Zhuhai Wanlida Electrical
Automation Co., Ltd.
http://www.zhwld.com
User’s manual of MGPR-850Hc generator grounding
protection device
Prepared by: Li Chang Wen
Proofed by: He Wenhui
Approved by:Lin Cunli
Document No.: WLD [K]-JY-319-2018 Version No.: V1.04.01
Date of publication: June, 2018
Copyright: Zhuhai Wanlida Electrical Automation Co., Ltd.
Note: Our Company reserves the right to modify this manual. For any inconsistency between
the product and this manual, please contact us for relevant services.
Technical support hotline: 0756-3395398 Fax: 0756-3395111
Foreword
F o r e w o r d
1. Model description
MGPR-850Hc is the microcomputer generator grounding protection device, the
structure type of MGPR-850Hc series protection is Hc.
2. Standards referenced
General specification for static protection, security and automatic equipment
DL 478-2010
Technical code for relaying protection and security automatic equipment
GB/T 14285-2006
Protective relay and automatic equipment design rules of power equipment
GB50062-2008
Transformer substation correspondence network and system DL/T 860.5-2006
Intelligent substation technology norms Q/GDW 383 -2009
Intelligent substation relay protection technical specifications Q/GDW_441-2010
IEC61850 engineering application model Q/GDW 396-2010
3. Caution
The appearance should be inspected before power is applied, to ensure that the panel is OK
without scratch, the screws are tightened, the device is grounded firmly, all screws of
plug-ins are tightened and in good contact.
When power is applied, the “Run” indicator on the panel should flash, primary differential
current data are displayed on the LCD in cycle.
Operating circuit inside the device is only applicable to DC power supply, if AC power is
used, it should be applied with rectifier and filter.
It is prohibited to plug or unplug the plug-ins, in order to avoid damage to the device.
It is prohibited to do digital output test when the device is running with primary equipments.
2
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
1. Product description
1.1 Scope of application
MGPR-850Hc microcomputer generator grounding protection device applies to
medium-small capacity generator protection, the device, MGPR-810Hc microcomputer
generator differential protection device, MGPR-820Hc microcomputer generator backup
protection measuring and control device together constitute a complete generator
protection.
1.2 Function and specification
1.2.1 Protective function
Rotor 1-point grounding protection
Rotor 2-point grounding protection
Fundamental zero sequence voltage protection(stator grounding protection )
Harmonic zero sequence voltage protection(stator grounding protection )
Zero sequence over-current protection(stator grounding protection)
1.2.2 Auxiliary function
Harmonic spectrum analysis
Phase display
Fault recorder
Self-checking fault alarm of device
Remote calling and modification of protection’s settings
One way (or two ways) programmable output of 4~20mA
Network print
Virtual correspondent node remote test
1.2.3 Monitoring function
Remote binary quantity: the device has 20-way binary input.
1.2.4 Communication capability
With industrial Ethernet port and standard RS485 multipoint communication port. Supports
MODBUS、IEC-60870-5-103(RS485 communication mode)、IEC-61850-5-104(Industrial
Ethernet communication mode) standard communication protocol and a new generation of
substation’s communication standard IEC 61850.
Supports single and dual network communication, it is fully qualified for network
redundancy and backup
1.2.5 GPS clock synchronization function
The device is able to receive GPS clock second synchronization or IRIG-B through RS485
differential voltage, and it can be done with monitoring system to accomplish GPS precise
clock synchronization or Ethernet-based SNTP synchronization.
3
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
1.2.6 Device specifications
32-bit POWERPC microprocessor
Real-time multi-task operating system and C++ program techniques, realizing online
programming
320*240 LCD display, easy for inspection
One or two ways 4~20mA DC quantity output, which can be set flexibly as any
corresponding electric quantity (such as voltage.)
Collecting 2 ways of 4~20mA DC quantities for measurement of non-electric quantities, such
as temperature, pressure, and realizing online monitoring. (optional)
Having perfect harmonic analysis function
Support network printing function, include two ways: real-time print and artificial print
Support virtual correspondent node remote test, including remote communication to
correspondent node, remote measure to correspondent node, event to correspondent node, can
online testing, it is convenient for debugger to debug the device on-site.
Excellent hardware interchangeability, user maintenance is easily and it reduced quantity of
spare parts
Protection output relays can be configured flexibly for user convenience
Using a 6U, 19/3” standard enclosure in a rear plug-in structure. the device can be installed in
site on a switchboard or combined in a centralized manner
1.2.7 Main technical specifications
Rated data
Power supply: DC/AC 86~265V
Operating voltage: DC 220V or DC 110V
AC voltage: 100/ 3 V or 100V
AC current: 5A or 1A
Frequency: 50Hz
Power consumption
DC circuit: <10W (normal operation). <15W (protection operation)
AC voltage circuit: <0.5VA/phase
AC current circuit: <1VA/phase (In = 5A). <0.5VA/phase (In = 1A).
