Zhuhai Wanlida Electrical
Automation Co., Ltd.
http://www.zhwld.com
User’s manual of MGPR-810Hc generator differential
protection device
Prepared by: Qiu Lei
Proofed by: He Wenhui
Approved by:Lin Cunli
Document No.: WLD [K]-JY-317-2018 Version No.: V1.03.02
Date of publication: June, 2018
Copyright: Zhuhai Wanlida Electrical Automation Co., Ltd.
Note: Our Company reserves the right to modify this manual. For any inconsistency between
the product and this manual, please contact us for relevant services.
Technical support hotline: 0756-3395398 Fax: 0756-3395111
Foreword
F o r e w o r d
1. Model description
The structure type of MGPR-810Hc series protection is Hc, device supports A, B, C
three phase current protection.
2. Standards referenced
General specification for static protection, security and automatic equipment
DL 478-2010
Technical code for relaying protection and security automatic equipment
GB/T 14285-2006
Protective relay and automatic equipment design rules of power equipment
GB50062-2008
Transformer substation correspondence network and system DL/T 860.5-2006
Intelligent substation technology norms Q/GDW 383 -2009
Intelligent substation relay protection technical specifications Q/GDW_441-2010
IEC61850 engineering application model Q/GDW 396-2010
3. Caution
The appearance should be inspected before power is applied, to ensure that the panel is OK
without scratch, the screws are tightened, the device is grounded firmly, all screws of
plug-ins are tightened and in good contact.
When power is applied, the “Run” indicator on the panel should flash, primary differential
current data are displayed on the LCD in cycle.
Operating circuit inside the device is only applicable to DC power supply, if AC power is
used, it should be applied with rectifier and filter.
It is prohibited to plug or unplug the plug-ins, in order to avoid damage to the device.
It is prohibited to do digital output test when the device is running with primary equipments.
2
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
1. Product description
1.1 Scope of application
MGPR-810Hc microcomputer generator differential protection device applies to
medium-small capacity generator protection. The device, MGPR-820Hc microcomputer generator
backup protection measuring and control device, MGPR-850Hc microcomputer generator
grounding protection device together constitute a complete generator protection.
1.2 Function and specification
1.2.1 Protective function
Differential instantaneous over-current protection
Complex percentage differential protection
Transverse differential protection
Differential over-current alarm
CT failure protection
No-electric quantity protection(2 way)
1.2.2 Auxiliary function
Harmonic spectrum analysis
Phase display
Fault recorder
Self-checking fault alarm of device
Remote calling and modification of protection’s settings
One way (or two ways) programmable output of 4~20mA
Network print
Virtual correspondent node remote test
1.2.3 Monitoring function
Remote binary quantity: the device has 20-way binary input.
1.2.4 Communication capability
With industrial Ethernet port and standard RS485 multipoint communication port. Supports
MODBUS、IEC-60870-5-103(RS485 communication mode)、IEC-61850-5-104(Industrial
Ethernet communication mode)standard communication protocol and a new generation of
substation’s communication standard IEC 61850.
Supports single and dual network communication, it is fully qualified for network
redundancy and backup
1.2.5 GPS clock synchronization function
The device is able to receive GPS clock second synchronization or IRIG-B through RS485
differential voltage, and it can be done with monitoring system to accomplish GPS precise
clock synchronization or Ethernet-based SNTP synchronization.
3
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
1.2.6 Device specifications
32-bit POWERPC microprocessor
Real-time multi-task operating system and C++ program techniques, realizing online
programming
320*240 LCD display, easy for inspection
One or two ways 4~20mA DC quantity output, which can be set flexibly as any
corresponding electric quantity (such as current, etc.)
Having the electric energy quality analysis function and perfect harmonic analysis function
Integrating perfect metering functions and Metrology Function
Support network printing function, include two ways: real-time print and artificial print
Support virtual correspondent node remote test, including remote communication to
correspondent node, remote measure to correspondent node, event to correspondent node, can
online testing, it is convenient for debugger to debug the device on-site.
Excellent hardware interchangeability, user maintenance is easily and it reduced quantity of
spare parts
Protection output relays can be configured flexibly for user convenience
Using a 6U, 19/3” standard enclosure in a rear plug-in structure. the device can be installed in
site on a switchboard or combined in a centralized manner
1.2.7 Main technical specifications
Rated data
Power supply: DC/AC 86~265V
Operating voltage: DC 220V or DC 110V
AC voltage: 100/ 3 V or 100V
AC current: 5A or 1A
Frequency: 50Hz
Power consumption
DC circuit: <10W (normal operation). <15W (protection operation)
AC voltage circuit: <0.5VA/phase
AC current circuit: <1VA/phase (In = 5A). <0.5VA/phase (In = 1A).
