Zhuhai Wanlida Electrical
Automation Co., Ltd.
http://www.zhwld.com
User’s manual of MPTS-820Hc PT paralleling and voltage
protection device
Prepared by: Li Changwen
Proofed by: He Wenhui
Approved by:Lin Cunli
Document No.: WLD [K]-JY-309-2018 Version No.: V1.03.01
Date of publication: June, 2018
Copyright: Zhuhai Wanlida Electrical Automation Co., Ltd.
Note: Our Company reserves the right to modify this manual. For any inconsistency between
the product and this manual, please contact us for relevant services.
Technical support hotline: 0756-3395398 Fax: 0756-3395111
Foreword
F o r e w o r d
1. Model description
MPTS-820Hc is PT paralleling and voltage protection device.
2. Standards referenced
General specification for static protection, security and automatic equipment,
DL 478-2001
Technical code for relaying protection and security automatic equipment
GB/T 14285-2006
Protective relay and automatic equipment design rules of power equipment
GB50062-92
Transformer substation correspondence network and system DL/T 860
Intelligent substation technology norms Q/GDW 383 -2009
Intelligent substation relay protection technical specifications Q/GDW_441-2010
IEC61850 engineering application model Q/GDW 396-2010
3. Caution
Negative sequence voltage involved in this series of protection is combined with
phase voltage.
The appearance should be inspected before power is applied, to ensure that the
panel is OK without scratch, the screws are tightened, the device is grounded
firmly, all screws of plug-ins are tightened and in good contact.
When power is applied, the “Run” indicator on the panel should flash, protection
and measuring data are displayed on the lcd in cycle.
It is prohibited to plug or unplug the plug-ins, in order to avoid damage to the
device.
It is prohibited to do digital output test when the device is running with primary
equipments.
2
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
1. Product description
1.1 Scope of application
The MPTS-820Hc PT parallelling and voltage protection device applies to different voltage
ratings. The device can perform parallelling operations according to the operating condition of PT
and the bus.
1.2 Function and specification
1.2.1 Protective function
PT parallelling function(Remote/Local)
Over-voltage protection of Bus I and II
Low-voltage protection of Bus I and II
Alarm of zero sequence voltage of Bus I and II
Alarm of PT failure of Bus I and II
PT failure Block
1.2.2 Auxiliary function
Phase display
Self-checking fault alarm of device
Remote calling and modification of protection’s settings
One way (or two ways) programmable output of 4~20mA
Network print
Virtual correspondent node remote test
1.2.3 Monitoring function
Electric quantity measuring(remote measuring): Voltage of both bus, negative sequence
voltage, zero-sequence voltage of both bus and frequency of both bus.
Remote binary quantity: the device has 20-way binary input.
1.2.4 Communication capability
With industrial Ethernet port and standard RS485 multipoint communication port. Supports
ModBus、IEC-60870-5-103(RS485 communication mode)、IEC-61850-5-104(Industrial
Ethernet communication mode ) standard communication protocol and WLD2003
communication protocol..
Supports single and dual network communication, it is fully qualified for network
redundancy and backup
1.2.5 GPS clock synchronization function
The device is able to receive GPS clock second synchronization or IRIG-B through RS485
differential voltage, and it can be done with monitoring system to accomplish GPS precise
clock synchronization or Ethernet-based SNTP synchronization.
1.2.6 Device specifications
32-bit POWERPC microprocessor
3
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
Real-time multi-task operating system and C++ program techniques, realizing online
programming
320*240 LCD display, easy for inspection
One or two ways 4~20mA DC quantity output, which can be set flexibly as any
corresponding electric quantity (such as current, voltage, power, etc.)
Having the electric energy quality analysis function and perfect harmonic analysis function
Support network printing function, include two ways: real-time print and artificial print
Support virtual correspondent node remote test, including remote communication to
correspondent node, remote measure to correspondent node, event to correspondent node, can
online testing, it is convenient for debugger to debug the device on-site.
Excellent hardware interchangeability, user maintenance is easily and it reduced quantity of
spare parts
Protection output relays can be configured flexibly for user convenience
Using a 6U, 19/3” standard enclosure in a rear plug-in structure. the device can be installed in
site on a switchboard or combined in a centralized manner
1.2.7 Main technical specifications
Rated data
Power supply: DC/AC 86~265V
Operating voltage: DC 220V or DC 110V
AC voltage: 100/ 3 V or 100V
Power consumption
DC circuit: <10W (normal operation); <15W (protection operation)
AC voltage circuit: <0.5VA/phase
Overload capability
AC voltage circuit: 1.2Un, continuous operation
Range and error of setting value
Maximum range of setting value:
Voltage element: 1V~120V
Frequency: 45.00Hz~55.00Hz
Timing element: 0.00S~100.00S
Error of setting value:
Current and voltage setting value: ≤±3% of setting value
Frequency setting value: ≤±0.02Hz
Whole-group operation time (including relay’s intrinsic time):
Intrinsic operating time of voltage protection: not greater than 40ms.