Overload capability
AC voltage circuit: 1.2Un, continuous operation
Current measuring circuit: 1.2 In, continuous operation
Protective current circuit: 2In, continuous operation
10In, allowing 10s
40In, allowing 1s
Range and error of setting value
Maximum range of setting value:
4
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
Current element: 0.1In~20In
Voltage component:1V~120V
Timing element: 0.00s~100.00s
Error of setting value:
Current and voltage setting value: ≤±3% of setting value
Rotor grounding protection operation error:when 1k~5k,error does not exceed±0.5k;
when 5k~50k,error does not exceed ±10%;Rotor grounding protection delay error does not
exceed±1% setting +1s; grounding position setting error of rotor 2-point grounding protection
does not more than 10%.
Measuring accuracy
4~20mA DC quantity output: ≤±1%
Capacity of trip/closing output contact
Can be connected to DC 250V, 8A for prolonged periods.
GSP clock synchronization error
Clock synchronization error≤2ms
Environmental conditions
Ambient temperature:
Operating:-20℃~+55℃.
Storage:-25℃~+70℃, rainproof and snow-proof rooms with relative humidity not
greater than 80%, ambient air free of acid, alkaline or other corrosive and explosive gas. No
excitation quality is applied at the limits, the device shall not have any irreversible change.
After temperature restoration, the device shall operate properly.
Relative humidity:
The average relative humidity of the most humid month shall not be greater than 90%,
the average minimum temperature of this month not lower than 25℃ and there shall be no
surface condensation. At the highest temperature of +40℃, the average maximum humidity
shall not exceed 50%.
Atmospheric pressure: 80kPa~110kPa (below relative altitude of 2KM)
1.2.8 Hardware structure
The device uses a 6U, 19/3” standard enclosure, with aluminum alloy casing and installed by
overall embedding. The display panel is mounted in the front, and the other plug-in modules are
rear mounted. From the rear view, I/O, the power, CPU and AC plug-in modules are from the left
to the right.
External dimensions and boring diagram
Structural and dimensional diagram Boring diagram for installation
Devices fabricated on-screen steps: first release on-screen stents unfastening screws, remove
the stents. Install the device on the screen from the front and push until close to the fixed plate.
5
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
Install the stent 2, and then stent 1, and then use fastening screw to insertion hole from rear of
stent1, and then screwed into stent 2 and tighten screw. The stents from up and down are installed
in the same way. Use grounding screws to connect grounding line.
2. Function of device
2.1 Rotor grounding protection
The device employs Ping-Pong switching theory, calculating the grounding resistance
and grounding position by solving two different grounding circuit equations. The principle
is shown in Fig.2-1. Which: S1, S2 are electronic switches controlled by microcomputer,
Rg is the grounding resistor, a is the grounding position, E is the rotor voltage. Ra, Rb as
the voltage lower voltage resistors, R1 as measuring resistor.
Fig.2-1 Rotor grounding protection switching sampling principal diagram
6
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
Calculate and store grounding position, and it is used for judging 2-point grounding. In
order to prevent from misoperation and calculation overflow, startup logic is applied,
E>30V.
When Rg is smaller or equal to grounding resistance setting, rotor 1-point grounding
operates after time delay, the output can be selected either alarm or trip. The protection is
equipped with software control word, hard strap. The protection operation logic is as
Fig.2-2.
ON/OFF
One point grounding & Protection output
t/0 sequence
R g ≤grounding resistance setting
Fig.2-2 Rotor 1-point grounding protection operation logic
2.2 Rotor 2-point grounding protection
If generator is 1-point grounding, it is not harmful to generator, if it is another point
grounding, it would be a serious threat to the safety of generator.
After 1-point fault occurs, the protection device will continue to measure the
grounding resistor and grounding position, when another grounding occurs, the variation
of a is detected, if the variation value △a is higher than setting, the device will judge that
2-point grounding occurs, the generator is tripped immediately. The protection is equipped
with software control word, hard strap. The protection operation logic is shown in Fig.2-3.
ON/OFF
Two points
grounding & t/0
Protection
Rg ≤grounding resistance setting & t/0 output sequence
△a >a set
Fig.2-3 Rotor 2-point grounding protection operation logic
2.3 Stator grounding protection
As stator circuit single phase grounding protection of generator, when any point of
the stator of generator single phase grounding, the protection operates after the required
delay, the output can be selected either signal or trip.
Base frequency zero sequence voltage protects stator winding single phase
grounding of 85%~95% from generator terminal;
3rd order harmonic voltage protects stator winding single phase grounding around
neutral point.
7
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
Base frequency zero sequence voltage operation logic is as:
∣Un∣>Uop
3rd order harmonic voltage operation logic is as:
Scheme 1:∣Us3∣≧Kz∣Un3∣
Scheme 2:∣Us3+Kp﹡Un3∣≧Kz∣Un3∣
Either of the 2 schemes can be selected through protection ON/OFF setting.
Uop is the base frequency zero sequence voltage setting; Un is neutral point TV, if
there is no TV at neutral point, generator side base frequency zero sequence voltage may
be used; Us3 and Un3 are generator side TV open-delta winding and 3rd order harmonics
at neutral point TV output accordingly; Kp is the ratio balancing coefficient, Kz is restrain
coefficient, they are different positive real numbers.
Zero sequence voltage criterion and 3rd order harmonics criterion are equipped with
their own output circuit, The protection is equipped with software control word, hard strap
(Stator grounding plate).
The protection operation logic is shown in Fig.2-4.1 and Fig.2-4.2.