Overload capability
AC voltage circuit: 1.2Un, continuous operation
Current measuring circuit: 1.2 In, continuous operation
Protective current circuit: 2In, continuous operation
10In, allowing 10s
40In, allowing 1s
Range and error of setting value
Maximum range of setting value:
Current element: 0.1In~20In
Timing element: 0.00s~100.00s
4
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
Error of setting value:
Current and voltage setting value: ≤±3% of setting value
Frequency setting value: ≤±0.02Hz
Angle setting value: ≤±2°
Whole-group operation time (including relay’s intrinsic time): Intrinsic operating
time of current instantaneous over-current protection: not greater than 40ms at 1.2
times the setting value
Measuring accuracy
AC current: Class 0.2
AC voltage: Class 0.2
SOE resolution: ≤2ms
Pulse width of pulse quantity: ≥10ms
4~20mA DC quantity output: ≤±1%
Capacity of trip/closing output contact
Can be connected to DC 250V, 8A for prolonged periods.
GSP clock synchronization error
Clock synchronization error≤2ms
Environmental conditions
Ambient temperature:
Operating:-20℃~+55℃.
Storage:-25℃~+70℃, rainproof and snow-proof rooms with relative humidity not
greater than 80%, ambient air free of acid, alkaline or other corrosive and explosive gas. No
excitation quality is applied at the limits, the device shall not have any irreversible change.
After temperature restoration, the device shall operate properly.
Relative humidity:
The average relative humidity of the most humid month shall not be greater than 90%,
the average minimum temperature of this month not lower than 25℃ and there shall be no
surface condensation. At the highest temperature of +40℃, the average maximum humidity
shall not exceed 50%.
Atmospheric pressure: 80kPa~110kPa (below relative altitude of 2KM)
1.2.8 Hardware structure
The device uses a 6U, 19/3” standard enclosure, with aluminum alloy casing and installed by
overall embedding. The display panel is mounted in the front, and the other plug-in modules are
rear mounted. From the rear view, I/O, the power, CPU and AC plug-in modules are from the left
to the right.
External dimensions and boring diagram
5
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
Structural and dimensional diagram Boring diagram for installation
Devices fabricated on-screen steps: first release on-screen stents unfastening screws, remove
the stents. Install the device on the screen from the front and push until close to the fixed plate.
Install the stent 2, and then stent 1, and then use fastening screw to insertion hole from rear of
stent1, and then screwed into stent 2 and tighten screw. The stents from up and down are installed
in the same way. Use grounding screws to connect grounding line.
6
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
2. Function of device
2.1 Differential instantaneous over-current protection
When any-phase differential current exceeds the differential instantaneous over-current
setting value, protection operates instantaneously to protect transformer.
Operating criterion:│Id│>Isd
In which, │Id│=│I1+I2│
Isd: Differential instantaneous over-current setting.
2.2 Complex percentage differential protection
As the main protection of generator, this protection uses differential protection with the ratio
braking characteristics. Id
K
Operate
Id0
Ir0 Ir
Figure 2-1 Differential operation curve
The operating formula is as follows:
1. When Ir < Ir0, Id>Id0
2. When Ir1≥Ir0, Id – Id0>K * ( Ir – Ir0)
Among the formula:Id is differential current,Id0 is setting value of differential threshold
current, Ir is restraint current,Ir0 is the restraint current of turning-point, K is percentage
coefficient.
Operating current:Id =∣I1+I2∣ Restraint current:Ir = | I1-I2 |
In the formula:I1---- generator current l2----- neutral current
According to the phase in the program, if any of the above conditions is met, percentage
differential protection operates.
2.3 Transverse differential protection
When the generator stator winding has branch of two parallel, generally device will install
transverse differential protection of differential reaction generator stator winding transverse short
circuit. In order to eliminate the influence of higher harmonic, this device will filter out third
harmonic in internal automatic. When the rotor of the generator excitation loop two points
happen earth fault, transverse differential protection may be mis-operation. In order to prevent
transverse differential protection mis-operation caused by exciting circuit two points earth fault,
after one-point earth in exciting circuit, device will automatically take transverse differential
protection switch to the time limit for action in the trip. The time limit for action can be set by the
user.
2.4 Differential over-current alarm
Under normal circumstances, device monitors every phase differential current. When
7
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
any-phase differential current exceeds the setting, protection operates.
