Zhuhai Wanlida Electrical
Automation Co., Ltd.
http://www.zhwld.com
User’s manual of MTPR-820Hc transformer protection
and monitoring device
Prepared by: Zhu Yanan
Proofed by: Li Changwen
Approved by:Lin Cunli
Document No.: WLD [K]-JY-312-2018 Version No.: V1.03.01
Date of publication: June, 2018
Copyright: Zhuhai Wanlida Electrical Automation Co., Ltd.
Note: Our Company reserves the right to modify this manual. For any inconsistency between
the product and this manual, please contact us for relevant services.
Technical support hotline: 0756-3395398 Fax: 0756-3395111
Foreword
F o r e w o r d
1. Model description
MTPR-820Hc is the microcomputer transformer protection and monitoring device, the
structural type of the MTPR-820Hc series protection is Hc. MTPR-820Hc supports A, B, C
three-phase current protection, also supports A, C two-phase current protection. When
ordering, please specify.
2. Standards referenced
General specification for static protection, security and automatic equipment,
DL 478-2001
Technical code for relaying protection and security automatic equipment
GB/T 14285-2006
Protective relay and automatic equipment design rules of power equipment
GB50062-92
Transformer substation correspondence network and system DL/T 860
Intelligent substation technology norms Q/GDW 383 -2009
Intelligent substation relay protection technical specifications Q/GDW_441-2010
IEC61850 engineering application model Q/GDW 396-2010
3. Caution
Negative sequence voltage involved in this device of protection function is combined with
phase voltage, all of low voltage component depend on line voltage in compound voltage
block, if one of the three line voltages is lower than low voltage setting, low voltage
component will operates and unblocks over current protection.
The value of measuring current phase B can be gotten form measuring current phase A and
phase C.
There are 4 standard curves of inverse protection involved in this device of protection
function, if the fault current is higher than 15 times of the rated current, the inverse protection
component will be exported according to the action time of 15 times of rated current.
The appearance should be inspected before power is applied, to ensure that the panel is OK
without scratch, the screws are tightened, the device is grounded firmly, all screws of
plug-ins are tightened and in good contact.
When power is applied, the “Run” indicator on the panel should flash, protection and
measuring data are displayed on the LCD in cycle.
The terminal D25~D28 are measuring circuit of 4~20mA DC signal, when testing,
Signal should be supplied by special equipment, the behavior of applying the signal of relay
2
Foreword
protection tester directly is prohibited. (Optional)
When the device is equipped with ungrounded system, terminal D07, D08 are zero sequence
small current input terminal, the AC current input should be limited within 2A, the measuring
current input should be limited within 6A. When testing, pay attention to avoid large signal
applied so as to avoid damage to components.
Operating circuit inside the device is only applicable to DC power supply, if AC power is
used, it should be applied with rectifier and filter.
It is prohibited to plug or unplug the plug-ins, in order to avoid damage to the device.
It is prohibited to do digital output test when the device is running with primary equipments.
3
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
1. Product description
1.1 Scope of application
The MTPR-820Hc line protection and monitoring device applies to the line protection and
monitoring in ungrounded systems, systems grounded via an arc suppression coil or resistor with
voltage ratings, or grounded system solidly of below 110kV.
1.2 Function and specification
1.2.1 Protective function
3-step compounded voltage block directional over-current protection(Three-step OC)
Inverse time limit overcurrent protection
Negative sequence overcurrent protection
Overload protection
High-voltage side ground protection(HV ZS OC)
Low-voltage side ground protection(UV ZS OC)
Voltage protection (under-voltage protection and over-voltage protection) (Voltage Protect)
Body protection
Non-electric quantity protection(2 ways)(Can be selected or not)
Longitudinal differential protection(Diff.Protect)
1.2.2 Auxiliary function
Harmonic spectrum analysis
Phase display
Fault recorder
Integral energy
Self-checking fault alarm of device
Remote calling and modification of protection’s settings
One way (or two ways) programmable output of 4~20mA
Network print
Virtual correspondent node remote test
1.2.3 Monitoring function
Electric quantity(remote measuring quantity):voltage, current, active power, reactive power,
active energy, reactive energy, power factor, grid frequency, non-electric quantity measuring
(optional), etc.
Remote binary quantity: the device has 25-way binary input, in which: 20-way for external
gathering, and 5-way for internal gathering.
1.2.4 Communication capability
With industrial Ethernet port and standard RS485 multipoint communication port. Supports
MODBUS、IEC-60870-5-103(RS485 communication mode)、IEC-61850-5-104(Industrial
4
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Ethernet communication mode) standard communication protocol and a new generation of
substation’s communication standard IEC 61850.
Supports single and dual network communication, it is fully qualified for network
redundancy and backup
1.2.5 GPS clock synchronization function
The device is able to receive GPS clock second synchronization or IRIG-B through RS485
differential voltage, and it can be done with monitoring system to accomplish GPS precise
clock synchronization or Ethernet-based SNTP synchronization.
1.2.6 Device specifications
32-bit POWERPC microprocessor
Real-time multi-task operating system and C++ program techniques, realizing online
programming
320*240 LCD display, easy for inspection
One or two ways 4~20mA DC quantity output, which can be set flexibly as any
corresponding electric quantity (such as current, voltage, power, etc.)
Collecting 2 ways of 4~20mA DC quantities for measurement of non-electric quantities, such
as temperature, pressure, and realizing online monitoring. (optional)
Having the electric energy quality analysis function and perfect harmonic analysis function
Integrating perfect metering functions and Metrology Function
Support network printing function, include two ways: real-time print and artificial print
Support virtual correspondent node remote test, including remote communication to
correspondent node, remote measure to correspondent node, event to correspondent node, can
online testing, it is convenient for debugger to debug the device on-site.
Excellent hardware interchangeability, user maintenance is easily and it reduced quantity of
spare parts
Protection output relays can be configured flexibly for user convenience
Using a 6U, 19/3” standard enclosure in a rear plug-in structure. the device can be installed in
site on a switchboard or combined in a centralized manner
1.2.7 Main technical specifications
Rated data
Power supply: DC/AC 86~265V
Operating voltage: DC 220V or DC 110V
AC voltage: 100/ 3 V or 100V
AC current: 5A or 1A
Frequency: 50Hz
Power consumption
DC circuit: <10W (normal operation). <15W (protection operation)
AC voltage circuit: <0.5VA/phase
AC current circuit: <1VA/phase (In = 5A). <0.5VA/phase (In = 1A).
Overload capability
AC voltage circuit: 1.2Un, continuous operation
5
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Current measuring circuit: 1.2 In, continuous operation
Protective current circuit: 2In, continuous operation
10In, allowing 10s
40In, allowing 1s
Range and error of setting value
Maximum range of setting value:
Voltage element: 1V~120V
Current element: 0.1In~20In
Frequency: 45.00Hz~55.00Hz
Timing element: 0.00s~100.00s
Error of setting value:
Current and voltage setting value: ≤±3% of setting value
Frequency setting value: ≤±0.02Hz
Angle setting value: ≤±2°
Whole-group operation time (including relay’s intrinsic time): Intrinsic operating
time of current instantaneous over-current protection: not greater than 40ms at 1.2
times the setting value
Measuring accuracy
AC current: Class 0.2
AC voltage: Class 0.2
4~20mA DC quantity input: ≤±1%
Power: Class 0.5
Integral energy: Class 1 (active), Class 2 (reactive)
Frequency: ≤±0.02Hz
SOE resolution: ≤2ms
Pulse width of pulse quantity: ≥10ms
4~20mA DC quantity output: ≤±1%
Capacity of trip/closing output contact
Can be connected to DC 250V, 8A for prolonged periods.
GSP clock synchronization error
Clock synchronization error≤2ms
Environmental conditions
Ambient temperature:
Operating:-20℃~+55℃.
Storage:-25℃~+70℃, rainproof and snow-proof rooms with relative humidity not
greater than 80%, ambient air free of acid, alkaline or other corrosive and explosive gas. No
excitation quality is applied at the limits, the device shall not have any irreversible change.
After temperature restoration, the device shall operate properly.
Relative humidity:
The average relative humidity of the most humid month shall not be greater than 90%,
6
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
the average minimum temperature of this month not lower than 25℃ and there shall be no
surface condensation. At the highest temperature of +40℃, the average maximum humidity
shall not exceed 50%.
Atmospheric pressure: 80kPa~110kPa (below relative altitude of 2KM)
1.2.8 Hardware structure
The device uses a 6U, 19/3” standard enclosure, with aluminum alloy casing and installed by
overall embedding. The display panel is mounted in the front, and the other plug-in modules are
rear mounted. From the rear view, I/O, the power, CPU and AC plug-in modules are from the left
to the right.
External dimensions and boring diagram
Structural and dimensional diagram Boring diagram for installation
Devices fabricated on-screen steps: first release on-screen stents unfastening screws, remove
the stents. Install the device on the screen from the front and push until close to the fixed plate.
Install the stent 2, and then stent 1, and then use fastening screw to insertion hole from rear of
stent1, and then screwed into stent 2 and tighten screw. The stents from up and down are installed
in the same way. Use grounding screws to connect grounding line.