Us>setting value ON/OFF Protection
& t/0 output
Zero sequence Block ON/OFF sequence
voltage of HV
side<setting value
Fig.2-4.1 Stator grounding base frequency protection operation logic
Fig.2-4.2 Stator grounding harmonic protection operation logic
2.4 Zero sequence over-current protection
As stator circuit single phase grounding protection of generator, when any point of
the stator of generator single phase grounding, the protection operates after the required
delay, the output can be selected either signal or trip. The zero sequence block voltage
8
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
and direction voltage used are acquired from generator terminal zero voltage, and zero
sequence block and direction can be set to ON or OFF.
The protection is equipped with software control word, hard strap (Stator grounding
plate). The protection operation logic is shown in Fig.2-5.
Fig.2-5 Zero sequence over-current protection operation logic
2.5 Fault Record
It records the current waveform sampled by the device, for more information please refer to
communication code table.
2.6 Network print
Device supports network printing function, can print remote control information, SOE
information and the setting parameter list. The printer IP address must been set rightly on the
device (the network segment of printer must be as same as that of device IP addresses), then
connect a printer, put on "real-time report print ", it can print the current remote control
information or SOE information when device is connected to the back-ground (including remote
communication shift, protection action), and can print the current SOE information when device is
not connected to the background. In addition, when press the "ok" button in the "print report" or
"print setting value" menu, it can print the all setting parameter or the all report information,
including action value.
2.7 Virtual correspondent node remote test
The function is used to complete the communication node remote test of the device, do not
need to access the actual analog electric quantity or the input quantity. Specific operation as
follows, connect to the background, In the remote test menu, operate the “virtual input test”, the
“virtual measure test” and the “virtual SOE test” menu in the “remote test” menu, press the "OK"
button after the modification of various settings, then by observing the background pop-up
warning window or the change of the corresponding value, to determine whether the device
communication node is right. It is convenient for debugger to debug the device on-site. When you
are in the mode of remote test, the all protect must be off.
2.8 GPS clock synchronization
The GPS clock synchronization signal is input as rs485 differential voltage, the device is able
to receive GPS clock second synchronization. If there is GPS signal, there will be flashing
on the bottom of cycle menu. Otherwise won’t.
The principle of GPS clock synchronization: The second pulse or minute pulse act with the
monitoring system, the time base with second precision is sent by monitoring system, when the
9
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
GPS second differential signal arrives, the time base is unified and the milliseconds are cleared.
The device is able to receive GPS clock second synchronization or IRIG-B through RS485
differential voltage, and it can be done with monitoring system to accomplish GPS precise clock
synchronization or Ethernet-based SNTP synchronization.
2.9 Overhaul status
When the device put into overhaul plate, remote sign, remote measure can uploading
background computer. But the device can’t remote control by background computer. The SOE
event、Alarm event、Trip event, etc also can’t uploading background computer.
3. Setting of parameters and setting values of the device
3.1 System parameters
Parameter Range Description
Settings of setting value zone number(Setting Zone No.)
Setting value zone
0-7 Set step:1(factory default 0)
number(Setting Zone No.)
Communication settings(Comm. Setting)
Set step :1 (factory default 1)
NET Protocol 0-2
(0-Quit;1-IEC104; 2-IEC61850)
Set step :1 (factory default 0)
RS485 Protocol 0-2
(0-Quit;1-IEC103; 2-Modbus)
RS485 address(RS485
1-99 Set step:1(factory default 1)
Address)
RS485 baud rate(RS485 Set step:1(factory default 2)0:2.4KB;1:4.8KB;
0-5
Baudrate) 2:9.6KB;3:19.2KB;4:38.4KB;5:115.2KB;
IP address(IP Address) One section set step:1(factory default 192.168.0.253)
SNTP Address (SNTP It has four
One section set step:1(factory default 192.168.0.254)
Address) sections. The
KW default value(KW range of every
One section set step:1(factory default 12.8.6.1)
Default) section is
Printer IP address(Printer 0-255
One section set step:1(factory default 192.168.0.255)
IP)
Setting of basic parameters(B. Parameters)
Earth Mode 0-1 00:No Earth, 01:Earth(major grounding),
For harmonic calculation, select the corresponding
Harmonic Channel 0-4 reference quantity:
0:exit from harmonic calculation function
1:Us,2:Un,3:Ug,4:I0
10
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
Parameter Range Description
Wave Record 0-1 Set step:1(factory default 0)00:Off;01:On
Hard Plate 0-1 Set step:1(factory default 0)00:Off;01:On
Set step:1(factory default 0)00:Normal;01:Test(set
Rotor PROT Mode 0-1 rotor protection on debug status, in order to test
zero-drift voltage of RU, EU, that is dRU, dEU)
Set step:1(factory default 0)00:Scheme 1;01:Scheme
Harmonic protection
0-1 2
program choice
For harmonic zero sequence stator grounding protection
Remote communication
10-100ms Set step: 1 (factory default 40ms)
ack time (input ack time)
Real-time print report
0-1 Set step: 1 (factory default 0) 00:exit;01:on
on/off(auto print report)
D/A channel setting(D/A Setting)
Select DA1~2 to output corresponding reference
quantities:
DA1~2 Channel 0: No D/A output 1:Us, 2:Un, 3:Ug
0-3
Selection Voltage reference quantity: 0-120V corresponding to
4mA-20mA
DA1~2 Adjustment
0.05-1.5 Adjust D/A channel 1~2(4-20mA) parameters
Factor
Channel factor setting(Channel Coef.)