2.5 CT failure
CT is the maximum load current.
When in normal operation, the sum of three phase current of each side is zero. When one
phase CT failure occurs, the sum of three phase current is not zero. To distinguish from ground
fault, the following should be judged:
1) Among three phase current, the minimum one is zero.
2) The maximum phase current is more than zero and less than CT failure block current.
2.6 Excitation Failure
Non-electricity protection, the delay time can be set.
2.7 Water ride/Thermal equipment Fault
Non-electricity protection, the delay time can be set.
2.8 Fault Record
It records the current waveform sampled by the device, for more information please refer to
communication code table.
2.9 Fault Record
Device supports network printing function, can print remote control information, SOE
information and the setting parameter list. The printer IP address must been set rightly on the
device (the network segment of printer must be as same as that of device IP addresses), then
connect a printer, put on "real-time report print ", it can print the current remote control
information or SOE information when device is connected to the back-ground (including remote
communication shift, protection action), and can print the current SOE information when device is
not connected to the background. In addition, when press the "ok" button in the "print report" or
"print setting value" menu, it can print the all setting parameter or the all report information,
including action value.
2.10 Virtual correspondent node remote test
The function is used to complete the communication node remote test of the device, do not
need to access the actual analog electric quantity or the input quantity. Specific operation as
follows, connect to the background, In the remote test menu, operate the “virtual input test”, the
“virtual measure test” and the “virtual SOE test” menu in the “remote test” menu, press the "OK"
button after the modification of various settings, then by observing the background pop-up
warning window or the change of the corresponding value, to determine whether the device
communication node is right. It is convenient for debugger to debug the device on-site. When you
are in the mode of remote test, the all protect must be off.
2.11 GPS clock synchronization
The GPS clock synchronization signal is input as rs485 differential voltage, the device is able
to receive GPS clock second synchronization. If there is GPS signal, there will be flashing
on the bottom of cycle menu. Otherwise won’t.
8
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
The principle of GPS clock synchronization: The second pulse or minute pulse act with the
monitoring system, the time base with second precision is sent by monitoring system, when the
GPS second differential signal arrives, the time base is unified and the milliseconds are cleared.
The device is able to receive GPS clock second synchronization or IRIG-B through RS485
differential voltage, and it can be done with monitoring system to accomplish GPS precise clock
synchronization or Ethernet-based SNTP synchronization.
2.12 Overhaul status
When the device put into overhaul plate, remote sign, remote measure can uploading
background computer. But the device can’t remote control by background computer. The SOE
event、Alarm event、Trip event, etc also can’t uploading background computer.
3. Setting of parameters and setting values of the device
3.1 System parameters
Parameter Range Description
Settings of setting value zone number(Setting Zone No.)
Setting value zone
0-7 Set step:1(factory default 0)
number(Setting Zone No.)
Communication settings(Comm. Setting)
Set step :1 (factory default 1)
NET Protocol 0-2
(0-Quit;1-IEC104;2-IEC61850)
Set step :1 (factory default 0)
RS485 Protocol 0-2
(0-Quit;1-IEC103;2-MODBUS)
RS485 address(RS485
1-99 Set step:1(factory default 1)
Address)
RS485 baud rate(RS485 Set step:1(factory default 2)0:2.4KB;1:4.8KB;
0-5
Baudrate) 2:9.6KB;3:19.2KB;4:38.4KB;5:115.2KB;
IP address(IP Address) One section set step:1(factory default 192.168.0.253)
SNTP Address (SNTP It has four
One section set step:1(factory default 192.168.0.254)
Address) sections. The
KW default value(KW range of every
One section set step:1(factory default 12.8.6.1)
Default) section is
Printer IP address(Printer 0-255
One section set step:1(factory default 192.168.0.255)
IP)
Setting of basic parameters(B. Parameters)
Rating Current(In) 0-1 Set step: 1 (factory default 0) 00: 5A. 01: 1A
9
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
Parameter Range Description
For harmonic calculation, select the corresponding
Harmonic Channel 0-7 reference quantity:
0:exit from harmonic calculation function
1:Ia1,2:Ib1,3:Ic1,4:Ia2,5:Ib2,6:Ic2,7:IH
Wave Record 0-1 Set step:1(factory default 0)00:Off;01:On
Hard Word 0-1 Set step:1(factory default 0)00:Off;01:On
Remote communication
10-100ms Set step: 1 (factory default 40ms)
ack time (input ack time)
Real-time print report
0-1 Set step: 1 (factory default 0) 00:exit;01:on
on/off(auto print report)
D/A channel setting(D/A Setting)
Select DA1~2 to output corresponding reference
quantities:
0: No D/A output 1:Ia1, 2:Ib1, 3:Ic1, 4:Ia2, 5:Ib2, 6:Ic2,
7:IH
DA1~2 Channel Rating 5A:
0-7
Selection Current reference quantity: 0-6A corresponding to
4mA-20mA
Rating 1A:
Current reference quantity: 0-1.2A corresponding to
4mA-20mA
DA1~2 Adjustment
0.5-1.5 Adjust D/A channel 1~2(4-20mA) parameters
Factor
Channel factor setting(Channel Coef.)