Measuring accuracy
AC voltage: Class 0.2
Frequency: ≤±0.02Hz
SOE resolution: ≤2ms
4
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
4~20mA DC quantity output: ≤±1%
Capacity of trip/closing output contact
Can be connected to DC 250V, 8A for prolonged periods.
Environmental conditions
Ambient temperature:
Operating:-20℃~+55℃.
Storage:-25℃~+70℃, rainproof and snow-proof rooms with relative humidity not
greater than 80%, ambient air free of acid, alkaline or other corrosive and explosive gas. No
excitation quality is applied at the limits, the device shall not have any irreversible change.
After temperature restoration, the device shall operate properly.
Relative humidity:
The average relative humidity of the most humid month shall not be greater than 90%,
the average minimum temperature of this month not lower than 25℃ and there shall be no
surface condensation. At the highest temperature of +40℃, the average maximum humidity
shall not exceed 50%.
Atmospheric pressure: 80kPa~110kPa (below relative altitude of 2KM)
1.2.8 Hardware structure
The device uses a 6U, 19/3” standard enclosure, with aluminum alloy casing and installed by
overall embedding. The display panel is mounted in the front, and the other plug-in modules are
rear mounted. From the rear view, I/O, the power, CPU and AC plug-in modules are from the left
to the right.
External dimensions and boring diagram
Structural and dimensional diagram Boring diagram for installation
5
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
Devices fabricated on-screen steps: first release on-screen stents unfastening screws, remove
the stents. Install the device on the screen from the front and push until close to the fixed plate.
Install the stent 2, and then stent 1, and then use fastening screw to insertion hole from rear of
stent1, and then screwed into stent 2 and tighten screw. The stents from up and down are installed
in the same way. Use grounding screws to connect grounding line.
2. Function of device
2.1 PT parallelling function
For 2 buses or a single bus with different operating sections, when any PT group
on the 2 bus sections has a fault and must be stopped, PT switching can be carried out
manually or remotely through this device.
QF binary input closed
Choose remote control & switching command
PT switching On
Choose local & BK binary input closed ≥ & PT switching
terminals closed
Section I PT assistant position input closed
Section II PT assistant position input closed &
Figure 2-1 Remote/local switching logical diagram
6
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
PT Manual Parallel/Dissolve:
PT Switch function ON,put “PT switch ON/OFF” to ON ,-220V is tied to
Terminal B01,+220V is tied to Terminal B03, circuit breaker QF in the closing
position, B04 and B05 in any one terminal also access +220 V,There is a set of PT in
the closing position, the other group in the opening position。+220V is tied to
Terminal B02。When switch operates A01-A02、A17-A18、A19-A20、A21-A22、
A23-A24、A25-A26、A27-A28、A29-A30、A31-A32 should be connected,Also light
up the Parallel light。
PT remote Parallel/Dissolve:
PT Switch function ON,put “PT switch ON/OFF” to ON ,-220V is tied to
Terminal B01,+220V is tied to Terminal B03 and B06,B04 and B05 in any one
terminal also access +220 V,There is a set of PT in the closing position, the other
group in the opening position。When the device receives a remote parallel command,
A01-A02、A17-A18、A19-A20、A21-A22、A23-A24、A25-A26、A27-A28、A29-A30、
A31-A32 should be connected,Also light up the Parallel light。 The PT parallel
contacts are disconnected when the device receives a remote Dissolve command。
2.2 Over-voltage protection function
The device can monitor the voltage of 2 bus sections. When the maximum of line
voltage of a bus section is higher than the over-voltage setting value and the delay is
reached, the over-voltage protection will operate. The over-voltage operations of the 2
bus sections operate on different outputs.
Figure 2-2 Over-voltage protection logical diagram
2.3 Low-voltage protection function
The device can monitor the voltage of 2 bus sections. If any voltage of the 2 bus
sections is normal,When the minimum line voltage of a bus section is higher than the
low reverting voltage and the maximum line voltage of that bus is lower than the low
voltage setting value and higher than loss-of-voltage setting, and the delay is reached,
the low voltage protection will operate. The low voltage operations of the 2 bus
sections operate on different outputs.