7
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
2. Function of device
2.1 3 sections of compounded voltage block directional overcurrent protection
This device has 3 sections of compounded voltage block overcurrent protection. They are
instantaneous over-current protection, the time-limit instantaneous over-current protection,
over-current definite-time limit protection respectively. The current and time setting values of
each section can set separately. When the maximum phase current is greater than the setting
value of the current, and the negative sequence voltage (the negative sequence voltage is
synthesized from the phase voltages) or Under-voltage (being the line voltage; if one or more of
the 3 line voltages is/are less than the Under-voltage setting value, Under-voltage component
operates to open the over-current protection) condition is met, it will operate on trip after a delay.
The protection operation logic is shown in figure 2-1(using instantaneous over-current protection
as an example).In addition, after the operation of the compounded voltage component, a contact
can be output separately at the corresponding position. (The precondition to operation of the
compounded voltage component is the current is not zero.)
Note: the negative sequence voltage (U2) is compound by each phase voltage, low voltage
is the minimum value of three phase line voltage.
8
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Umin<Low-voltage
compounded
setting value voltage block
On/Off O ver-current U2>negative sequence ≥1 instantaneous
voltage setting value protection On/Off Protection
Ia≥Over-current & T output
instantaneous setting value sequence
Ib≥Over-current instantaneous
setting value ≥1
Ic≥Over-current instantaneous
setti ng value
Figure 2-1 Operation logic of compounded voltage lock over-current protection
2.2 Inverse time limit over-current protection
As stipulated by the IEC (IEC255-4), the following 4 standard characteristic equations are
usually used. The user may select one as the case may be:
t 0.14 0.02 p
Standard inverse time limit: ( I / I p ) 1 (1)
13.5
Unusual inverse time limit: t ( I / I )
1 p (2) p
t 80 2 p
Extreme inverse time limit: ( I / I p ) 1 (3)
120
Long inverse time limit: t (I / I ) 1
p (4)
p
Where: I is the fault current, Ip is the setting value of the inverse time limit starting current,
τp is the transformer’s overcurrent inverse time limit constant, corresponding to the overload
capacity of the transformer, derived from calculation.
When the amplitude of the inverse time limit overcurrent of any of phases A, B and C is
greater than the setting value of the inverse time limit starting current, the device will operate on
trip according to the inverse time limit characteristic curve. The software makes selection by
inverse time limit characteristic control word. The protection operation logic is shown in Figure
2-2.
Note: Imax=max{Ia,Ib,Ic},the same below
Inverse time
limit over- T
Imax>Ip current On/Off Protection output
sequence
Figure 2-2 Operation logic of inverse time limit over-current
2.3 Negative sequence overcurrent protection
By processing of the currents of Phases A, B and C, the negative sequence current is
calculated. The negative sequence overcurrent protection is available in the definite time limit
and inverse time limit modes.
Negative sequence overcurrent definite time limit:If the negative sequence current exceeds
the setting of negative sequence current, the device will operate on trip.
9
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Negative sequence overcurrent inverse time limit:Having four characteristic curves for
choice, the same as the high voltage side inverse time limit overcurrent protection.
To avoid any potential protection false operation arising from the asynchronism of the 3
phases upon closing of the circuit breaker, the set delay shall not be less than 0.2S.
2.4 Overload protection
For Phases A, B and C, when the maximum phase current is greater than the overload
setting value, there will be an operation after a delay. The protection output may elect to operate
on signal or trip. The protection operation logic is shown in Figure 2-3.
Overload On/Off
Imax>Overload T Protection output
setting value sequence
Figure 2-3 Operation logic of overload protection
2.5 High-voltage side ground protection
The zero sequence current uses special zero sequence CT, which can detect the primary
cable zero sequence CT current accurately. When the current exceeds the setting value and the
setting delay is reached, the protection will operate. The protection output may operate on signal
or trip.
I0> zero sequence Protection On/Off T Protection output
curre nt setting value sequence
Figure 2-4 Operation logic of high-voltage side ground protection
2.6 Low-voltage side ground protection
The low-voltage zero sequence overcurrent protection is available in the definite time limit and
inverse time limit modes, the same as the negative sequence overcurrent protection.
2.7 Voltage protection
2.7.1 Under voltage protection
The device judges the maximum line voltage value, if it is lower than the setting value
and the setting delay is reached, the protection will operate on trip and is blocked by the switch
position, and PT failure. The protection operation logic is shown in Figure 2-5.
Circuit breaker at
closed position
Umax<Uddy
&
Undervoltage on/off Protection
& T output PT failure PT failure block sequence
Figure 2-5 Operation logic of Under-voltage protection
To avoid any potential protection false operation upon closing of the circuit breaker, the setting
10
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
delay shall not be less than 0.2S.
2.7.2 Overvoltage protection
The device judges the maximum line voltage value, if it is greater than the setting value
and the setting delay is reached, the protection will operate on trip and is blocked by the switch
position. The protection operation logic is shown in Figure 2-6.
C ircuit breaker at
closed position
Over-voltage on/off
& T Protection
Um ax〉Ugdy output on/off
Figure 2-6 Operation logic of Overvoltage protection
2.8 Body protection
The device has 5 body protections, such as heavy gas trip, light gas alarm, Over temperature
trip, temperature alarm and pressure relief protection. The operation contact signal operates on trip
or alarm subject to CPU processing, and its operating time is recorded by the software.
2.9 Non-electric quantity protection(Can be selected or not)
The device has the 2-way non-electric quantity protection function, switched on/off by
control word, which are used for trip.
2.10 PT failure alarm
The judgment criterion of PT failure depends on the wiring mode. When the PT failure
block function is enabled, if PT failure occurs, the device will exit from judgment of Undervoltage
protection and compounded voltage block component. The judgment criterion of PT failure is as
follows:
The current value of the phase with the maximum current is less than the maximum load
current (using the setting value of the overload current).
① Maximum inter-phase voltage < 30V, and current of any phase > 0.1In;
② Negative sequence voltage > 8V
If any of the above conditions is met, the delay (settable) will report PT failure, and will
return when failure disappears.
Max{ Ia,Ib,Ic}<Igfh
MaxU<30V
& PT failu re on/off PT failure
Max{Ia,Ib,Ic}>0.1*In & TPT operation
≥ information
U2>8V
MaxU=Max(Uab,Ubc,Uca)
MinU=Min(Uab,Ubc,Uca)
Figure 2-7 PT failure judgment logic
11
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
2.11 CT failure alarm(CT Failure Alarm)
This protection device sets CT failure for both high and low voltage side separately. When
the CT failure function is turned on, if any of the high or low voltage side’s CT failure occurs, the
device sends alarm signal.
Among the protection CT of both high and low voltage side, when the current value of any
phase exceeds the setting value of the overload protection current, CT failure detection will be
disabled.
Protection CT 3-phase wiring
During normal operation, the sum of the 3 phase currents is zero (less than 0.1 times the
rated current). In case of CT failure in any phase, the sum of the 3 phase currents is not zero
(greater than 0.1 times the rated current). To differentiate from ground fault, the following
judgment is required:
①In the 3 phase currents, the value of the phase with the minimum current is zero (less than
0.1 times the rating current).
②The value of the phase with the maximum current is not zero (greater than 0.1 times the
rated current), but less than the setting value of the overload current.
Protection CT 2-phase wiring
A phase is greater than 0.15In and less than the setting value of the overload current. A
phase less than 0.08 In is judged as CT failure.
Above-mentioned judgment is applicable to high and low voltage side CT failure. For high
voltage side CT failure, the setting value of overload current is the setting value of the overload
protection’s current, to be set in “Overload” in menu “Setting Value”; For low voltage side CT
failure, the setting value of overload current is the setting value of the low voltage side overload
protection’s current, to be set in “Failure Alarm” in menu “Setting Value”.
2.12 Operate circuit break
This function can be selected or not..When this function be selected, the device monitoring the
HWJ and TWJ states. If HWJ and TWJ both On or Off, the delay (settable) will report operate
circuit break, and will return when failure disappears.
2.13 Under-frequency unloading protection(Under-frequency)
The frequency is derived from software calculation, use the frequency of UAB. The
unloading protection is blocked by under-voltage block, under-current block or slip block, in
which slip block can be switched On/Off. The operation logic of under-frequency unloading is
shown in Figure 2-8.
12
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
F<Fdpjz Low-frequency
Df/dt<Dfdt unloading
protection on/off Tdpjz Protection output
Imax>Idzh & sequence
Uab>Udz
Figure 2-8 Operation logic of under-frequency unloading
2.14 Longitudinal differential protection(Diff.Protect)
2.14.1 Differential instantaneous over-current protection(Inst.Diff.PROT)
The differential instantaneous over-current protection operates quickly when there is a
serious fault in the transformer. When any phase’s differential current is greater than the
differential instantaneous over-current setting value, there will be an instantaneous operation on
the output. The protection operation logic is shown in Figure 2-9.
Differential instantaneous current compute formula is shown as follows:
Idif I1 K phI2
I1 is current of the high voltage side
K ph is equilibrium coefficient of the low voltage side(set in menu “System
Parameters”)
I2 is current of the low voltage side.
