’s normal operation, it will display the I~IV sides current data、device
address and time in cycle. Press the “Enter” key to enter the main menu, which is a multi-level
tree menu. Press the ““, ““ keys to move the cursor to the desired entry, press the “Enter” key
to enter this entry, and press the “Cancel” key to return to the next higher level of screen. If this
screen is still a menu, continue to press the ““, ““ key to select the desired entry, press the
“Enter” key to enter the next level of screen, and press the “Cancel” key to return to the next
higher level of menu. If there is no menu screen, be sure to press the “Cancel” key to return to the
next higher level of menu. The main menu is shown at the center of the following figure, with the
corresponding submenus on both sides.
17
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
01.Run States -1/5- Main menu 05.Report Dis. -1/4-
Current Data Trip Report Binary Input
Soft Strap 01.Run Status Binary Report Event Report
Harmonic Data AD Volt. Data 02.Run Parameters Print Report
03.Setting View 06.Parameters -1/5- 02.Run Param. -1/3- Comm. Setting
Setting Zone No. 04.Setting Value B. Parameters
PROT On/Off D/A Setting
Clock Setting 05. Report Manage Balance Coe.
Channel Coe.
03.Setting View-1/8- 06. SYS Parameters
Abrupt Current 07.Device Test 07.DeviceTest. -1/2- Instant Dif. Output Test
Percent Dif. 08.PassWord Lamp Test Diff. C Over limit ...... 09.Version Info. 08.Password □□□□
04.Setting Value-1/8-
Abrupt Current 10.Comm Test
PROT AUTO DEV V2.00 Instant Dif. Type:MTPR-830Hc
Percent Dif. 10.Comm test ID:□□.□□.□□
Diff. C Over limit Input Test CRC:□□□□□□□□ ...... SOE Test Date:20XX-XX-XX
Note 1:For the Setting menu, see the description of each device.
Run Status
The [Run Status] menu contains 5 submenus, including current data, binary input, soft strap,
harmonic data, AD voltage data. It is described as follows:
Current Data -1/21-
Ia1 = □□□·□□ A
000.0°
Ib1 = □□□·□□ A
000.0°
Ic1 = □□□·□□ A
000.0°
Ia2 = □□□·□□ A
000.0°
Ib2 = □□□·□□ A
000.0° Ic2 = □□□·□□ A
000.0°
18
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
Binary Input -1/24-
Heavy Gas :□
VR Heavy Gas :□
Press relief :□
Spare Non-e. :□ Description varies with model, see corresponding terminal
Light Gas :□ diagram for details
VR Light Gas :□
Oil High T :□
Oil Level Low :□
Cooling Lost :□
Input 10 :□
......
Note: In the standard configurations, the input circuit has the connection to an external
220VDC control power supply. When no DC control power supply or control system is available
on site, but a 110VDC control power supply is available, a 110VDC control power supply may be
used for direct connection through local hardware adjustment, or the 24V power supply of the
device may be used as the input power supply (when the input common terminal is +24V, terminal
number: B22, Terminal B01 is kept float). However, this must be specified upon ordering.
Soft Strap -1/7-
Instant Diff. Off
Percent Diff. Off
Diff. C Over Limit Off
CT Failure Alarm Off
CT Failure Lock Off
......
Harmonic Data -1/10-
2nd : □□□·□□%
3rd : □□□·□□% 2~11 harmonics for which analog channels
4th : □□□·□□% have been selected in system
5th : □□□·□□%
......
11th :□□□·□□%
AD Volt. Data -1/2-
AD1:□□·□□□V AD Voltage Check
AD2:□□·□□□V
Run Parameters
In the [Run Parameters] menu includes 3 submenus, including [Setting Zone No.]、[PROT
On/Off]、[Clock Setting], The screen Content is as follows:
Setting Zone No. :Range 00~07.
PROT On/Off:The device protect plate can be select in this menu.
19
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
PROT On/Off -1/43- Parameter Modify
Instant Diff.
On Off ◇Enter ◆Cancel
Press “+”, “-” keys to select the protection function On or Off. The interface will eje
ct the window as right chart show when you press the “Enter” key. Move the cursor to t
he desired position for modification by pressing the ““, ““ keys. Press the “Enter” ke
y to complete setting, and the device will prompt modifying success or not. If the “Canc
el” key is pressed, the protect plate status setting will be cancelled and the menu will ret
urn previous menu.
Clock setting:
A battery-back real-time clock is provided in the device, which can perform time adjust
remotely via the communication network or in-site time adjust in the [Time Setting] menu.