Channel coefficient 1 0.500-5.000 Adjust channel 1 analog reference value(Us)
Channel coefficient 2 0.500-5.000 Adjust channel 2 analog reference value(Un)
Channel coefficient 3 0.500-5.000 Adjust channel 3 analog reference value(Ug)
Channel coefficient 4 0.500-5.000 Adjust channel 4 analog reference value(I0)
Channel coefficient 5 0.500-5.000 Adjust channel 5 analog reference value(magnetizing
voltages)
Channel coefficient 6 0.500-5.000 Adjust channel 6 analog reference value(switching
voltage RU0)
Channel coefficient 7 0.500-5.000 Adjust channel 7 analog reference value(switching
voltage RU1)
Channel coefficient 8 0.500-5.000 Adjust the coefficient of ground resistance Rg
dRU, the zero-drift voltage of RU. The integer digit
Channel coefficient 9 0.000-1.200 stands for sign bit, 1 stands for negative, 0 stands for
positive; the fraction digits stand for data.
dEU, the zero-drift voltage of EU. The integer digit
Channel coefficient 10 0.000-1.200 stands for sign bit, 1 stands for negative, 0 stands for
positive; the fraction digits stand for data.
11
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
3.2 List of setting values
Setting value Range Description
Rotor grounding section I
(Rotor 1-point ) 1/0 1/0:on/off(factory default off) Ⅰ
(Rotor grounding section II)
Rotor 1-point 1/0 1/0:on/off (factory default off) Ⅱ
Rotor 2-point 1/0 1/0:on/off (factory default off)
Fundamental zero sequence protection
(Fund.harm.ZS U) 1/0 1/0:on/off (factory default off)
High voltage side zero sequence block
(High-vol.ZS Lock) 1/0 1/0:on/off (factory default off)
Harmonic zero sequence protection
(Harm.ZS U) 1/0 1/0:on/off (factory default off)
zero sequence over-current section I 1/0 1/0:on/off (factory default off)
Zero sequence over-current section II 1/0 1/0:on/off (factory default off)
Zero voltage block zero current
(ZSV Lock ZSI) 1/0 1/0:on/off (factory default off)
Zero sequence current section I
direction 1/0 1/0:on/off (factory default off)
Zero sequence current section II
direction 1/0 1/0:on/off (factory default off)
Rotor 1-point grounding
1-point Section I resistance
setting(Rotor 1-point 1R) 1.0-50.0kΩ
Set step:0.01 KΩ(factory default 50 kΩ)
1-point Section I time of delay
(Rotor 1-point 1T) 1.0-10.0s
Set step:0.01S(factory default 10s)
1-point Section II resistance setting Set step:0.01 KΩ(factory default 20 kΩ)
(Rotor 1-point 2R) 0.5-20.0kΩ
1-point Section II time of delay Set step:0.01s(factory default 10s)
(Rotor 1-point 2T) 1.0-10.0s
Rotor 2-point grounding
2-point resistance setting 1.0-50.0kΩ Set step:0.01(factory default 50 kΩ) (Rotor Ground R)
2-point time of delay Set step:0.01S(factory default 50s)
(Rotor Ground T) 1.0-50.0s
Grounding position change △ a Set step:0.01(factory default 100)
(%)(Ground P.Δa(%)) 1.0-100.0
Rotor 2-point T 1.0-50.0s Set step:0.01s(factory default 50s)
Fundamental zero sequence stator grounding
Fundamental harmonic voltage Set step:0.01V(factory default 120V)
(Fund.Harm.U) 1-120V
High voltage side block zero Set step:0.01V(factory default 120V)
sequence voltage 1-120V
(High-vol.ZS Lock)
Fundamental harmonic delay Set step:0.01s(factory default 100s)
(Fund.harm.T) 1-100s
Harmonic zero sequence stator grounding
Harmonic ratio Kz Set step:0.01 (factory default 2)
(Harm. Ratio Kz) 0.5-2
12
Protection on/off word
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
Setting value Range Description
Third harmonic delay 1-10s Set step:0.01S(factory default 10s) (3rd harm.T)
Balance coefficient Kp 0.2-4 Set step:0.01 (factory default 4) (Eq.Coef.Kp)
Zero sequence current stator grounding
Section I current setting 0.01-100.00A Set step:0.01A(factory default 2A) (ZS OC Value1)
section I time of delay 0.1-100s Set step:0.01S(factory default 100s) (ZS OC T1)
Section II current setting 0.01-100.00A Set step:0.01A(factory default 2A) (ZS OC Value2)
Section II time of delay 0.1-100s Set step:0.01s(factory default 100s) (ZS OC T2)
Zero sequence Set step:0.01V(factory default 50V)
voltage block of Zero sequence
over-current 1-50V
(ZS Voltage Lock)
Zero sequence Set step:0.01º(factory default 359 º)
over-current direction sensitive
angle 0-359º
(Dir.Sen.Angle)
4. Description of binary input, output and analog quantity
4.1 Monitoring of analog quantities
Analog quantities can be monitored under the [Protection Data], [Measured Data] and [Pulse
Energy] menus in the [Run States] menu, press the “”, “” keys to flip over. The factory
precision of the device has been calibrated. The protection current is calibrated at double the rated
current. The list is as follows:
Analog quantity Analog quantity
Test method
terminal name
Terminal D01, D02 Generator terminal Add 50V, displayed deviation not exceed±1% zero sequence voltage
Terminal D03, D04 Neutral point side Add 50V, displayed deviation not exceed±1% zero sequence voltage
Terminal D05, D06 High voltage side zero Add 50V, displayed deviation not exceed±1% sequence voltage
Terminal D07, D08 Zero sequence current Add 2A, displayed deviation not exceed±1%
Note: The following six items can be inspected in [Channel coefficients setting] in
[System parameters], they are only used for factory testing and setting. Please set
according to the following order.