Iadif>difference instantaneous
current setting value
Difference Ibdif>difference instantaneous Protection output instantaneous on/off sequence
current setting value ≥
Icdif>difference instantaneous
current setting value
Figure 2-9 Operation logic of differential instantaneous protection
2.14.2 Percentage differential protection(Per.Diff.PROT)
The 3-broken-line percentage differential principle applies to transformer percentage
differential protection, with the operation equation of:
I I
When Ires < Ir1, dif do
When Ir1 < Ires < Ir2 I, dif - Ido Kres1 Ires - Ir1
Ires > Ir2 Idif - Ido - Kres1 Ir2 - Ir1 Kres2 I - IWhen , res r2
If any of the above conditions is met, the percentage differential protection will
operate.
I
Where: dif is the differential current Idif I1 K phI2 ;
Ido is the setting value of the differential threshold current;
13
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Ires is the braking current; Ires = Idif - I1 - K phI2 ;
Ir1 is the braking current of Inflexion point 1;
Ir2 is the braking current of Inflexion point 2;
Kres1 is Percentage factor 1;
Kres2 is Percentage factor 2;
I1, I 2 are secondary side currents of the current transformer on the high-voltage side and
low-voltage side respectively. The current transformers on both sides are wired in the Y type and
pointed to the transformer. By setting the unbalance factor and wiring mode, the device can adjust
the amplitude and phase of the currents on both sides automatically.
The percentage differential protection can ensure the external short-circuit does not
operate and has high sensitivity when there is an internal fault.
I d if
I d o
I r1 I r2 I re s
Figure 2-10 Differential operation curve
Using control word, you can elect whether to block percentage differential protection via
instantaneous CT failure sends alarm signal at the same time.
Harmonic braking equation:
I / I K
h.x dif.x xb
Where I: h.x is second harmonic component of differential current;
I
dif .x is differential current of every phase;
Kxb second harmonic braking coefficient, to be set for the excitation surge when
transformer no-load closing is avoided.
If the percentage of second harmonic component in differential current is greater than the
setting coefficient, then judge unbalanced current which produced by transformer excitation surge
making operation of percentage differential protection, so block percentage differential protection
at that time.
2.14.3 Differential current over-limit alarm(Diff.C OL Alarm)
If the differential current of any phase is greater than the setting value, the device will send
alarm signal after 10s.It can discover inner trouble of transformer to inform inspector to examine
and repair in time.
14
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Ia2>d ifference current over-limit setting value
Ib2>difference current over-limit DIfferential current over- Protection output
setting value limit alarm On/Off sequence≥
Ic2> difference current over-limit
setting value
Figure 2-11 logic of differential current over-limit alarm
2.15 Pulse Energy/integral energy(Can be selected or not)
Pulse Energy
The impulse circuit of the device uses an internal power supply; passive energy impulses are
input from the outside; and accumulation of Pulse Energy is finished by the software.
Integral energy
The software accumulates active and reactive powers into active and reactive energy in real time.
2.16 Fault recorder
See the communication coding table for the protection voltage and current waveform data
collected by the recording unit.
2.17 Network print
Device supports network printing function, can print remote control information, soe
information and the setting parameter list. The printer IP address must been set rightly on the
device (the network segment of printer must be as same as that of device IP addresses), then
connect a printer, put on "real-time report print ", it can print the current remote control
information or SOE information when device is connected to the back-ground (including remote
communication shift, protection action), and can print the current SOE information when device is
not connected to the background. In addition, when press the "ok" button in the "print report" or
"print setting value" menu, it can print the all setting parameter or the all report information,
including action value.
2.18 Virtual correspondent node remote test
The function is used to complete the communication node remote test of the device, do not
need to access the actual analog electric quantity or the input quantity. Specific operation as
follows, connect to the background, In the remote test menu, operate the “virtual input test”, the
“virtual measure test” and the “virtual SOE test” menu in the “remote test” menu, press the "OK"
button after the modification of various settings, then by observing the background pop-up
warning window or the change of the corresponding value, to determine whether the device
communication node is right. It is convenient for debugger to debug the device on-site. When you
are in the mode of remote test, the all protect must be off.
2.19 GPS clock synchronization
The GPS clock synchronization signal is input as rs485 differential voltage, the device is able
15
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
to receive GPS clock second synchronization. If there is GPS signal, there will be flashing on
the bottom of cycle menu. Otherwise won’t.
The principle of GPS clock synchronization: The second pulse or minute pulse act with the
monitoring system, the time base with second precision is sent by monitoring system, when the
GPS second differential signal arrives, the time base is unified and the milliseconds are cleared.
The device is able to receive GPS clock second synchronization or IRIG-B through RS485
differential voltage, and it can be done with monitoring system to accomplish GPS precise clock
synchronization or Ethernet-based SNTP synchronization.
2.20 Overhaul status
When the device put into overhaul plate, remote sign, remote measure can uploading
background computer. But the device can’t remote control by background computer. The SOE
event、Alarm event、Trip event, etc also can’t uploading background computer.
3. Setting of parameters and setting values of the device
3.1 System parameters
Parameter Range Description
Settings of setting value zone number(Setting Zone No.)
Setting value zone
0-7 Set step:1(factory default 0)
number(Setting Zone No.)
Communication settings(Comm. Setting)
NET Protocol 0-2 Set step :1 (factory default 1)
(0-Quit;1-IEC104; 2-IEC61850)
RS485 Protocol 0-2 Set step :1 (factory default 0)
(0-Quit;1-IEC103; 2-Modbus)
RS485 address(RS485
1-99 Set step:1(factory default 1)
Address)
RS485 baud rate(RS485 Set step:1(factory default 2)0:2.4KB;1:4.8KB;
0-5
Baudrate) 2:9.6KB;3:19.2KB;4:38.4KB;5:115.2KB;
IP address(IP Address) One section set step:1(factory default 192.168.0.253)
SNTP Address (SNTP It has four
One section set step:1(factory default 192.168.0.254)
Address) sections. The
KW default value(KW range of every
One section set step:1(factory default 12.8.6.1)
Default) section is
Printer IP address(Printer 0-255
One section set step:1(factory default 192.168.0.134)
IP)
16
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Parameter Range Description
Coefficient of transformer
PT Ratio 1-1500 Set step: 1 (factory default 1)
CT Ratio 1-5000 Set step: 1 (factory default 1)
Setting of basic parameters(B. Parameters)
Rating Current(In) 0-1 Set step: 1 (factory default 0) 00: 5A. 01: 1A
CT Wiring Mode 0-1 Set step: 1 (factory default 0) 00: 3-phase. 01: 2-phase
PT Wiring Mode 0-1 Set step: 1 (factory default 0) 00: Y-Y. 01: V-V
For harmonic calculation, select the corresponding
reference quantity:
Harmonic Channel 0-12 0:exit from harmonic calculation function
1:Ia1,2:Ib1,3:Ic1,4:I0,5:IA,6:IC,7:I0L,8:Uab,
9:Ubc,10:Ia2,11:Ib2,12:Ic2
Wave Record 0-1 Set step:1(factory default 0)00:Off;01:On
00:ungrounded
Earth Mode 0-1 01:grounded
(While ordering if have no special elucidation then
according to ungrounded mode allocation)
Remote communication
10-100ms Set step: 1 (factory default 40ms)
ack time (input ack time)
0:YD-11,1:YD-1,2:DY-1,3:DY-11,4:YY-12
Transformer wiring Mode 0-4
(factory default 0)
Low-voltage side balance
0-10 Set step: 0.01 (factory default 1)
coefficient
Measure IB Set step: 1 (factory default 0)
0-1
compound(IB compound) 00:non-compound;01:compound
Remote/Local switch 0-1 Set step: 1 (factory default 0) 00:exit;01:on
Real-time print report
0-1 Set step: 1 (factory default 0) 00:exit;01:on
on/off(auto print report)
Display Mode 0-1 Set step: 1 (factory default 0) 00:Diagram;01:Analog
D/A channel setting(D/A Setting)
Select DA1~2 to output corresponding reference
DA1~2 Channel quantities:
0-7
Selection 0: No D/A output 1:IA,2:IC,3:Uab,4:Ubc,5:Uca,6:P,7:Q
Voltage reference quantity: 0-120V corresponding to
17
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Parameter Range Description
4mA-20mA.
Rating 5A:
Current reference quantity: 0-6A corresponding to
4mA-20mA,
Power reference quantity: 0-1000W corresponding to
4mA-20mA.
Rating 1A:
Current reference quantity: 0-1.2A corresponding to
4mA-20mA,
Power reference quantity: 0-200W corresponding to
4mA-20mA.
DA1~2 Adjustment
0.5-1.5 Adjust D/A channel 1~2(4-20mA) parameters
Factor
Integral Energy
0-4294967.295k
Positive active energy
Wh
0-4294967.295k
Positive reactive energy
vh Set step:0.001
0-4294967.295k Press “confirm” for reservation, and revert to last menu.
Negative active energy
Wh
0-4294967.295
Negative reactive energy
kvh
Channel factor setting(Channel Coef.)
Set step:0.001(factory default 1)
Channel data 1~12 0.5-1.5 Channel data 1-12 are corresponded to the channel factor
of analog quantity 1-12.
Set step:0.001(factory default 1)
Channel data 13~14 0.5-1.5 Channel data 13,14 are corresponded to channel factor of
DC quantity 1,2.