Figure 2-3 Low voltage protection logical diagram
7
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
2.4 Zero sequence voltage alarm function
The device can monitor the zero sequence voltage of 2 bus sections. When
single-phase grounding occurs in a bus section, as its zero sequence voltage is greater
than the setting value and the delay is reached, a zero sequence alarm signal will be
given.
Figure 2-4 Zero sequence over-voltage protection logical diagram
2.5 PT failure alarm function
The device can monitor PT failure of 2 bus sections. It has the following criterion for
any period of busbar PT.
When PT failure protection is putting on, negative sequence voltage U2>8V, and
the delay 10s is reached, it will be considered PT failure. When PT failure protection
is putting on, negative sequence voltage U2<8V, and the delay 3s is reached, it will be
alarmed as PT failure.
2.6 Display
In normal operation, the LCD screen displays the protection line voltages on
primary side of 2 sections Uab1, Ubc1, Uca1,Uab2, Ubc2, Uca2, opening triangle
voltage of 2 sections U01,U02,and the frequency of 2 sections F1, F2 and
communication address alternatively in turn. The high brightness LED displays the
maximum voltage of 2 sections (1b, 2b).
2.7 Network print
Device supports network printing function, can print remote control information,
soe information and the setting parameter list. The printer IP address must been set
rightly on the device(the network segment of printer must be as same as that of device
IP addresses), then connect a printer, put on "real-time report print ", it can print the
current remote control information or soe information when device is connected to the
background(including remote communication shift, protection action), and can print
the current soe information when device is not connected to the background. In
addition, when press the "ok" button in the "print report" or "print setting value"
menu, it can print the all setting parameter or the all report information, including
action value.
2.8 Virtual correspondent node remote test
The function is used to complete the communication node remote test of the
device, do not need to access the actual analog electric quantity or the input quantity.
Specific operation as follows, connect to the background, In the remote test menu,
operate the “virtual input test”, the “virtual measure test” and the “virtual SOE test”
menu in the “remote test” menu, press the "OK" button after the modification of
8
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
various settings, then by observing the background pop-up warning window or the
change of the corresponding value, to determine whether the device communication
node is right. It is convenient for debugger to debug the device on-site.
2.9 GPS clock synchronization
The GPS clock synchronization signal is input as rs485 differential voltage, the device is able
to receive GPS clock second synchronization. If there is GPS signal, there will be flashing
on the bottom of cycle menu. Otherwise won’t.
The principle of GPS clock synchronization: The second pulse or minute pulse act with the
monitoring system, the time base with second precision is sent by monitoring system, when the
GPS second differential signal arrives, the time base is unified and the milliseconds are cleared.
The device is able to receive GPS clock second synchronization or IRIG-B through RS485
differential voltage, and it can be done with monitoring system to accomplish GPS precise clock
synchronization or Ethernet-based SNTP synchronization.
2.10 Overhaul status
When the device put into overhaul plate, remote sign, remote measure can uploading
background computer. But the device can’t remote control by background computer. The SOE
event、Alarm event、Trip event, etc also can’t uploading background computer.
3. Setting of parameters and setting values of the device
3.1 System parameters
Parameter Range Description
Settings of setting value zone number(Setting Zone No.)
Setting value zone
0-7 Set step:1(factory default 0)
number(Setting Zone No.)