Enter this menu and press the “Enter” key, the clock will stop refreshing and a cursor will
Clock setting appear. Move the cursor to the desired position for modification by
Date:20□□-□□-□□ pressing the ““, ““ keys, modify to the desired value with the “+”,
Time: □□:□□:□□
“-” keys. Press the “Enter” key to complete setting. If the “Cancel”
key is pressed, the setting will be cancelled and the screen continues to refresh the clock.
Setting View
This meun just for query.You can’t modif the value to prevent faulty operation.
Setting Value
After entering the password, you can enter the [Setting Value] menu. See the settings
description of the protection device for the detailed description.
Report Manage
The [Report Manage] menu includes 4 submenus, including trip report, binary report, event
report and print report. Event recording includes: device self-check fault, device setting value
modification, system parameter modification and setting zone number modification, etc. Trip
report can be record for the last 50 events, binary report for 100, event report for 30 at most.
Beyond this, the latest report will overwrite the earliest one. Press the “Enter” key to enter the
corresponding [To view xx report, please enter report number: 00] menu, and enter any figure
within storage volume, press the “Enter” key to display the contents of that report. The screen is as
follows:
Report No.:□□ ↓ Report No. of this report
Year, month, day, hour, minute, second and 20□□-□□-□□ millisecond when it took place
□□:□□:□□:□□□
□□□□□□
Press key to see the specific operation value. Press and keys to flip over. Operation
values.
Action value view
20
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
Ia1 = □□□·□□ A
Ib1 = □□□·□□ A
Ic1 = □□□·□□ A
……
System parameters
After entering the [SYS Parameters] menu, the correct password is required to enter the [SYS
Parameters] menu. It displays the following:
Parameters -1/5-
Comm. Setting
B. Parameters
D/A Setting
Balance Coef.
Channel Coef.
Communication Setting
Comm. setting -1/8-
NET Protocol
□□ 00:Quit;01:IEC104;02:IEC61850;
RS485 Protocol
□□
00:Quit;01:IEC103;02:MODBUS;
RS485 Address □□ Communication address of device 01~99
RS485 Baud rate
□□ 00:2.4KB;01:4.8KB;02:9.6KB;03:19.2KB;04:
IP Address
□□□. □□□. □□□. □□□ 38.4KB;05:115.2KB
SNTP Address
□□□. □□□. □□□. □□□
K W Default For Ethernet communication
□□□. □□□. □□□. □□□
Printer IP
□□□. □□□. □□□. □□□
Setting of basic parameters (see the description of the protection device for basic parameters)
B.Parameters: -1/11-
Rating Current 1
□□
Rating Current 2
□□
Rating Current 3 Setting the CT secondary current rating 00: 5A. 01: 1A
□□
Rating Current 4
□□
......
D/A setting
The device has two 4~20mA outputs. The DA1~DA2 adjustment factor is used to adjust the
accuracy of the channel output. The DA1~DA2 channel selection is used to select the
21
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
corresponding analog quantity channel (see the description of the protection device for specific
reference quantities). In the accuracy test, make sure the field ground is in good contact.
Otherwise the accuracy might be affected.
Channel Coefficient
The device can adjust channel coefficient by this menu to raise Sample size.
Device test
After entering the [Device Test] menu, the correct password is required to enter the [Device
Test] menu. It’s have two menu include [Output Test] and [Lamp Test].
Output Test
Enter [Output Test] menu, It displays the following:
Output Test -1/11-
Differential 1
Differential 2 Press “Enter” key Differential 1
Differential 3 On Off
Differential 4 Note:
Standby Output Node:A17,A18 Open
…… Press “Cancel” key
Operate All
(Note: When the test is performed on the 6 protection outputs, the starting relay will be in the
“Closed” state automatically. The “+”, “-” keys are used for switching between the “Close/Open”
control.)
Lamp Test
Lamp Test
◇Light ◆Quench
Used for testing Stand or fall of all LED lights.
Password
The [Password] menu is used to modify the password for entry into the Settings, System
parameters and Output Test submenus. The initial password is provided by the factory. The
universal password is “1000”.
Move the cursor to the desired position for modification by pressing the ““, ““ keys,
Input password modify to the desired password with the “+”, “-” keys. Press the
0 0 0 0 “Enter” key to enter the new password setting menu as above.
press the “Cancel” key to cancel the setting.
Version information
In the main menu, after entering the [Version Info.] menu, the Type, ID, CRC and Date of the
software will be displayed.