18
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
3.2 List of setting values
Setting value Range Description
Instantaneous Overcurrent
Protection On/Off 1/0 1/0:On/Off (factory default Off)
(Inst.PROT)
The time Delay Instantaneous
Overcurrent Protection On/Off 1/0 1/0:On/Off (factory default Off)
(Delay Inst.PROT)
Overcurrent Definite-time Limit
Protection On/Off 1/0 1/0:On/Off (factory default Off)
(DT Overcurrent)
Instantaneous Overcurrent
Compounded Voltage Lock On/Off 1/0 1/0:On/Off (factory default Off)
(Inst. CV Lock)
The time delay Instantaneous
Compounded Voltage Lock On/Off 1/0 1/0:On/Off (factory default Off)
(Delay CV Lock)
Overcurrent Definite-time Limit
Compounded Voltage Lock On/Off 1/0 1/0:On/Off (factory default Off)
(DT OC CV Lock)
Inverse time Limit Overcurrent
Protection On/Off 1/0 1/0:On/Off (factory default Off)
(IT Overcurrent)
Negative sequence over-current 1/0 1/0: On/Off (factory default Off)
definite time limit (NS OC DT)
Negative sequence over-current 1/0 1/0: On/Off (factory default Off)
inverse time limit (NS OC IT)
Overload alarm (Overload Alarm) 1/0 1/0: On/Off (factory default Off)
Overload trip 1/0 1/0: On/Off (factory default Off)
(Overload Trip)
Zero sequence over-current
Section I 1/0 1/0: On/Off (factory default Off)
(ZS OC 1 Trip)
Zero sequence over-current 1/0 1/0: On/Off (factory default Off)
Section II (ZS OC 2 Trip)
Zero sequence over-current 1/0 1/0: On/Off (factory default Off)
Section III alarm (ZS OC 3 Alarm)
Zero sequence over-current 1/0 1/0: On/Off (factory default Off)
Section III trip (ZS OC 3 Trip)
19
Protection on/off word
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Setting value Range Description
Under-voltage zero sequence
definite time limit over-current 1/0 1/0: On/Off (factory default Off)
(UV ZS OC DT)
Under-voltage zero sequence
inverse time limit over-current 1/0 1/0: On/Off (factory default Off)
(UV ZS OC IT)
Under-voltage
1/0 1/0: On/Off (factory default Off)
protection(Undervoltage)
Over-voltage
1/0 1/0: On/Off (factory default Off)
protection(Overvoltage)
Heavy gas trip 1/0 1/0: On/Off (factory default Off)
(Heavy Gas Trip)
Light gas alarm 1/0 1/0: On/Off (factory default Off)
(Light Gas Alarm)
Over-temperature trip(Over 1/0 1/0: On/Off (factory default Off)
Temp.Trip)
Temperature alarm(Temperature 1/0 1/0: On/Off (factory default Off)
ALM)
Pressure relief trip(P-relief Trip) 1/0 1/0: On/Off (factory default Off)
Non-electric quantity 1 protection 1/0 1/0: On/Off (factory default Off)
(Non-electric 1)
Non-electric quantity 2 protection 1/0 1/0: On/Off (factory default Off)
(Non-electric 2)
PT failure alarm 1/0 1/0: On/Off (factory default Off)
(PT Failure Alarm)
PT failure block 1/0 1/0: On/Off (factory default Off)
(PT Failure Lock)
CT failure alarm 1/0 1/0: On/Off (factory default Off)
(CT Failure Alarm)
Compounded voltage contact
output 1/0 1/0: On/Off (factory default Off)
(CV Point Output)
Under-frequency unloading 1/0 1/0: On/Off (factory default Off)
(Under-frequency)
Slip block(Slip Lock) 1/0 1/0: On/Off (factory default Off)
Differential instantaneous
over-current protection 1/0 1/0: On/Off (factory default Off)
(Inst.Diff.PROT)
Percentage differential protection 1/0 1/0: On/Off (factory default Off)
(Per.Diff.PROT)
20
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Setting value Range Description
Overcurrent protection
Undervoltage block
10.00-90.00V Set step:0.01V(factory default 90V)
(Undervoltage)
Negative sequence voltage
block 2.00-30.00V Set step:0.01V(factory default 10V)
(NS Voltage)
Instantaneous current
0.10-100.00A Set step:0.01A(factory default 100A)
(Inst.Current)
Instantaneous delay
0.00-100.00s Set step:0.01s(factory default 100s)
(Inst.Time)
The time delay instantaneous
current 0.10-100.00A Set step:0.01A(factory default 100A)
(Delay Inst.C)
The time delay instantaneous
delay 0.00-100.00s Set step:0.01s(factory default 100s)
(Delay Inst.Time)
DT overcurrent
0.10-100.00A Set step:0.01A(factory default 100A)
(DT Overcurrent)
DT overcurrent
0.00-100.00s Set step:0.01s(factory default 100s)
(DT OC Time)
Overcurrent inverse time limit protection
Inverse time limit characteristic
curve 1-4 Set step:1(factory default 1)
(IT Trait Curve)
Inverse time limit constant
0.00-1.00s Set step:0.01S (factory default 1s)
(IT Time Contant)
Inverse time limit starting
current 0.10-100.00A Set step:0.01A(factory default 10)
(IT Start Current)
Negative sequence overcurrent
Negative sequence current
0.00-100.00A Set step:0.01A(factory default 100A)
(NS DT Current)
Negative sequence overcurrent
Set step:0.01s(factory default 100s)
delay 0.00-100.00s
(NS DT Time)
21
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Setting value Range Description
Negative sequence inverse Set step:1(factory default 1)
time limit characteristic curve 1-4
(NS IT Curve)
Negative sequence inverse
time limit constant 0.00-1.00s Set step:0.01S (factory default 1s)
(NS IT Constant)
Negative sequence inverse
time limit starting current 0.10-100.00A Set step:0.01A(factory default 10)
(NS IT Start C)
Overload
Overload current
0.10-100.00A Set step:0.01A(factory default 100A)
(Overload Current)
Overload delay
0.00-100.00s Set step:0.01s(factory default 100s)
(Overload Time)
High-voltage side zero sequence overcurrent
Setting value of Zero sequence
overcurrent Section I Set step: 0.01A 0.00-100.00A
(factory default 2A)
(ZS Overcurrent 1)
Zero sequence overcurrent Set step: 0.01S
Section I delay 0.00-100s (factory default
(ZS OC 1 Time) 100s) Standard products
Setting value of Zero sequence are designed based
overcurrent Section II Set step: 0.01A 0.00-100.00A on a neutral point
(factory default 2A)
(ZS Overcurrent 2) ungrounded
Zero sequence overcurrent Set step: 0.01S system. Specify
Section II delay 0.00-100s (factory default any other mode
(ZS OC 2 Time) 100s) upon ordering if
Setting value of Zero sequence any
overcurrent Section III Set step: 0.01A 0.00-100.00A
(factory default 2A)
(ZS Overcurrent 3)
Zero sequence overcurrent Set step: 0.01S
Section III delay 0.00-100s (factory default
(ZS OC 3 Time) 100s)
Low-voltage side zero sequence overcurrent
Setting value of low-voltage
0.10-100.00A
zero sequence current Set step: 0.01A (factory default 100A)
(DT Current)
Definite time limit delay 0.00-100.00s Set step: 0.01s (factory default 100s)
22
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Setting value Range Description
(DT Time)
Inverse time limit characteristic
curve selection 1-4 Set step: 1 (factory default 1)
(IT Trait Curve)
Inverse time limit constant
0.00-1.00s Set step: 0.01S (factory default 1s)
(IT Time Contant)
Inverse time limit starting
0.10-100.00A
current Set step: 0.01A (factory default 10A)
(IT Start Current)
Voltage protection
Undervoltage setting value
10.00-90.00V Set step: 0.01V (factory default 90V)
(Undervolt. Value)
Undervoltage delay
0.10-100.00s Set step: 0.01S (factory default 2s)
(Undervolt. Time)
Overvoltage setting value
90.00-150.00V Set step: 0.01V (factory default 110V)
(Overvolt. Value)
Overvoltage delay
0.10-100.00s Set step: 0.01S (factory default 2s)
(Overvolt. Time)
Failure setting value
PT failure delay
0.50-100.00S Set step: 0.01S (factory default 10S)
(PT Failure Time)
CT failure delay
0.50-100.00S Set step: 0.01S (factory default 10S)
(CT Failure Time)
Low voltage side overload
current
(Only used for low-voltage 0-100.00A Set step: 0.01A (factory default 100A)
side CT failure criterion)
(UV Side Overload)
Non-electric quantity protection
Setting value of Non-electric
quantity 1 current(Non-elec.1 4.00-20.00mA Set step: 0.01mA (factory default 20mA)
Value)
Setting value of Non-electric
quantity 1 delay (Non-elec.1 0.00-100.00S Set step: 0.01S (factory default 100S)
Time)
Setting value of Non-electric
quantity 2 current 4.00-20.00mA Set step: 0.01mA (factory default 20mA)
(Non-elec.2 Value)
23
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Setting value Range Description
Setting value of Non-electric
quantity 2 delay (Non-elec.2 0.00-100.00S Set step: 0.01S (factory default 100S)
Time)
Under-frequency unloading
Setting value of
under-frequency unloading 45.00-50.00Hz Set step: 0.01Hz (factory default 48Hz)
(Under-freq.Value)
Setting value of
under-frequency unloading 0.50-100.00S Set step: 0.01S (factory default 5S)
delay(Under-freq.Time)
Setting value of
under-frequency unloading low
current block(Low Current 0.2-5A Set step: 0.01A (factory default 2A)
Lock)
Setting value of
under-frequency unloading
under-voltage block(Undervolt. 10.00-90.00V Set step: 0.01V (factory default 90V)
Lock)
Setting value of
under-frequency unloading slip 0.5-10.00Hz/s Set step: 0.01Hz/s (factory default 1Hz/s)
block(df/dt Lock)
Longitudinal differential protection
Differential protection Sudden
change quantity(Abrupt 0.1-10.00A Set step: 0.01A (factory default 1A)
Current)
Setting value of differential
instantaneous over-current 0.1-100.00A Set step: 0.01A (factory default 100A)
current (Inst.Diff. C)
Percentage differential 0.1-100.00A Set step: 0.01A (factory default 100A)
threshold current (Per.Diff. Sill)
Percentage differential braking
inflexion point 0.1-20.00A Set step: 0.01A (factory default 5A)
1(Per.Res.Inflex.1)
Percentage differential braking
inflexion point 0.1-20.00A Set step: 0.01A (factory default 5A)
2(Per.Res.Inflex.2)
Percentage braking coefficient
1 0.00-1.00 Set step: 0.01 (factory default 1)
(Restraint Coef.1)
Percentage braking coefficient
2 0.00-1.00 Set step: 0.01 (factory default 1)
(Restraint Coef.2)
Second harmonic braking 0.00-1.00 Set step: 0.01 (factory default 1)
coefficient (Sec.Res.Coef.)