Communication settings(Comm. Setting)
Set step :1 (factory default 1)
NET Protocol 0-1
(0-Quit;1-IEC104)
Set step :1 (factory default 0)
RS485 Protocol 0-4 (0-Quit; 1-IEC103,2-Modbus,3-WLD2003-300,
4-WLD2003-600)
RS485 address(RS485
1-99 Set step:1(factory default 1)
Address)
RS485 baud rate(RS485 Set step:1(factory default 2)0:2.4KB;1:4.8KB;
0-5
Baudrate) 2:9.6KB;3:19.2KB;4:38.4KB;5:115.2KB;
IP address(IP Address) It has four One section set step:1(factory default 192.168.0.253)
SNTP Address (SNTP sections. The
One section set step:1(factory default 192.168.0.254)
Address) range of every
9
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
Parameter Range Description
KW default value(KW section is
One section set step:1(factory default 12.8.6.1)
Default) 0-255
Printer IP address(Printer
One section set step:1(factory default 192.168.0.134)
IP)
Coefficient of transformer
Bus 1 PT Ratio (Bus 1
1-1500 Set step :1(factory default 1)
PT transformation ratio)
Bus 2 PT Ratio (Bus 2
1-1500 Set step :1(factory default 1)
PT transformation ratio)
Setting of basic parameters(B. Parameters)
V Connection (Voltage
0-1 Set step :1 (factory default 0) 00:YY;01:VV
Wiring mode)
Remote communication
10-100ms Set step: 1 (factory default 40ms)
ack time (input ack time)
Juxtaposed with PT knife
0-1 Set step: 1 (factory default 1) 00:exit;01:on
lock
Real-time print report
0-1 Set step: 1 (factory default 0) 00:exit;01:on
on/off(auto print report)
D/A channel setting(D/A Setting)
Select DA1~2 to output corresponding reference
quantities:
0:No D/A output
DA1~2 Channel
0-14 1:Ua1,2:Ub1,3:Uc1,4:U01,5:Ua2,6:Ub2,7:Uc2,8:U02,9:
Selection
Uab1,10:Ubc1,11:Uca1,12:Uab2,13:Ubc2,14:Uca2
Voltage reference quantity: 0-120V corresponding to
4mA-20mA,
DA1~2 Adjustment
0.5-1.5 Adjust D/A channel 1~2(4-20mA) parameters
Factor
Channel factor setting(Channel Coef.)
Channel 1-8 0.500-5.000 Set step:0.001(factory default 1.000)
10
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
3.2 List of setting values
Setting value Range Description
PT Switch 1/0 1/0:ON / OFF (factory default OFF)
Bus1 OverVoltage 1/0 1/0:ON / OFF (factory default OFF)
Bus1 Low Voltage 1/0 1/0:ON / OFF (factory default OFF)
Bus2 OverVoltage 1/0 1/0:ON / OFF (factory default OFF)
Bus2 Low Voltage 1/0 1/0:ON / OFF (factory default OFF)
Bus1 Ground Alarm
On/Off 1/0 1/0:ON / OFF (factory default OFF)
(Bus1 GroundAlarm)
Bus2 Ground Alarm
On/Off 1/0 1/0:ON / OFF (factory default OFF)
(Bus2 GroundAlarm)
Bus 1 PT Failure
On/Off (Bus 1 PT 1/0 1/0:ON / OFF (factory default OFF)
Failure)
Bus 2 PT Failure
On/Off (Bus 2 PT 1/0 1/0:ON / OFF (factory default OFF)
Failure)
PT Failure Lock 1/0 1/0:ON / OFF (factory default OFF)
Protection of bus I voltage(Bus 1 V PROT)
Setting value of Bus I
90-150V Set step:0.01V(factory default 120V)
over-voltage (Over Voltage 1)
Setting value of Bus I
10-90V Set step:0.01V(factory default 60V)
low-voltage (Low Voltage 1)
Setting value of Bus I
5-60V Set step:0.01V(factory default 30V)
loss-of-voltage (No Voltage 1)
Bus I over-voltage delay
0.1-100s Set step:0.01s(factory default 100s)
(Over Voltage 1 T)
Bus I low-voltage delay
0.1-100s Set step:0.01s(factory default 100s)
(Low Voltage 1 T)
11
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
Setting value Range Description
Protection of bus II voltage (Bus 2 V PROT)
Setting value of Bus II
90-150V Set step:0.01V(factory default 120V)
over-voltage (Over Voltage 2)
Setting value of Bus II
10-90V Set step:0.01V(factory default 60V)
low-voltage (Low Voltage 2)
Setting value of Bus II
loss-of-voltage (No Voltage 5-60V Set step:0.01V(factory default 30V)
2t)
Bus II over-voltage delay
0.1-100s Set step:0.01s(factory default 100s)
(Over Voltage 2 T)
Bus II low-voltage delay
0.1-100s Set step:0.01s(factory default 100s)
(Low Voltage 2 T)
Bus I zero sequence voltage protection(Bus 1 Ground)
Bus I zero sequence voltage
setting value 5-100V Set step:0.01V(factory default 100V)
(ZS Voltage 1 Set)
Bus I zero sequence delay
0.1-100.00s Set step:0.01s(factory default 100s)
(ZS 1 Time)
Bus II zero sequence over voltage protection(Bus 2 Ground)
Bus II zero sequence voltage
setting value 5-100V Set step:0.01V(factory default 100V)
(ZS Voltage 2 Set)
Bus II zero sequence delay
0.1-100.00s Set step:0.01s(factory default 100s)
(ZS 2 Time)
4. Description of binary input, output and analog quantity
4.1 Monitoring of analog quantities
Analog quantities can be monitored under the [Protection Data], [Measured Data] and [Pulse
Energy] menus in the [Run States] menu, press the “”, “” keys to flip over. The factory