PROT AUTO DEV V2.00
Type:MTPR-830Hc ID:□□.□□.□□
CRC:□□□□□□□□
Date:20XX-XX-XX
22
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
Note: For a corresponding nonstandard model, the device’s displayed Type does have to be changed.
Comm test
When debugger debug the device on-site in the case of no-accessing the actual analog electric quantity
or the input quantity, [Comm. Test] is used to do the test of the communication node of the device.
6. Check of protection function
6.1 Check of differential instantaneous over-current protection
Set differential instantaneous over-current protection to on. Hard strap function is off (when
it’s on, C15 differential protection strap should be connected). Add each side current and make the
differential current more than the setting,the differential instantaneous over-current protection will
operate. According to output matrix,the corresponding terminals should be connected.
For example:
Wire as the following diagram. Set differential instantaneous over-current protection to on.
Hard strap function is off.
MTPR-830Hc
Ia1 D1
Ia1’ D2 B29
Ib1 D3
Power supply Ib1’ D4
Ic1 D5 B30
Ic1’ D6
Figure 6-1
Set according to the following table. Measure the operating current and take them down in
the following table. When instantaneous over-current protection operates, according to output
matrix,the corresponding terminals should be connected..
Instantaneous
Add only phase A current, over-current protection 1ln 2ln 5ln 10ln
check the operating value setting(A)
Operating value
Instantaneous
Add only phase B
over-current protection 1ln 2ln 5ln 10ln
current,check the
setting (A)
operating value
Operating value
Instantaneous
Add only phase C
over-current protection 1ln 2ln 5ln 10ln
current,check the
setting (A)
operating value
Operating value
23
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
6.2 Check of Complex percentage differential protection
Set percentage differential protection to on, only add phase A current to each side(same
angle),do not add harmonic. Let differential current exceed percentage differential minimum
threshold, restraint current should be zero. When percentage differential operates,according to
output matrix,the corresponding terminals should be connected.
The minimum threshold of
Only add phase A 1ln 2ln 5ln 10ln
percentage differential (A)
current to each side,
Operating value
check operating zone
Operating zone
For protection check under other conditions, please refer to the detailed description about
percentage differential in “device function” of this manual. Concerning in this manual, add all
sides current and satisfy percentage differential curve and harmonics don’t restrain.
6.3 Check of differential over-current alarm
Set differential over-current alarm to On, add current to every side and make the differential
current exceed differential over-current setting, the device will report differential over-current
alarm. Test corresponding terminals according to output matrix should be short. Differential
instantaneous protection checking method should be referenced.
6.4 Lost of cooling control power
There are long and short delay for lost of cooling control power, when lost of cooling
control power signal exists, together with oil high temperature signal, the device will output after
short delay; when lost of cooling control power signal exists, no oil high temperature signal exists,
the device will output after long delay.
Wire according to the following Fig, set lost of cooling control power to On.
MTPR-830Hc
Input common port
B01 B29
Oil temp erature is high B08 Power supply
B30
C ooling control power
B10
Figure 6-2
Connect B01-B08 and B01-B10 ( note that I/O board has external DC 220V and
self-generated 24V), the device will output after short delay; If only B01-B10 is short, the device
will output after long delay. Test the 2 delays and compare them with setting.
After it operates, test the terminals should be shorted according to output matrix.
24
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
Addendum 1: Terminal diagram of the device
I/O POWER CPU A C
A01 Main transformer
Input comon
trip side I B01 point-
A02 Main transformer B02 Main transformer D01 D02trip side I heavy gas signal NET1 Ia1 Ia1'
A03 Main transformer Pressure regulatortrip side II B03 heavy gas signal
A04 Main transformer Pressure release
D03 Ib1 Ib1' D04
trip side II B04 signal
A05 Main transformer B05 Backup Non-electricitytrip side III quantity signal D05 Ic1 Ic1' D06
A06 Main transformer B06 Main transformertrip side III light gas signal
A07 Main transformer B07 Pressure regulator D07 Ia2 Ia2' D08trip side IV light gas signal
A08 Main transformertrip side IV B08
High oil NET2
temperature signal D09 Ib2 Ib2' D10
A09 B09 Low oil signal
A10 Main transformer B10 Lost of cooling Ic2'heavy gas trip control power D11 Ic2 D12
A11 Pressure regulatorheavy gas trip B11 Input 10
A12 Pressure release B12 D13 Ia3 Ia3' D14trip Input 11
A13 Backup Non-electricityquantity trip B13 Input 12 D15 Ib3 Ib3' D16
A14 B14 Input 13
Run Light
A15 B15 Input 14 D17 Ic3 Ic3' D18
A16 Main transformercommon port - B16 Input 15 D19 Ia4 Ia4' D20
DEBUG D21 Ib4 Ib4' D22
D23 Ic4 Ic4' D24
Differential
A17 B17 GPS-Atrip side I Input 16 C01
A18 Differential B18 Input 17 C02 GPS-B Note:
trip side I
A19 Differential C03 1.Ia1,Ib1,Ic1 aretrip side II B19 Input 18
A20 Differential B20 Differential C04 COM1A protection currents oftrip side II protection plate side I.