Excitation voltage must not be added, set all
rotor grounding protection to OFF, set rotor
Not add magnetizing grounding protection to debug state, save system
RU zero-drift voltage
voltage parameter, reenter menu[Channel coefficient
9],set according to dRU displayed to channel
coefficient 9. For example, if it is -0.025V, just
13
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
Analog quantity Analog quantity
Test method
terminal name
set as 1.025; if it is 0.028V, just set as
0.028.(Note: The integer digit stands for sign bit,
if absolute value of zero-drift exceeds 0.2V, it is
recommended to replace the AC board).
The Setting method of channel coefficient 10 is
Not add magnetizing
EU zero-drift voltage the same with that of channel coefficient 9. After
voltage
setting,set rotor protection operating mode on 0.
Add DC 100V, displayed deviation not exceed
Terminal D09, D11 Magnetizing voltage 2%;there is deviation,adjust channel coefficient
5.
In menu, set rotor 1-point or rotor 2-point
protection to on and short connect terminals D11,
Switching voltage D13, add positive DC100V to D09, D11,check
Terminal D09, D11
RU0 in【channel coefficient 6】, it should display
1.32V,deviation should not exceed 0.01V;if
there is deviation,adjust channel coefficient 6.
In menu, set rotor 1-point or 2-point protection
to on and short connect D09, D13,add positive
Switching voltage DC100V to D09, D11 , check in 【 channel
Terminal D09, D11
RU1 coefficient 7】,should display 1.32V,deviation
not exceed 0.01V;if there is deviation,adjust
channel coefficient 7.
Under menu, set rotor 1-point or 2-point
protection to on and connect resistance 10KΩ
between D11, D13,add positive DC100V to
Terminal D09, D11, Adjust grounding
D09, D11,check in 【channel coefficient 8】,
D13 resistance coefficient
it should display 10KΩ,deviation not exceed
0.5KΩ; if there is deviation,adjust channel
coefficient 8.
Note: After setting above, test positive to shaft grounding and negative to shaft
grounding, if deviation of the 2 resistances are high, firstly fine-tune channel
coefficient 6, 7, after the deviation becomes low, fine-tune channel coefficient 8.
14
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
4.2 Monitoring of binary input
Binary input can be monitored under the [Binary input] menu in the [Run States] menu, press
the “”, “” keys to flip over.
Binary input Binary input name Test method
terminal
B01 Common terminal of binary input -
(Should be connected to DC220V
or DC110V
negative terminal of external power
supply)
B02 Input 1
B03 Input 2
B04 Input 3 External power supply of 220V or 110V DC
B05 Input 4 can be applied, connect the negative terminal
B06 Input 5 to terminal B01, positive terminal to terminal
B07 Input 6 B02~B21, in [Binary input] menu in the
B08 Input 7 [Run States], the status of binary input can be
B09 Input 8 seen.
B10 Input 9 The device also has a 24V DC supply, if
B11 Input 10 it is used, terminal B22 can be connected to
B12 Input 11 terminal B02~B21, in [Binary input] menu
B13 Input 12 in the [Run States], the status of binary input
B14 Input 13 can be seen.
B15 Input 14 Please note about the binary input voltage
B16 Input 15 upon ordering, it is set to DC220V by default.
B17 Input 16
B18 Rotor 2-point strap
B19 Rotor 1-point strap
B20 Stator grounding strap
B21 Overhaul
B22 Positive terminal of internal 24V
power supply
4.3 Monitoring of binary output
Binary output can be monitored under the [Binary output] menu, press the ““, ““ keys to
flip over.
Binary output terminals Binary output name Test method
A17-A18 Spare Trip Node Select open and close menu, use “+”,
15
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
A19-A20 Trip Main Switch “-” key to operate and test the
A21-A22 Trip Field Discharge Switch corresponding terminals.
Close Steam valve/Guide
A23-A24
hydrofoil
Rotor 1-point grounding
A25-A26
output
A27-A28 Output 6
A29-A30 Output 7
A31-A32 Output 8
B23-B24 Trip Signal
B23-B25 Alarm Signal
5. Operation instructions
5.1 Control panel of device
320*240 matrix LCD (The LCD will go off after a period of absence of keyboard operation. the
LCD will be illuminated automatically when any key is pressed or in case of protection trip or
alarm.)