precision of the device has been calibrated. The protection current is calibrated at double the rated
current and the measuring current at a single rated current. The list is as follows:
12
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
Analog quantity Analog quantity
Test method
terminal name
Bus I Phase A
Terminals D01, D02 voltage for Add 100V, displayed deviation not exceeding 1%
protection Ua1
Bus I Phase B
Terminals D03, D04 voltage for Add 100V, displayed deviation not exceeding 1%
protection Ub1
Bus I Phase C
Terminals D05, D06 voltage for Add 100V, displayed deviation not exceeding 1%
protection Uc1
Bus I zero
Terminals D07, D08 sequence voltage Add 100V, displayed deviation not exceeding 1%
U01
Bus I frequency
for measurement Add 60V on Ua1 at industrial frequency 50 Hz,
f1 displayed error not exceeding ±0.02Hz
Bus II Phase A
Terminals D09, D10 voltage for Add 100V, displayed deviation not exceeding 1%
protection Ua2
Bus II Phase B
Terminals D11, D12 voltage for Add 100V, displayed deviation not exceeding 1%
protection Ub2
Bus II Phase C
Terminals D13, D14 voltage for Add 100V, displayed deviation not exceeding 1%
protection Uc2
Bus II zero
Terminals D15, D16 sequence voltage Add 100V, displayed deviation not exceeding 1%
U02
Bus II frequency
for measurement Add 60V on UA2 at industrial frequency 50 Hz,
f2 displayed error not exceeding ±0.02Hz
4.2 Monitoring of binary input
Binary input can be monitored under the [Binary input] menu in the [Run States] menu, press
the “”, “” keys to flip over.
Binary input Binary input name Test method
terminal
B01 Common terminal of binary input - External power supply of 220V or 110V DC
(Should be connected to DC220V can be applied, connect the negative terminal
or DC110V to terminal B01, positive terminal to terminal
negative terminal of external power B02~B21, in [Binary input] menu in the
supply) [Run States], the status of binary input can be
B02 BK Point seen.
B03 QF Point The device also has a 24V DC supply, if
B04 PT 1 Trolley it is used, terminal B22 can be connected to
13
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
B05 PT 2 Trolley terminal B02~B21, in [Binary input] menu
B06 Remote/Local in the [Run States], the status of binary input
B07 Input 6 can be seen.
B08 Input 7 Please note about the binary input voltage
B09 Input 8 upon ordering, it is set to DC220V by default.
B10 Input 9
B11 Input 10
B12 Input 11
B13 Input 12
B14 Input 13
B15 Input 14
B16 Input 15
B17 Input 16
B18 Input 17
B19 Input 18
B20 Input 19
B21 Overhaul
B22 Positive terminal of internal 24V
power supply
4.3 Monitoring of binary output
Binary output can be monitored under the [Binary output] menu, press the ““, ““ keys to
flip over.
Binary output terminals Binary output name Test method
B23-B24 Trip Signal
B23-B25 Alarm Signal
A01-A02 PT Parallel Signal
A03-A04 Earth Signal
PT Failure Select open and close menu, use “+”, “-” A05-A06
key to operate and test the corresponding
A07-A08 Bus 1 Abnormal V
terminals.
A09-A10 Bus 2 Abnormal V
A11-A12 Spare Output 1
A13-A14 Spare Output 2
A15-A16 Spare Output 3
14
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
5. Operation instructions
5.1 Control panel of device
320*240 matrix LCD (The LCD will go off after a period of absence of keyboard operation. the
LCD will be illuminated automatically when any key is pressed or in case of protection trip or
alarm.)
Signal indicator: run, communication, trip, alarm, fault (of the device), parallel, remote.
Key pad: , , , , Cancel, -, +, Enter, Revert
5.2 Instructions for use of key pad and LCD display
During the device’s normal operation, it will display the primary measuring current、voltage、
power, secondary protective data、measuring data、device address、time and statue (indicating
whether reclosure charging is finished) in cycle. Press the “Enter” key to enter the main menu,
which is a multi-level tree menu. Press the ““, ““ keys to move the cursor to the desired entry,
press the “Enter” key to enter this entry, and press the “Cancel” key to return to the next higher
level of screen. If this screen is still a menu, continue to press the ““, ““ key to select the
desired entry, press the “Enter” key to enter the next level of screen, and press the “Cancel” key
to return to the next higher level of menu. If there is no menu screen, be sure to press the “Cancel”
key to return to the next higher level of menu. The main menu is shown at the center of the
following figure, with the corresponding submenus on both sides.