A21 Differential Overhaul COM1Btrip side III B21 C05 2.Ia2,Ib2,Ic2 are
A22 Differential B22 (+24V) C06 Shielded ground protection currents oftrip side III
A23 Differential B23 C07 COM2A side II.trip side IV Common terminal
A24 Differential
3.Ia3,Ib3,Ic3 are
B24 Trip Signal C08 COM2Btrip side IV protection currents of
A25 Differential B25 C09 DCS1+
trip standby Alarm Signal side III.
A26 Differential B26 C10 DCS1- 4.Ia4,Ib4,Ic4 aretrip standby
A27 Output 6 B27 Power off C11 DCS2+ protection currents of
side IV.
A28 Output 6 B28 Power off C12 DCS2- 5.COM1 and COM2 are 485
A29 Output 7 B29 Power interfaces, Net1 and
A30 Output 7 B30 Power Net2 are Ethernet
interfaces.
A31 Output 8 B31 6. Whether +24V on Power
A32 Output 8 B32 Shielded ground board is standard
configuration or not
can be fixed when using
internal +24V as feeder.
Figure 1 Terminal diagram of MTPR-830Hc transformer differential protection device
25
User’s manual of MTPR-830Hc transformer differential protection device WLD[K]-JY-313-2018
Addendum 2: Typical wiring diagram of the device
breaker
C B A
breaker
A
B
C
D01 D02 D03 D04 D05 D06 D07 D08 D09 D10 D11 D12 D13 D14 D15 D16 D17 D18 D19 D20 D21 D22 D23 D24
Ia1 Ia1'Ib1 Ib1'Ic1 Ic1'Ia2 Ia2'Ib2 Ib2'Ic2 Ic2'Ia3 Ia3'Ib3 Ib3'Ic3 Ic3'Ia4 Ia4'Ib4 Ib4'Ic4 Ic4'
I side current II side current III side current IV side current
AC plug-in unit
MTPR-830Hc transformer differential protection device
Net1 Main A01transformer
Trip side I A02
Net2
Main A03
transformer
Debugging port Trip side II A04
C01 GPS+ Maintransformer A05
C02 GPS- Trip side III A06
C03 Main A07
transformer
C04 COM1A Power plug-in unit Trip side IV A08
C05 COM1A AC/DC A09
Shielded
C06 Shielded ground ground Body heavy gas signal A10
Voltage regulation
C07 COM2A heavy gas signal A11
C08 COM2A Pressure release signalA12
DCSOut1+ Standby non-electricC09 quantity signal A13
4~20mA
RL C10 DCSOut1- A14
C11 DCSOut2+ A15
4~20mA
RL C12 DCSOut2- common terminal A16
Differential
Trip side I
Differential
Trip side II
Differential
Trip side III
Differential
Trip side IV
Differential Trip
side standby
Output 6
Output 7
Output 8
Figure 2 Typical wiring diagram of MTPR-830Hc transformer differential protection device
26
breaker
CPU plug-in unit
-WC B01 Input common terminal- B19 Input 18
+WC DifferentialB02 Body heavy gas signal B20 protection plate
Voltage regulation
B03 heavy gas signal B21 Overhaul
B04 Pressure release signal B22 24V+
Standby non-electric
B05 quantity signal B23 Signal common terminal
B06 Body light gas signal B24 Trip Signal
Voltage regulation
B07 light gas signal B25 Alarm Signal
B08 Oil temperature high B26
B09 Oil low signal B27 Power off
B10 Lost of cooling control power B28 Power off
B11 Input 10 B29 Power+
B12 Input 11 B30 Power-
B13 Input 12 B31
B14 Input 13 B32 Shielded ground
B15 Input 14
B16 Input 15
B17 Input 16
B18 Input 17
I/O plug-in unit
breaker