24
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Setting value Range Description
Differential over limit current
value 0.1-100.00A Set step: 0.01A (factory default 100A)
(Diff.C OL Value)
Operate circuit break
Operate CIR Time 1.00-100.00S Set step:0.01s(factory default 3s)
4. Description of binary input, output and analog quantity
4.1 Monitoring of analog quantities
Analog quantities can be monitored under the [Protection Data], [Measured Data] and [Pulse
Energy] menus in the [Run States] menu, press the “”, “” keys to flip over. The factory
precision of the device has been calibrated. The protection current is calibrated at double the rated
current and the measuring current at a single rated current. The list is as follows:
Note: for protection CT 3-phase, PT Y-Y wiring. due to the under-frequency unloading
protection of this device, the frequency display is put in the protection data.
Analog quantity Analog quantity
Test method
terminal name
Terminals D01, Protection Phase A Add double the rating, displayed deviation not
D02 current (Ia1) exceeding 1%
Protection Phase Add double the rating, displayed deviation not
Terminals D03, D04
B current (Ib1) exceeding 1%
Protection Phase Add double the rating, displayed deviation not
Terminals D05, D06
C current (Ic1) exceeding 1%
Zero sequence
Terminals D07, D08 Add 1A, displayed deviation not exceeding 0.2%
current (I0)
Measurement
Add a single rating, displayed deviation not
Terminals D09, D10 Phase A current
exceeding 0.2%
(IA)
Measurement
Add a single rating, displayed deviation not
Terminals D11, D12 Phase C current
exceeding 0.2%
(IC)
Low-voltage side
Add double the rating, displayed deviation not
Terminals D13, D14 zero sequence
exceeding 0.2%
current (I0L)
AB wire voltage
Terminals D15, D16 Add 50V, displayed deviation not exceeding 0.5%
(Uab)
F system Add 50V 50Hz, displayed deviation not exceeding
Terminals D15, D16
frequency ±0.02Hz
BC wire voltage
Terminals D17, D18 Add 50V, displayed deviation not exceeding 0.2%
(Ubc)
Low-voltage side
Add double the rating, displayed deviation not
Terminals D19, D20 Phase A current
exceeding 1%
(Ia2)
25
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Analog quantity Analog quantity
Test method
terminal name
Low-voltage side
Add double the rating, displayed deviation not
Terminals D21, D22 Phase B current
exceeding 1%
(Ib2)
Low-voltage side
Add double the rating, displayed deviation
Terminals D23, D24 Phase C current
not exceeding 1%
(Ic2)
4~20mA DC Input
Terminals D25、D26 Add 10mA, displayed deviation not exceeding 1%
1
4~20mA DC Input
Terminals D27、D28 Add 10mA, displayed deviation not exceeding 1%
2
Terminals D09、
D10;D13、D14 add
Add a single rating to current and 100V to line voltage
current by polarity;D15、
3-phase active power Alter phase angle, displayed power deviation not
D16;D17、D18;D19、 exceeding 0.5%
D20 add voltage by
polarity
Terminals D09、
D10;D13、D14 add
Add a single rating to current and 100V to line voltage
current by polarity;D15、 3-phase reactive Alter phase angle, displayed power deviation not
D16;D17、D18;D19、 power exceeding 0.5%
D20 add voltage by
polarity
4.2 Monitoring of binary input
Binary input can be monitored under the [Binary input] menu in the [Run States] menu, press
the “”, “” keys to flip over.
Binary input Binary input name Test method
terminal
B01 Common terminal of binary input - External power supply of 220V or 110V DC
(Should be connected to DC220V can be applied, connect the negative terminal
or DC110V to terminal B01, positive terminal to terminal
negative terminal of external power B02~B21, in [Binary input] menu in the
supply) [Run States], the status of binary input can be
B02 Breaker position seen.
B03 Trolley run position The device also has a 24V DC supply, if
26
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
B04 Trolley test position it is used, terminal B22 can be connected to
B05 Earth switch position terminal B02~B21, in [Binary input] menu in
B06 Spring is not energized the [Run States], the status of binary input can
B07 Heavy gas trip be seen.
(Heavy Gas) “Manual Trip”, “Manual Close” , “TWJ” ,
B08 Light gas warning “HWJ” are taken from the operate circuit to
(Light Gas) monitoring the status.
B09 Over temperature trip Connect the negative terminal to terminal
(Over T Trip) A11 (-KM), positive terminal to terminal A06
B10 Temperature warning (Manual Close), A08(Manual Trip),in [Binary
(Temp. Alarm) input] menu in the [Run States], the status of
B11 Input 10 binary input can be seen.
B12 Input 11 Connect the positive terminal to terminal
B13 Input 12 A12(+KM), negative terminal to terminal
A05(TWJ),A04(HWJ),in [Binary input] menu
B14 Input 13
in the [Run States], the status of binary input
B15 Input 14
can be seen.
B16 Input 15
Connect the negative terminal to terminal
B17 Input 16
A11(-KM),positive terminal to terminal
B18 Input 17
A14(Remote common),in [Binary input]
B19 Input 18
menu in the [Run States], the Remote/Local
B20 Input 19 status of binary input can be seen.
B21 Overhaul Please note about the binary input voltage
Binary input Manual Trip upon ordering, it is set to DC220V by default.
of Operate Manual Close
circuit HWJ
TWJ
Remote/Local
B22 Positive terminal of internal 24V
power supply
4.3 Monitoring of binary output
Binary output can be monitored under the [Binary output] menu, press the ““, ““ keys to
flip over.
Binary output terminals Binary output name Test method
B23-B24 Trip Signal Select open and close menu, use “+”, “-”
B23-B25 Alarm Signal key to operate and test the corresponding
B23-B26 Operate CIR Signal terminals. A29-A30 and A31-A32 are
A17-A18 PROT Output 1 common open terminals that should close.
27
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
A19-A20 PROT Output 2
A21-A22 Output 3
A23-A24 Output 4
A25-A26 Output 5
A27-A28 Output 6
A29-A30 Output 7
A31-A32 Output 8
A14-A16 Remote Trip
A14-A15 Remote Close
5. Operation instructions
5.1 Control panel of device
320*240 matrix LCD (The LCD will go off after a period of absence of keyboard operation. the
LCD will be illuminated automatically when any key is pressed or in case of protection trip or
alarm.)
Signal indicator: run, communication, trip, alarm, device fail, backup, remote.
Key pad: , , , , Cancel, -, +, Enter, Revert
5.2 Instructions for use of key pad and LCD display
During the device’s normal operation, it will display the primary measuring current、voltage、
power, secondary protective data、measuring data、device address、time and statue (indicating
whether reclosure charging is finished) in cycle. Press the “Enter” key to enter the main menu,
which is a multi-level tree menu. Press the ““, ““ keys to move the cursor to the desired entry,
press the “Enter” key to enter this entry, and press the “Cancel” key to return to the next higher
28
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
level of screen. If this screen is still a menu, continue to press the ““, ““ key to select the
desired entry, press the “Enter” key to enter the next level of screen, and press the “Cancel” key
to return to the next higher level of menu. If there is no menu screen, be sure to press the “Cancel”
key to return to the next higher level of menu. The main menu is shown at the center of the
following figure, with the corresponding submenus on both sides.
01.Run States -1/8-
Protection Data Main menu
Measuring Data 05.Report Dis. -1/4-
Binary Input
01.Run Status Trip Report
Soft Strap Binary Report
Pulse Energy 02.Run Parameters Event Report
Harmonic Data
03.Setting View 06.Parameters -1/6-
02.Run Param. -1/3-
Setting Zone No. 04.Setting Value Comm. Setting Transformer Coe.