Signal indicator: run, communication, trip, alarm, fault (of the device), spare, remote.
Key pad: , , , , Cancel, -, +, Enter, Revert
5.2 Instructions for use of key pad and LCD display
During the device’s normal operation, it will display the primary differential current data 、
device address and time in cycle. Press the “Enter” key to enter the main menu, which is a
multi-level tree menu. Press the ““, ““ keys to move the cursor to the desired entry, press the
16
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
“Enter” key to enter this entry, and press the “Cancel” key to return to the next higher level of
screen. If this screen is still a menu, continue to press the ““, ““ key to select the desired entry,
press the “Enter” key to enter the next level of screen, and press the “Cancel” key to return to the
next higher level of menu. If there is no menu screen, be sure to press the “Cancel” key to return
to the next higher level of menu. The main menu is shown at the center of the following figure,
with the corresponding submenus on both sides.
01.Run States -1/5- Main menu 05.Report Dis. -1/5-
Protection Data Trip Report Binary Input Binary Report
Soft Strap 01.Run Status Event Report
Harmonic Data 02.Run Parameters Print Report AD Volt. Data
03.Setting View 06.Parameters -1/9- Comm. Setting
02.Run Param. -1/3-
B. Parameters Setting Zone No. 04.Setting Value D/A Setting
PROT On/Off
Clock Setting 05. Report Manage Channel Coe.
Language Select
06. SYS Parameters
03.Setting View-1/6-
Rotor 1-point Ⅰ 07.Device Test
07.DeviceTest. -1/2-
Output Test
Lamp Test
Rotor 1-point Ⅱ
08.PassWord ......
09.Version Info. 08.Password □□□□
04.Setting Value-1/6- 10.Comm Test
Rotor 1-point Ⅰ PROT AUTO DEV V2.00
Type:MGPR-850Hc Rotor 1-point Ⅱ 10.Comm test
...... Input Test
ID:□□.□□.□□
Measure Test CRC:□□□□□□□□
SOE Test Date:20XX-XX-XX
Note 1:For the Setting menu, see the description of each device.
Run Status
The [Run Status] menu contains 5 submenus, including protection data, binary input, soft
strap, harmonic data, AD voltage data. It is described as follows:
PROT Data -1/9-
Us = □□□·□□ V 000.0°
Un = □□□·□□ V Secondary value of generator terminal zero
000.0° sequence voltage, neutral point zero
Ug = □□□·□□ V sequence voltage, high voltage side zero
000.0° sequence voltage, zero sequence vo current
I0 = □□□·□□ A secondary value
000.0°
Us3 =□□□·□□ V They are generator terminal zero sequence
Un3 = □□□·□□ V voltage 3rd order harmonics, neutral point zero
E = □□□·□□ V sequence voltage, Magnetizing voltage, rotor
Rg = □□□·□□ kΩ grounding resistance, rotor grounding position
a = □□□·□□ %
17
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
Binary Input -1/20-
Input 1 :□ Standby binary input
Input 2 :□
Input 3 :□
Input 4 :□
Input 5 :□
...... Description varies with model, see corresponding terminal
Transverse differential strap :□ diagram for details
D ifferential protection strap :□
Note: In the standard configurations, the input circuit has the connection to an external
220VDC control power supply. When no DC control power supply or control system is available
on site, but a 110VDC control power supply is available, a 110VDC control power supply may be
used for direct connection through local hardware adjustment, or the 24V power supply of the
device may be used as the input power supply (when the input common terminal is +24V, terminal
number: B22, Terminal B01 is kept float). However, this must be specified upon ordering.
Soft Strap -1/11-
Rotor1-pointⅠ Off
Rotor 1-point Ⅱ Off
......
Harmonic Data -1/10-
2nd : □□□·□□%
3rd : □□□·□□%
4th : □□□·□□% 2~11 harmonics for which analog channels
5th : □□□·□□%
...... have been selected in system
11th :□□□·□□%
AD Volt. Data -1/2-
AD1:□□·□□□V AD Voltage Check
AD2:□□·□□□V
Run Parameters
In the [Run Parameters] menu includes 3 submenus, including [Setting Zone No.]、[PROT
On/Off]、[Clock Setting], The screen Content is as follows:
Setting Zone No. :Range 00~07.
PROT On/Off:The device protect plate can be select in this menu.
PROT On/Off -1/11- Parameter Modify
Rotor1-poinⅠ
On Off ◇Enter ◆Cancel
18
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
Press “+”, “-” keys to select the protection function On or Off. The interface will eje
ct the window as right chart show when you press the “Enter” key. Move the cursor to t
he desired position for modification by pressing the “”, “” keys. Press the “Enter” key
to complete setting, and the device will prompt modifying success or not. If the “Cance
l” key is pressed, the protect plate status setting will be cancelled and the menu will retur
n previous menu.
Clock setting:
A battery-back real-time clock is provided in the device, which can perform time adjust
remotely via the communication network or in-site time adjust in the [Time Setting] menu.
Enter this menu and press the “Enter” key, the clock will stop refreshing and a cursor will
Clock setting appear. Move the cursor to the desired position for modification
by pressing the “”, “” keys, modify to the desired value with
Date:20□□-□□-□□ the “+”, “-” keys. Press the “Enter” key to complete setting. If
Time: □□:□□:□□
the “Cancel” key is pressed, the setting will be cancelled and
the screen continues to refresh the clock.