15
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
01.Run States -1/5- Main menu 05.Report Dis. -1/4-
Protection Data Trip Report Measuring Data 01.Run Status Binary Report Binary Input Event Report
Soft Strap 02.Run Parameters Print Report AD Volt.Data
03.Setting View 06.Parameters -1/6- Comm. Setting
04.Setting Value Transformer Coe. B. Parameters
02.Run Param. -1/3-
Setting Zone No. 05. Report Manage D/A Setting
Pulse Energy PROT On/Off Channel Coe.
Clock Setting 06. SYS Parameters
07.DeviceTest. -1/2-
03.Setting View-1/16- 07.Device Test Output Test
Bus1 OverVoltage
Bus1 Low Voltage 08.PassWord
Lamp Test
Bus2 OverVoltage 09.Version Info. 08.Password ...... □□□□
10.Comm Test
04.Setting Value-1/16- PROT AUTO DEV V2.00
Bus1 OverVoltage Type:MPTS-810Hc
Bus1 Low Voltage 10.Comm test ID:□□.□□.□□ Bus2 OverVoltage Input Test CRC:□□□□□□□□
...... Measure Test Date:20XX-XX-XX
SOE Test
Note 1:For the Setting menu, see the description of each device.
Run Status
The [Run Status] menu contains 8 submenus, including protection data, measuring data,
binary input, soft strap, pulse energy, harmonic data, DC measurement and trip statistics, AD
voltage data. It is described as follows:
Bus 1 Data ↑ ↓
Ua1 = □□□·□□ V
Ub1 = □□□·□□ V Bus I protection PT secondary voltage value
Uc1 = □□□·□□ V
U01 = □□□·□□ V
U21 = □□□·□□ V Bus I zeggive sequence
voltage value and frequency
F1 = □□□·□□ Hz
16
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
Bus 2 Data ↑ ↓
Ua2 = □□□·□□ V
Ub2 = □□□·□□ V Bus II protection PT secondary voltage
Uc2 = □□□·□□ V
U02 = □□□·□□ V Bus II zero voltage value, negative
U22 = □□□·□□ V sequence voltage value and frequency
F2 = □□□·□□ Hz
Binary Input -1/20-
BK Point :□
QF Point :□
PT 1 Trolley :□
PT 2 Trolley :□
Remote/Local :□ Description varies with model, see corresponding terminal
Input 6 :□ diagram for details
Input 7 :□
Input 8 :□
Input 9 :□
Input 10 :□ ......
Note: In the standard configurations, the input circuit has the connection to an external
220VDC control power supply. When no DC control power supply or control system is available
on site, but a 110VDC control power supply is available, a 110VDC control power supply may be
used for direct connection through local hardware adjustment, or the 24V power supply of the
device may be used as the input power supply (when the input common terminal is +24V, terminal
number: B22, Terminal B01 is kept float). However, this must be specified upon ordering.
Soft Strap -1/10-
PT Switch Off
Bus1 OverVoltage Off
Bus1 Low Voltage Off
Bus2 OverVoltage Off
......
AD Volt. Data -1/2-
AD1:□□·□□□V AD Voltage Check
AD2:□□·□□□V
Run Parameters
In the [Run Parameters] menu includes 3 submenus,including [Settng Zone No.]、[PROT
On/Off]、[Clock Setting], The screen Content is as follows:
Setting Zone No. :Range 00~07.
PROT On/Off:The device protect plate can be select in this menu.
17
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
PROT On/Off -1/10- Parameter Modify
PT Switch
On Off ◇Enter ◆Cancel
Press “+”, “-” keys to select the protection function On or Off. The interface will eje
ct the window as right chart show when you press the “Enter” key. Move the cursor to t
he desired position for modification by pressing the “”, “” keys. Press the “Enter” key
to complete setting, and the device will prompt modifying success or not. If the “Cance
l” key is pressed, the protect plate status setting will be cancelled and the menu will retur
n previous menu.
Clock setting:
A battery-back real-time clock is provided in the device, which can perform time adjust
remotely via the communication network or in-site time adjust in the [Time Setting] menu.