PROT On/Off 05. Report Manage B. Parameters
D/A Setting
03.Setting View-1/16-
06. SYS Parameters Pulse Energy 3-overcurrent
Inverse time limit 07.Device Test 07.DeviceTest. -1/2- overcurrent Output Test
N-seq. overcurrent
08.PassWord Lamp Test04.Setting Value-1/16-
3-overcurrent 09.Version Info.
Inverse time limit 08.Password
overcurrent 10.Comm Test □□□□
N-seq. overcurrent
PROT AUTO DEV V2.00
Type:MTPR-820Hc
10.Comm test ID:□□.□□.□□
Input Test CRC:□□□□□□□□
Measure Test Date:201XX-XX-XX
Note 1:For the Setting menu, see the description of each device.
Run Status
The [Run Status] menu contains 8 submenus, including protection data, measuring data,
binary input, soft strap, pulse energy, harmonic data, DC measurement and trip statistics, AD
voltage data. It is described as follows:
29
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
PROT Data -1/14-
Ia1 = □□□·□□ A
000.0° High voltage side protection currents
Ib1 = □□□·□□ A
000.0° PT secondary line voltage value
Ic1 = □□□·□□ A
High voltage side protection positive sequence current
000.0° High voltage side protection negative sequence current
Uab = □□□·□□ V 000.0°
Ubc = □□□·□□ V 000.0°
Uca = □□□·□□ V 000.0°
Meas. Data -1/10-
IA = □□□·□□ A 000.0°
Measuring CT secondary current value
IB = □□□·□□ A 000.0°
IC = □□□·□□ A 000.0° Converted to PT, CT secondary active power
P = □□□□·□ W Converted to PT, CT secondary reactive power
Q= □□□□·□ var Cosine function for included angle of voltage
Cosφ = □·□□□ and current. for -90°<φ<90°, COSφ is positive.
for 90°<φ<270°, COS φ is negative
At Closed, breaker is at closed position. at Open, breaker
is at open position.
Binary Input -1/25- Note: The position of the breaker relates to protection
Break :□ logic, with fixed position.
Trolley Run :□
When Closed, trolley at running position
Trolley Test :□ When Closed, trolley at test position
Earth Switch :□ When Closed, earth switch at closed position
When Closed, energy storage not completed Spring :□
Heavy Gas :□ Description varies with model, see corresponding terminal
Light Gas :□ diagram for details
Over T Trip :□
NoAtel: In the standard configurations, the input circuit has the connection to an external
220VDC control power supply. When no DC control power supply or control system is available
on site, but a 110VDC control power supply is available, a 110VDC control power supply may be
used for direct connection through local hardware adjustment, or the 24V power supply of the
device may be used as the input power supply (when the input common terminal is +24V, terminal
number: B22, Terminal B01 is kept float). However, this must be specified upon ordering.
30
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Soft Strap -1/43-
Inst. PROT Off
Delay Inst. PROT Off
......
Pulse Energy -1/4-
Accumulation of the device’s real-time active and +□□□□□□□·□□□kWh
reactive calculations over time, + for positive +□□□□□□□·□□□kvh
direction, - for negative direction.
-□□□□□□□·□□□kWh
-□□□□□□□·□□□kvh
Harmonic Data -1/10-
2nd : □□□·□□%
3rd : □□□·□□%
4th : □□□·□□% 2~11 harmonics for which analog channels
5th : □□□·□□% have been selected in system
......
DC Input Data -1/2-
External DC input 4~20mA (2-way) DC1:□□□·□□mA
DC2:□□□·□□mA
AD Volt. Data -1/2-
AD Voltage Check
AD1:□□·□□□V
AD2:□□·□□□V
Run Parameters
In the [Run Parameters] menu includes 3 submenus,including [Settng Zone No.]、[PROT
On/Off]、[Clock Setting], The screen Content is as follows:
Setting Zone No. :Range 00~07.
PROT On/Off:The device protect plate can be select in this menu.
PROT On/Off -1/43- Parameter Modify
Inst. PROT
On Off ◇Enter ◆Cancel
Press “+”, “-” keys to select the protection function On or Off. The interface will eje
ct the window as right chart show when you press the “Enter” key. Move the cursor to t
he desired position for modification by pressing the “”, “” keys. Press the “Enter” key
to complete setting, and the device will prompt modifying success or not. If the “Cance
31
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
l” key is pressed, the protect plate status setting will be cancelled and the menu will retu
rn previous menu.
Clock setting:
A battery-back real-time clock is provided in the device, which can perform time adjust
remotely via the communication network or in-site time adjust in the [Time Setting] menu.
Enter this menu and press the “Enter” key, the clock will stop refreshing and a cursor will
appear. Move the cursor to the desired position for modification
Clock setting
by pressing the “”, “” keys, modify to the desired value with
Date:20□□-□□-□□ the “+”, “-” keys. Press the “Enter” key to complete setting. If
Time: □□:□□:□□ the “Cancel” key is pressed, the setting will be cancelled and
the screen continues to refresh the clock.
Setting View
This meun just for query.You can’t modif the value to prevent faulty operation.
Setting Value
After entering the password, you can enter the [Setting Value] menu. See the settings
description of the protection device for the detailed description.
Report Manage
The [Report Manage] menu includes 4 submenus, including trip report, binary report, event
report and print report. Event recording includes: device self-check fault, device setting value
modification, system parameter modification and setting zone number modification, etc. Trip
report can be record for the last 50 events, binary report for 100, event report for 30 at most.
Beyond this, the latest report will overwrite the earliest one. Press the “Enter” key to enter the
corresponding [To view xx report, please enter report number: 00] menu, and enter any figure
within storage volume, press the “Enter” key to display the contents of that report. The screen is as
follows:
Report No.:□□ ↓ Report No. of this report
20□□-□□-□□ Year, month, day, hour, minute, second and
□□:□□:□□:□□□ millisecond when it took place
□□□□□□
Press key to see the specific operation value. Press and keys to flip over. Operation
values.
Action value view
Ia = □□□·□□ A
Ib = □□□·□□ A Protect CT secondary current value
Ic = □□□·□□ A
Uab = □□□·□□ V
Ubc = □□□·□□ V Protect PT secondary voltage value
Uca = □□□·□□ V
32
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
System parameters
After entering the [SYS Parameters] menu, the correct password is required to enter the [SYS
Parameters] menu. It displays the following:
Parameters -1/6-
Comm. Setting
Transforrmer Coe.
B. Parameters
D/A Setting
Pulse Energy
Channel Coef.
Communication Setting\
Comm. setting -1/8-
NET Protocol
□□ 00:Quit; 01:IEC104; 02:IEC61850;
RS485 Protocol
□□ 00:Quit; 01:IEC103; 02:Modbus;
RS485 Address
□□ Communication address of device 01~99
RS485 Baud rate
□□ 00:2.4KB;01:4.8KB;02:9.6KB;03:
IP Address 19.2KB;04:38.4KB;05:115.2KB
□□□. □□□. □□□. □□□
SNTP Address
□□□. □□□. □□□. □□□ For Ethernet communication
K W Default
□□□. □□□. □□□. □□□
Printer IP
□□□. □□□. □□□. □□□
Transform Coefficient
TransformCoe -1/2-
PT Ratio
□□□□
CT Ratio
□□□□
Max:1500 Min:0001
It will prompt maximum value and minimum value of each parameter below the window.
Setting of basic parameters (see the description of the protection device for basic parameters)
33
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
B.Parameters: -1/11-
Rating Current
□□
CT Wiring Mode
Setting the CT secondary current rating 00: 5A. 01: 1A
□□ Setting the CT secondary wiring mode00: 3-phase. 01: 2-phase
PT Wiring Mode
□□
Setting the PT secondary wiring mode00: Y-Y. 01: V-V Harmonic Channel
□□ Setting analog quantity channels 0~11 for harmonic monitoring, select 0
to exit from the harmonic calculation function
D/A setting
The device has two 4~20mA outputs. The DA1~DA2 adjustment factor is used to adjust the
accuracy of the channel output. The DA1~DA2 channel selection is used to select the
corresponding analog quantity channel (see the description of the protection device for specific
reference quantities). In the accuracy test, make sure the field ground is in good contact. otherwise
the accuracy might be affected.
Pulse energy setting
Energy base numbers can be set, including positive active energy, positive reactive energy,
negative active energy and negative reactive energy.
Channel Coefficient
The device can adjust channel coefficient by this menu to raise Sample size.
Device test
After entering the [Device Test] menu, the correct password is required to enter the [Device
Test] menu. It’s have two menu include [Output Test] and [Lamp Test].
Output Test
Enter [Output Test] menu, It displays the following:
Output Test -1/14-
Remote Close Press “Enter” key Remote Close
Remote Trip On Off
Trip Signal 1
Note:
Trip Signal 2
Press “Cancel” key d……
(Note: When the test is performed on the 6 protection outputs, the starting relay will be in the
“Closed” state automatically. The “+”, “-” keys are used for switching between the “Close/Open”
control.)
Lamp Test
Lamp Test
◇Light ◆Quench
Used for testing Stand or fall of all LED lights.
34
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Password
The [Password] menu is used to modify the password for entry into the Settings, System
parameters and Output Test submenus. The initial password is provided by the factory. The
universal password is “1000”.
Move the cursor to the desired position for modification by
Input password pressing the ““, “” keys, modify to the desired password with
the “+”, “-” keys. Press the “Enter” key to enter the new password
0 0 0 0
setting menu as above. Press the “Cancel” key to cancel the setting.