Setting View
This meun just for query.You can’t modif the value to prevent faulty operation.
Setting Value
After entering the password, you can enter the [Setting Value] menu. See the settings
description of the protection device for the detailed description.
Report Manage
The [Report Manage] menu includes 4 submenus, including trip report, binary report, event
report and print report. Event recording includes: device self-check fault, device setting value
modification, system parameter modification and setting zone number modification, etc. Trip
report can be record for the last 50 events, binary report for 100, event report for 30 at most.
Beyond this, the latest report will overwrite the earliest one. Press the “Enter” key to enter the
corresponding [To view xx report, please enter report number: 00] menu, and enter any figure
within storage volume, press the “Enter” key to display the contents of that report. The screen is as
follows:
Report No.:□□ ↓ Report No. of this report
Year, month, day, hour, minute, second and 20□□-□□-□□ millisecond when it took place
□□:□□:□□:□□□
□□□□□□
Press key to see the specific operation value. Press and keys to flip over. Operation
values.
Action value view
19
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
Us = □□□·□□ V
Un = □□□·□□ V
Ug = □□□·□□ V
I0 = □□□·□□ A
Us3 = □□□·□□ V
Un3 = □□□·□□ V
……
System parameters
After entering the [SYS Parameters] menu, the correct password is required to enter the [SYS
Parameters] menu. It displays the following:
Parameters -1/9-
Comm. Setting
Transformer Coe.
B. Parameters
D/A Setting
Channel Coe.
Language Select
Communication Setting
Comm. setting -1/7-
NET Protocol
□□ 00:Quit; 01:IEC104; 02:IEC61850;
RS485 Protocol
□□ 00:Quit; 01:IEC103; 02:Modbus;
RS485 Address
□□ Communication address of device 01~99
RS485 Baud rate
□□ 00:2.4KB;01:4.8KB;02:9.6KB;03:19.2KB;04:
IP Address
□□□. □□□. □□□. □□□ 38.4KB;05:115.2KB
SNTP Address
□□□. □□□. □□□. □□□ K W Default For Ethernet communication
□□□. □□□. □□□. □□□
Printer IP
□□□. □□□. □□□. □□□
Setting of basic parameters (see the description of the protection device for basic parameters)
B.Parameters: -1/8-
Rating Current
□□ Setting the CT secondary current rating 00: 5A. 01: 1A
Harmonic Channel
Setting analog quantity channels 0~4 for harmonic monitoring, select 0 □□
Wave Record to exit from the harmonic calculation function
□□
......
20
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
D/A setting
The device has two 4~20mA outputs. The DA1~DA2 adjustment factor is used to adjust the
accuracy of the channel output. The DA1~DA2 channel selection is used to select the
corresponding analog quantity channel (see the description of the protection device for specific
reference quantities). In the accuracy test, make sure the field ground is in good contact.
Otherwise the accuracy might be affected.
Channel Coefficient
The device can adjust channel coefficient by this menu to raise Sample size.
Device test
After entering the [Device Test] menu, the correct password is required to enter the [Device
Test] menu. It’s have two menu include [Output Test] and [Lamp Test].
Output Test
Enter [Output Test] menu, It displays the following:
Output Test -1/11-
Spare Trip Node
Trip Main Switch Press “Enter” key Spare Trip Node
Trip Field Discharge Switch On Off
Close Steam valve/Guide hydrofoil Note:
…… Node:A17,A18 Open
Operate All Press “Cancel” key
(Note: When the test is performed on the 6 protection outputs, the starting relay will be in the
“Closed” state automatically. The “+”, “-” keys are used for switching between the “Close/Open”
control.)
Lamp Test
Lamp Test
◇Light ◆Quench
Used for testing Stand or fall of all LED lights.
Password
The [Password] menu is used to modify the password for entry into the Settings, System
parameters and Output Test submenus. The initial password is provided by the factory. The
universal password is “1000”.
Move the cursor to the desired position for modification by pressing the ““, “” keys,
Input password modify to the desired password with the “+”, “-” keys. Press the
0 0 0 0 “Enter” key to enter the new password setting menu as above.
Press the “Cancel” key to cancel the setting.
Version information
In the main menu, after entering the [Version Info.] menu, the Type, ID, CRC and Date of the
software will be displayed.
21
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
PROT AUTO DEV V2.00
Type:MGPR-850Hc
ID:□□.□□.□□
CRC:□□□□□□□□
Date:2017-12-20
Note: For a corresponding nonstandard model, the device’s
displayed Type does have to be changed.
Comm test
When debugger debug the device on-site in the case of no-accessing the actual analog
electric quantity or the input quantity, [Comm Test] is used to do the test of the communication
node of the device.
6. Check of protection function
6.1 Check of rotor 1-point grounding protection
Wire as Fig 6-1,set rotror1-point grounding sectionⅠ, Ⅱ to on,set hard strap to on.
(Optional, if input requires external terminals B19)Set and take down as Tab 6-1,test
operating resistance. connect terminal S to terminal D09 D11 respectively,adjust resistor
to reduce resistance till protection operates. When protection op(erates, terminals
corresponding to 1-point grounding protection output control word should be connected.