Enter this menu and press the “Enter” key, the clock will stop refreshing and a cursor will
Clock setting appear. Move the cursor to the desired position for modification
by pressing the “”, “” keys, modify to the desired value with
Date:20□□-□□-□□ the “+”, “-” keys. Press the “Enter” key to complete setting. If
Time: □□:□□:□□
the “Cancel” key is pressed, the setting will be cancelled and
the screen continues to refresh the clock.
Setting View
This meun just for query.You can’t modif the value to prevent faulty operation.
Setting Value
After entering the password, you can enter the [Setting Value] menu. See the settings
description of the protection device for the detailed description.
Report Manage
The [Report Manage] menu includes 4 submenus, including trip report, binary report, event
report and print report. Event recording includes: device self-check fault, device setting value
modification, system parameter modification and setting zone number modification, etc. Trip
report can be record for the last 50 events, binary report for 100, event report for 30 at most.
Beyond this, the latest report will overwrite the earliest one. Press the “Enter” key to enter the
corresponding [To view xx report, please enter report number: 00] menu, and enter any figure
within storage volume, press the “Enter” key to display the contents of that report. The screen is as
follows:
Report No.:□□ ↓ Report No. of this report
Year, month, day, hour, minute, second and 20□□-□□-□□ millisecond when it took place
□□:□□:□□:□□□
□□□□□□
Press key to see the specific operation value. Press and keys to flip over. Operation
values.
18
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
Action value view
Uab1 = □□□·□□ V
Ubc1 = □□□·□□ V
Voltage of Bus I
Uca1 = □□□·□□ V
Uab2 = □□□·□□ V Voltage of Bus II
Ubc2 = □□□·□□ V
Uca2 = □□□·□□ V
U01 = □□□·□□ V Zero sequence voltage,
U02 = □□□·□□ V
。。。。。。
System parameters
After entering the [SYS Parameters] menu, the correct password is required to enter the [SYS
Parameters] menu. It displays the following:
Parameters -1/6-
Comm. Setting
Transforrmer Coe.
B. Parameters
D/A Setting
Channel Coef.
Communication Setting
Comm. setting -1/8-
NET Protocol
□□ 00:Quit; 01:IEC104; 02:IEC61850;
RS485 Protocol
□□ 00:Quit; 01:IEC103; 02:Modbus;
RS485 Address
□□
RS485 Baud rate Communication address of device 01~99
□□ 00:2.4KB;01:4.8KB;02:9.6KB;03:
IP Address
□□□. □□□. □□□. □□□ 19.2KB;04:38.4KB;05:115.2KB
SNTP Address
□□□. □□□. □□□. □□□
K W Default For Ethernet communication
□□□. □□□. □□□. □□□
Printer IP
□□□. □□□. □□□. □□□
Transform Coefficient
TransformCoe -1/2-
Bus1 PT
□□□□
Bus2 PT
□□□□
Max:1500 Min:0001
19
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
It will prompt maximum value and minimum value of each parameter below the window.
Setting of basic parameters (see the description of the protection device for basic parameters)
B.Parameters: -1/11-
PT Wiring Mode
□□ Setting the PT secondary wiring mode00: Y-Y. 01: V-V
......
D/A setting
The device has two 4~20mA outputs. The DA1~DA2 adjustment factor is used to adjust the
accuracy of the channel output. The DA1~DA2 channel selection is used to select the
corresponding analog quantity channel (see the description of the protection device for specific
reference quantities). In the accuracy test, make sure the field ground is in good contact. otherwise
the accuracy might be affected.
Pulse energy setting
Energy base numbers can be set, including positive active energy, positive reactive energy,
negative active energy and negative reactive energy.
Channel Coefficient
The device can adjust channel coefficient by this menu to raise Sample size.
Device test
After entering the [Device Test] menu, the correct password is required to enter the [Device
Test] menu. It’s have two menu include [Output Test] and [Lamp Test].
Output Test
Enter [Output Test] menu, It displays the following:
Output Test -1/14-
PT Parall Signal Press “Enter” key PT Parall Signal
…… On Off
Operate All Note: Node:A19,A20 Open
Press “Cancel” key
(Note: When the test is performed on the 6 protection outputs, the starting relay will be in the
“Closed” state automatically. The “+”, “-” keys are used for switching between the “Close/Open”
control.)
Lamp Test
Lamp Test
◇Light ◆Quench
Used for testing Stand or fall of all LED lights.
Password
The [Password] menu is used to modify the password for entry into the Settings, System
20
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
parameters and Output Test submenus. The initial password is provided by the factory. The
universal password is “1000”.