Version information
In the main menu, after entering the [Version Info.] menu, the Type, ID, CRC and Date of the
software will be displayed.
Note: For a corresponding nonstandard model, the device’s
PROT AUTO DEV V2.00
Type:MTPR-820Hc displayed Type does have to be changed.
ID:□□.□□.□□
CRC:□□□□□□□□
Date:20XX-XX-XX
Comm test
When debugger debug the device on-site in the case of no-accessing the actual analog electric quantity
or the input quantity, [Comm Test] is used to do the test of the communication node of the device
6. Check of protection function
6.1 Over-current protection checkout(Overcurrent)
Over-current protection has three segments; these are instantaneous over-current
protection, the time delay instantaneous protection, over-current definite-time limit
protection. It can be set and put on/off respectively. These three protections have same
principle. Take instantaneous over-current protection as an example to explain. Connect
as figure 6-1, put instantaneous over-current protection and instantaneous over-current
compounded voltage block in running.
MTPR-820Hc
Ia1(Ib1,Ic1) D01(D03,D05)
Ia1’(Ib1’,Ic1’) D02(D04,D06)B29
Power supply
Ua D15
Ub D16&D17 B30
Uc D18
Figure 6-1
35
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Set in accordance with the table as follow, take the operating value and keep it in the
table. When the instantaneous over-current protection is operated, terminals B23-B24、
A17-A18、A19-A20 should be connected.
Input 30V for UBC Current setting of
and current of phase instantaneous over In 2In 5In 10In
current protection(A)
A, take UBC as the
basis and shift Operating value
current to check the
Operating zone
operating zone
Input 30V for UCA Current setting of
and current of phase instantaneous over In 2In 5In 10In
current protection(A)
B, take UCA as the
basis and shift Operating value
current to check the
Operating zone
operating zone
Input 30V for UAB Current setting of
and current of phase instantaneous over In 2In 5In 10In
current protection(A)
C, take UAB as the
basis and shift Operating value
current to check the Operating zone
operating zone
Under voltage setting
20 40 60 80
(V)
Operating value of
Set overcurrent under voltage
value with 5A, input Setting of negative
current 6A sequence voltage(V) 5 10 15 20
Operating value of
negative sequence
voltage
6.2 Check of inverse time limit over-current protection(IT Overcurrent)
Connect as figure 6-1. Put inverse time limit over-current protection in running.
Choose a sort of curve in inverse time limit characteristic curve setting(01:Standard
inverse time limit;02:Unusual inverse time limit;03:Extreme inverse time limit;04:Long
inverse time limit),set inverse time limit constant p 0.50s,inverse time limit current Ip
5A.Inverse time limit settings are in accordance with table as follow. When inverse time
limit over-current protection is operated, terminals B23-B24、A17-A18、A19-A20 should be
36
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
connected.
Curve The operating current(A) 2Ip(A) 3Ip(A) 5Ip(A)
01:Standard Theoretical operating time(s) 5.105s 3.15s 2.140s
inverse
Ip=5A =0.5s The real operating time(s
)
, p
02:Unusual Theoretical operating time(s) 6.750s 3.375s 1.688s
inverse
Ip=5A =0.5s The real operating time
(s)
, p
03:Extreme Theoretical operating time(s) 13.333s 5.000s 1.667s
inverse
Ip=5A =0.5s The real operating time(s)
, p
04:Long inverse Theoretical operating time(s) 60.000s 30.000s 15.000s
Ip=5A,p =0.5s The real operating time(s)
6.3 Check of negative sequence over-current protection(NS Overcurrent)
The negative sequence current is calculated by protection currents. Connect as figure
6-1.
6.3.1 Negative sequence over-current definite time limit protection
Put negative sequence over-current definite time limit protection in running, input
three protection currents as negative sequence mode. Set in accordance with the table as
follow, take the operating value and keep it in the table.
Negative sequence current (A) 0.2In 0.4 In 0.6 In 0.8 In
Negative sequence delay (s) 10 5 2 1
Negative sequence current
operating value (A)
Negative sequence delay
operating time (s)
6.3.2 Negative sequence over-current inverse time limit protection
Put negative sequence over-current inverse time limit protection in running, input
three protection currents as negative sequence mode. Inspect this protection according as
over-current inverse time limit protection table.
When negative sequence over-current protection is operated, terminals B23-B24、
A17-A18、A19-A20 should be connected.
6.4 Check of overload protection(Overload)
Overload protection uses the maximal current to judge, trip or alarm can be chosen,
If put overload trip in running, alarm function exits automatically. Connect as figure 6-1, put
37
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
overload alarm in running.
Set in accordance with the table as follow, take the operating value and keep it in the
table. When overload alarm is operated, terminals B19-20 should be connected.
Put overload trip in running, when overload trip is operated, terminals B23-B24、
A17-A18、A19-A20 should be connected.
Overload current(A) 5 10 15 20
Overload delay(s) 10 5 2 1
Overload current
operating value (A)
Overload delay
operating value (s)
6.5 Check of zero sequence over-current protection(HV ZS OC)
Zero sequence over-current protection has three segments. It can be set and put
on/off respectively. These three protections have same principle,take zero sequence
over-current protection I as an example to explain. Connect as figure 6-2, put zero
sequence over-current protection I in running.
MTPR-820Hc
I0 D07 B29
Power supply
I0’ D08 B30
Figure 6-2
Set in accordance with the table as follow, take the operating value and keep it in the
table. When zero sequence over-current protection is operated, terminals B23-B24、
A17-A18、A19-A20 should be connected.
Zero sequence
0.20 0.50 1.00 1.50
current setting (A)
Operating value
6.6 Check of low voltage side zero sequence over-current protection(UV ZS OC)
Connect as figure 6-3,to inspect low voltage side zero sequence over-current
protection.
38
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
6.6.1 Low voltage side zero sequence over-current with definite-time delay(UV ZS
OC DT)
Put low voltage side zero sequence over-current with definite-time delay protection in
running, input currents, Set in accordance with the table as follow, take the operating
value and keep it in the table.
Low-voltage zero
5 10 15 20
sequence current (A)
Definite time
10 5 2 1
limit delay (s)
Low-voltage zero sequence
current operating value (A)
Definite time limit
delay operating value (s)
6.6.2 Low voltage side zero sequence over-current with inverse-time delay(UV ZS
OC IT)
Put low voltage side zero sequence over-current with inverse-time delay protection in
running, input currents, checkout method refers to inverse time limit over-current
protection.
MTPR-820Hc
I0L D13 B29
Power supply
I0L’ D14 B30
Figure 6-3
When low voltage side zero sequence over-current protection is operated, terminals
B23-B24、A17-A18、A19-A20 should be connected.
6.7 Check of voltage protection(Voltage Protect)
6.7.1 Check of under-voltage protection(Undervoltage)
Under-voltage protection uses the maximal line voltage to judge, it can choose PT
failure to block under-voltage protection. Connect as figure 6-4, put under-voltage
protection, PT failure alarm and PT failure block in running.
39
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
MTPR-820Hc
Ua D15
Ub D16&D17 B29
Uc D18
Power supply
B01
Breaker assistant
B30
contact
B02
Figure 6-4
Set in accordance with the table as follow, take the operating voltage and keep it in
the table. When Under-voltage protection is operated, terminals B23-B24、A17-A18、
A19-A20 should be connected. Simulate PT failure, When PT failure happens,
Under-voltage protection will be blocked.
Under-voltage
95 90 85 80
setting value (V)
Under-voltage delay (s) 10 5 2 1
Under-voltage
operating value(V)
Under-voltage delay
operating value (s)
6.7.2 Check of over-voltage protection(Overvoltage)
Over-voltage protection uses the maximal line voltage to judge. Connect as figure 6-4,
put over-voltage protection in running,and simulate the breaker closed.
Set in accordance with the table as follow, take the operating voltage and keep it in
the table. When over-voltage protection is operated, terminals B23-B24、A17-A18、
A19-A20 should be connected.
Over-voltage
105 110 115 120
setting value (V)
Over-voltage delay (s) 10 5 2 1
Over-voltage
operating value(V)
Over-voltage delay
operating value (s)
6.8 Check of body protection(Body Protect)
Put heavy gas trip, light gas alarm, over-temperature trip,temperature alarm and
40
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
pressure relief trip in running, connect terminal B01 with the cathode of the DC power
supply(Take binary input connecting with DC220V power as an example),anode connects
terminals B07~B11 respectively. When heavy gas trip, over-temperature trip, pressure
relief trip protection is operated, terminals B23-B24、A17-A18、A19-A20 should be
connected; When light gas alarm, temperature alarm protection is operated, terminals
B23-B25 should be connected.
6.9 Check of non-electric quantity protection(Non-electric)
Connect as figure 6-5, put non-electric quantity protection in running; take
non-electric quantity protection 1 as an example.
MTPR-820Hc
DCSIn+ D25 B29
Power supply
DCSIn- D26 B30
Figure 6-5
Set in accordance with the table as follow, take the operating value and keep it in the
table. When the protection is operated, terminals B23-B24、A17-A18、A19-A20 should be
connected.