Tab.6-1
1-point grounding resistance
setting(KΩ) 10.00 20.00 50.00
Connect S to Operating value (KΩ) D09 Error (%)
Connect S to Operating value
D11 (KΩ) Error (%)
MGPR-850Hc
B29
+ D09
DC 100V Power supply
D11 B30
-
S D13
50KΩ
Fig. 6-1
6.2 Check of rotor 2-point grounding protection
Wire as Fig 6-2,set rotor 2-point grounding protection to on,set hard strap to on..
(Optional, if input requires external terminals B18)When protection operates,terminals
corresponding to rotor 2-point grounding output control word should be connected. Set
and take down as Tab 6-2,test operating resistance and the change of grounding position.
Notice that resistor R0 of slip-line rheostat should be 100~300, power should be higher
22
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
than U2/R0.
Fig. 6-2
Tab.6-2
Rotor 2-point grounding resistance
setting(KΩ) 10.00 20.00 50.00
Operating value (KΩ)
Error (%)
Rotor 2-point grounding △a
setting( ) 10 20 30 %
Operating value (%)
Error (%)
6.3 Check of fundamental and harmonic stator grounding protection
6.3.1 Check of fundamental zero sequence voltage protection
Wire as Fig 6-3,set fundamental zero sequence voltage protection to on. When
protection operates,terminals corresponding to protection output control word should be
connected. Set and take down as Tab 6-3,test operating zero sequence voltage.
Tab.6-3
Setting (V) 20.00 30.00
Add Un Operating value (V)
Error (%)
MGPR-850Hc
Us D01 B29
D03
Un
Power supply
D05 B30 Ug
(N) D02(04, 06)
Fig. 6-3
Fig. 6-3
23
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
6.3.2 Check of harmonic zero sequence voltage protection
Wire as Fig 6-3,set harmonic voltage protection to on. When protection operates,
terminal corresponding to protection output control words should be connected. Set and
take down as Tab 6-4,test operating zero sequence voltage .
Tab.6-4
Setting (Kz) 2 2
Setting (Kp) 1 1.5
Add the third Operating value (Us3)
harmonic of Us
and Un Error (%)
Operating value (Un3)
Error (%)
6.4 Check of zero sequence over-current stator grounding protection
Wire as Fig 6-4,set zero sequence over-current section I, II to on,set hard strap
protection to on. (Optional, if input requires external terminals B20)Set and take down
as Tab 6-5,test operating zero sequence current. When protection operates,terminal
corresponding to zero sequence over-current protection output control words should be
connected.
Tab.6-5
Zero sequence
over-current setting (A) 0.50 1.00 1.50
Operating value(A)
Error (%)
MGPR-850Hc
Us D01 B29
Us’ D02
Power supply
I0 D07 B30
I0’ D08
Fig. 6-4
24
User’s manual of MGPR-850Hc generator grounding protection device
WLD[K]-JY-319-2018
Addendum 1: Terminal diagram of the device
I/O POWER CPU A C
Input comon
B01 point-
B02 Input 1 NET D01 Us Us' D02
B03 Input 2 D03 Un Un' D04
B04 Input 3
B05 Input 4 D05 Ug Ug' D06
B06 Input 5
B07 Input 6 D07 I0 I0' D08
B08 Input 7 NET2 D09 Excitation
B09 Input 8 voltage+
D10
B10 ExcitationInput 9 D11 voltage- D12
B11 Input 10
B12 D13 D14Input 11 Shaft
B13 Input 12 D15 D16
B14 Input 13
Run Light
B15 Input 14 D17 D18
B16 Input 15
D19 D20
DEBUG D21 D22
D23 D24
A17 Spare Trip Node B17 Input 16 C01 GPS-A 注:
A18 Spare Trip Node B18 Two points of C02 GPS-B 1.Us is zero sequencerotor plate
voltage of generator end
A19 Trip Main Switch B19 One points ofrotor plate C03
Stator side.A20 Trip Main Switch B20 grounding plate C04 COM1A 2.Un is zero sequence
A21 Trip Field?Discharge B21 Overhaul C05 COM1B voltage of neutral side.Switch
Trip Field?Discharge 3.Ug is zero sequenceA22 Switch B22 (+24V) C06 Shielded ground voltage of main
A23 Close SteamValve/Guide hydrofoil B23 Common terminal C07 COM2A transformer HV side.
A24 Close Steam B24 Trip Signal C08 COM2B 4.I0 is zero sequenceValve/Guide hydrofoil curent of generator end
A25 One point ofrotor Output B25 Alarm Signal C09 DCS1+ side.
A26 One point ofrotor Output B26 C10 DCS1-
5.COM1,COM2 are 485
interfaces;Net1,Net2 are
A27 Output 6 B27 Power off C11 DCS2+ Ethernet interfaces.
A28 Output 6 B28 Power off C12 DCS2- 6.+24V on power board is
A29 B29 Power not the standardOutput 7
configuration, it is
A30 Output 7 B30 Power used as input power
A31 Output 8 B31 suply only when using
internal 24V.
A32 Output 8 B32 Shielded ground
Figure 1 Terminals diagram of MGPR-850Hc microcomputer generator
grounding protection device
25