Move the cursor to the desired position for modification by pressing the ““, “” keys,
Input password modify to the desired password with the “+”, “-” keys. Press the
0 0 0 0 “Enter” key to enter the new password setting menu as above.
Press the “Cancel” key to cancel the setting.
Version information
In the main menu, after entering the [Version Info.] menu, the Type, ID, CRC and Date of the
software will be displayed.
PROT AUTO DEV V2.00
Type:MPTS-810Hc ID:□□.□□.□□
CRC:□□□□□□□□
Date:20XX-XX-XX
Note: For a corresponding nonstandard model, the device’s displayed Type does have to be changed.
Comm test
When debugger debug the device on-site in the case of no-accessing the actual analog electric
quantity or the input quantity, [Comm Test] is used to do the test of the communication node of
the device.
21
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
Addendum 1: Terminal diagram of the device
I/O POWER CPU A C
A PT Parallel B Input Com-
A02 PT Parallel B02 BK Switch NET
A03 Earth Signal B03 QF Switch
A Earth Signal B PT 1 DZ Position
A PT Failure B PT 1 DZ Position D01 Ua1 Ua1' D02
A06 PT Failure B06 Remote/Local
Bus 1 Voltage D03 Ub1 Ub1'D04
A07 Output B07 Input 6
A08 Bus 1 Voltage B08 NET2Input 7 D05 Uc1 Uc1' D06
Output
A09 Bus 2 Voltage B09 Input 8
Output
A Bus 2 Voltage
D07 Uo1 Uo1'D08
Input 9
Output B
A11 B11 Input D09 Ua2 Ua2' D10
A12 B12 Input
A13 B13 Input D11 Ub2 Ub2' D12
Run Light
A14 B14 Input 13 D13 Uc2 Uc2' D14
A15 B15 Input
A16 B16 Input D15 Uo2 Uo2' D16
D17 D18
DEBUG
D19 D20
A17 Parallel 1 B17 Input C01 GPS-A D21 D22
A18 Parallel 1 B18 Input C02 GPS-B D23 D24
A19 Parallel 2 B19 Input C03
A20 Parallel 2 B20 Input C04 COM1A
A21 Parallel 3 B21 Overhaul C05 COM1B 1.Ua1、Ub1、Uc1 are Bus 1 Voltage .
A Parallel 3 B (+24V) C06 Shielded ground 2.Ua2、Ub2、Uc2 are Bus 2 Voltage .3.U01、U02 are Bus ZS Voltage .
A23 Parallel 4 B23 4. Net1,Net2 are ethernetCommon terminal C07 COM2A ports,COM1,COM2 are 485 interfaces.
A24 Parallel 4 B24 Trip Signal C08 COM2B 5. If +24V on IO board is standard
configuration or not,it is used as input
A25 Parallel 5 B25 Alarm Signal C09 DCS1+ power supply only when using internal
A26 Parallel 5 B26 C10 24V.DCS1-
A27 Parallel 6 B27 Power off C11 DCS2+
A28 Parallel 6 B28 Power off C12 DCS2-
A29 Parallel 7 B29 Power
A30 Parallel 7 B30 Power
A31 Parallel 8 B31
A32 Parallel 8 B32 Shielded ground
Figure 1 Terminal diagram of MPTS-820Hc
PT paralleling and voltage protection device
22
User’s manual of MPTS-820Hc PT paralleling and voltage protection Device WLD[K]-JY-309-2018
Addendum 2: Typical wiring diagram of the device
QF
Switch
a1 a1 b1 b1 c1 c Ua2 Ua2 Ub2 Ub2 Uc2 Uc2 U02 U02
Bus 1 Voltage Bus 1 ZS Voltage Bus 2 Voltage Bus 2 ZS Voltage
AC
MPTS-820Hc
Parallel
Signal
Net 1
Earth
Signal
Net 2
PT Failure
DEBUG
Bus 1
Voltage
Output
Bus 2
Voltage
Output
Parallel1
COM A
COM B
I/O Parallel2
Shielded ground
COM A
Parallel3
COM B
Parallel4
Parallel5
Parallel6
Parallel7
Parallel8
Figure 2 Wiring diagram of MPTS-820Hc
PT paralleling and voltage protection device
23
CPU
Input Com- Input18
BK Switch Input19
QF Switch Overhaul
PT 1 DZ Position (24V+)
PT 2 DZ Position Common terminal
Remote/Local Trip Signal
Input6 Alarm Signal
Input7
Input8 Power off
Input9 Power off
Input10 Power
Input11 Power
Input12
Input13 Shielded ground
Input14
Input15
Input16
Input17
Power