Setting value of non-electric
5 10 15 18
quantity 1 current (mA)
Delay of non-electric
10 5 2 1
quantity 1 current (s)
Non-electric quantity 1
operating value (mA)
Non-electric quantity 1
delay operating value (s)
6.10 Check of PT failure and CT failure(PT/CT Failure)
Connect as figure 6-6, and also connect the breaker assistant contact, simulate PT
failure, high voltage side CT failure or low voltage side CT failure, then the device will send
alarm signal, terminals B23-B25 will be closed.
41
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
MTPR-820Hc
I a1(Ib1,Ic1) D01(03,05)
Ia1’(Ib1’,Ic1’) D02(04,06)
Ua D15 B29
Ub D16&D17 Power supply
Uc D18 B30
Ia2(Ib2,Ic2) D19(21,23 )
Ia2’(Ib2’,Ic2’) D20(22,24 )
Figure 6-6
6.11 Check of under-frequency unloading protection(Under-frequency)
Under-frequency unloading protection’s frequency adopts the frequency of voltage
Uab .To avoid burthen feedback,frequency slip block(can put in/out) and low current block
are adopted. To avoid mis-operating of under-frequency unloading protection because of
voltage declining too fast, it has low voltage block. Connect as figure 6-7 , put
under-frequency unloading protection in running. Put slip block in running if measuring slip
frequency. When measured the operating value of frequency and delay time, please put
slip block out of running, in order to prevent influence of action accuracy.
MTPR-820Hc
D01
Ia1 D02 B29
Ia1’
Ua
D15
Ub Power supply D16&D17 B30
Uc
D18
Figure 6-7
Set in accordance with the table as follow, take the operating value and keep it in the
table. When under-frequency unloading protection is operated, terminals B23-B24、
A17-A18、A19-A20 should be connected.
Under-frequency setting value
49.5 49 48.5 48
(Hz)
Under-current setting value (A) 0.5 0.5 1 1
Under-voltage setting value (V) 10 20 30 60
df/dt (Hz/s) 3 4 5 7
Setting of Delay (s) 0.5 1 2 3
42
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Frequency operating value (Hz)
Delay time operating value (s)
Slip operating value (Hz/s)
6.12 Check of longitudinal differential protection(Diff.Protect)
6.12.1 Checkout of differential instantaneous over-current protection(Inst.Diff.PROT)
Connect as figure 6-8; put differential instantaneous over-current protection in
running. Set in accordance with the table as follow, take the operating value and keep it in
the table. When differential instantaneous over-current protection is operated, terminals
B23-B24、A17-A18、A19-A20 should be connected.
MTPR-820Hc
Ia1(Ib1,Ic1) D01(D03,D05)
B29
I a1’(Ib1’,Ic1’) D02(D04,D06)
Power supply
Ia2(Ib2,Ic2) D19(D21,D23)
B30
Ia2’(Ib2’,Ic2’) D20(D22,D24)
Figure 6-8
Differential instantaneous over-current
setting value (A) 1In 2In 3In 4In
Differential instantaneous operating
value (A)
6.12.2 Check of percentage differential protection(Per.Diff.PROT)
Connect as figure 6-8; put percentage differential protection in running. Set in
accordance with the table as follow, take the operating value and keep it in the table.
When percentage differential protection is operated, terminals B23-B24、A17-A18、
A19-A20 should be connected.
Add some content of second harmonic to high voltage side currents(Add according
as the content of second harmonic in transformer excitation surge, which producing when
the transformer unload closing).It will block percentage differential protection when the
ratio of second harmonic content and differential current is greater than the setting value
of second harmonic braking coefficient.
43
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Rated current of motor(A) In In In In
Percentage differential threshold
current Ido(A) 0.4 In 0.4 In 0.4 In 0.4 In
Percentage differential braking
inflexion point 1 A 0.2 In 0.2 In 0.2 In 0.2 In ( )
Percentage differential braking
inflexion point 2 A 0.4 In 0.4 In 0.4 In 0.4 In ( )
Percentage braking coefficient 1 0.3 0.3 0.4 0.4
Percentage braking coefficient 2 0.5 0.5 0.6 0.6
Second harmonic braking coefficient 0.1 0.15 0.2 0.25
Differential operating value(A)
6.12.3 Check of differential over limit alarm(Diff.C OL Alarm)
Connect as figure 6-8; put differential over limit alarm in running. Set in accordance
with the table as follow, take the operating differential current value and keep it in the
table. When the operating condition is satisfied, the device reports differential over limit
alarm and turn on alarm signal.
Differential over limit
alarm current value 0.4 In 0.6 In 0.8 In In
Differential over limit
alarm current operating
value (A)
6.13 Operate Circuit Break
Operate circuit break output be controlled by software.When this function be selected.
Connect the negative terminal to terminal A11 (-KM), positive terminal to terminal A12.
Connect the negative terminal to terminal A05(TWJ),A04(HWJ) to make HWJ or TWJ
action.The device monitoring operate circuit normatlity.When you turn off
A05(TWJ),A04(HWJ) to connect the negative terminal or connect the negative terminal
both of them, The operate circuit break will action after delay time. Measuring terminals
B23-B26 should be shorted.
44
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Addendum 1: Terminal diagram of the device
I/O POWER CPU A C
Input comon
A01 Common point- B01 point-
A02 Trip position B02 Breaker NET
A03 Closure position B03 Trolley Run
A04 Closed position Trolly Testmonitoring B04
A05 Trip position B05 Earth Switchmonitoring
A06 Manual closinginput B06 Spring
A07 Closed coil B07 Heavy Gas
A08 Manual B08 Light Gas NET2tripping input
A09 PROT tripping B09 Over-T Tripinput
A10 Trip coil B10 Temp. Alarm
A11 KM B11 Input 10
A12 +KM B12 Input 11
A13 B13 Input 12
A14 Remote controlcommon terminal B14 Input 13
A15 Remote control
Run Light
closing contact B15 Input 14
A16 Remote controltrip contact B16 Input 15
DEBUG
A17 PROT Output 1 B17 Input 16 C01 GPS-A
A18 PROT Output 1 B18 Input 17 C02 GPS-B
A19 PROT Output 2 B19 Input 18 C03
A20 PROT Output 2 B20 Input 19 C04 COM1A
A21 Output 3 B21 Overhaul C05 COM1B
A22 Output 3 B22 (+24V) C06 Shielded ground
A23 Output 4 B23 Common terminal C07 COM2A
A24 Output 4 B24 Trip Signal C08 COM2B
A25 Output 5 B25 Alarm Signal C09 DCS1+ D25
A26 Output 5 B26 Operate CIR C10 DCS1- D26
A27 Output 6 B27 Power off C11 DCS2+ D27
A28 Output 6 B28 Power off C12 DCS2- D28
A29 Output 7 B29 Power 1.Ia1,Ib1,Ic1 are protection curents at high-voltage
A30 Output 7 B30 Power side.2.Ia2,Ib2,Ic2 are protection curents at low-voltage side.
A31 B31 3.IO,IOL are zero-sequence curents at high-voltage andOutput 8 low-voltage side.
A32 B32 Shielded ground 4.IA,IC are measuring curents.Output 8 5.Uab,Ubc are voltages at high-voltage side.
6.DCSIn is 2-way 420mA DC input.
7.Net1,Net2 are ethernet interfaces, COM1,COM2 are
485 interfaces.
8.If +24V on power board is standard configuration or
not,it is used as an input power suply only when using
internal 24V.
Figure 1 Terminal diagram of MTPR-820Hc
4
~
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
transformer protection and monitoring device
Addendum 2: Typical wiring diagram of the device
5
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Figure 2 Typical wiring diagram of
MTPR-820Hc transformer protection and monitoring device
Addendum 3: Operating circuit of MXPR-800Hc series device
Traditional operating circuits are started by current, while a voltage maintaining circuit
realizes electric trip prevention. An anti-trip relay will be selected depending on the current of the
trip/closing circuit of the circuit breaker. However, this has poor generality and can hardly be
realized for circuit breakers with low trip and closing currents (such as 10KV circuit breakers from
AEG Company in Germany, whose trip and closing currents are not greater than 0.2A). To
simplify wiring and design finalization, and to improve the generality of the product, we offer a
new operating circuit shown below.
6
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Schematic diagram of operating circuit
7
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Permanent magnetic breaker operating circuit
In the diagram, When the SA is connected to 5,6 contact,The SA is at the “Remote” position,
the power of the remote control circuit will be switched on, closing and trip with remote control.
when the SA is connected to 9,10 contact, The SA is in manual closing state. when the SA is
connected to 1,2 contact, The SA is in manual Tripping state.
8
MTPR-820Hc transformer protection and monitoring device WLD[K]-JY-312-2018
Note: The dotted line outlines the internal circuit of the protection device. All our devices
marked with “anti-trip circuit” are designed on this operating circuit.
Terminals Tn1, Tn2 corresponding to the protection relay Jn are determined by the
corresponding protection output control word. Jn can be any one or more of Protection outputs
1-8.
Whether local or remote control, the precondition to jump is Terminal A06 of the device is always
connected to +KM. After manual or remote controlled closing, if a short-circuit fault occurs, the
protection will operate to trip the circuit breaker. Though Terminal A06 of the device is connected to
+KM, the closing circuit is disconnected by TBJ1 and will not be closed again. In this way, circuit
breaker jump is effectively prevented.
9