Set step:0.001(factory default 1)
Channel data 1~7 0.5-5 Channel data 1-7 are corresponded to the channel factor
of analog quantity 1-7.
3.2 List of setting values
Setting value Range Description
Differential instantaneous
over-current protection 1/0 1/0:On/Off (factory default Off)
(Instant Diff.)
Percentage differential protection
1/0 1/0:On/Off (factory default Off)
(Percent Diff.)
Differential current over-current alarm
1/0 1/0:On/Off (factory default Off)
(Diff. C Over-Limit)
10
Protection on/off word
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
CT Failure Alarm 1/0 1/0:On/Off (factory default Off)
CT Failure Lock 1/0 1/0:On/Off (factory default Off)
Transverse differential protection 1/0 1/0:On/Off (factory default Off)
Excitation Fault 1/0 1/0:On/Off (factory default Off)
Water ride/Thermal equipment Fault 1/0 1/0:On/Off (factory default Off)
Mutation startup(Abrupt Current)
Starting current (Startup Current) 0.10-1.00A Set step:0.01A(factory default 0.50A)
Percentage differential protection (Percent Diff.)
Percentage differential threshold
0.10—5.00A Set step:0.01A(factory default 2A)
current (Percent Diff. Sill)
Percentage differential restraint
turning-point point 0.1—12.50A Set step:0.01A(factory default 5A)
(Per. Res. Inflex.)
Percentage restraint coefficient1
0.10-0.80 Set step:0.01(factory default 0.50)
(Restraint Coe.)
Differential over-current alarm (Diff. C Over limit)
Differential over-current setting
1.00-100.00A Set step:0.01A(factory default 5A)
(Diff. C OL Value)
CT failure alarm/block (CT Failure)
Block current
0.10-10.00A Set step:0.01A(factory default 5A)
(Overload Current)
Delay setting (Time Set) 0.00-100.00s Set step:0.01s(factory default 5s)
Excitation Fault
Excitation Fault 0-100s Set step:0.01s(factory default 5s)
Water ride/Thermal equipment Fault
Water ride/Thermal equipment
0-100s Set step:0.01s(factory default 5s)
Fault
Transverse differential protection
Transverse differential protection
0.10-20.00A Set step:0.01A(factory default 5A)
setting
Transverse differential protection
0.00-100.00s Set step 0.01s(factory default 5s)
time
Differential current over-current
Differential current over-current
0.00-100.00A Set step:0.01A(factory default 5A)
setting
11
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
Differential current over-current
0.00-100.00s Set step 0.01s(factory default 5s)
time
4. Description of binary input, output and analog quantity
4.1 Monitoring of analog quantities
Analog quantities can be monitored under the [Protection Data], [Measured Data] and [Pulse
Energy] menus in the [Run States] menu, press the “”, “” keys to flip over. The factory
precision of the device has been calibrated. The protection current is calibrated at double the rated
current. The list is as follows:
Analog quantity Analog quantity
Test method
terminal name
1 side protection Add double the rating, displayed deviation not
Terminals D01、D02
phase A current (Ia1) exceed 1%
1 side protection Add double the rating, displayed deviation not
Terminals D03、D04
phase B current (Ib1) exceed 1%
1 side protection Add double the rating, displayed deviation not
Terminals D05、D06
phase C current (Ic1) exceed 1%
2 side protection Add double the rating, displayed deviation not
Terminals D07、D08
phase A current (Ia2) exceed 1%
2 side protection Add double the rating, displayed deviation not
Terminals D09、D10
phase B current (Ib2) exceed 1%
2 side protection Add double the rating, displayed deviation not
Terminals D11、D12
phase C current (Ic2) exceed 1%
Transverse differential Add double the rating, displayed deviation not
Terminals D13、D14
current (IH) exceed 1%
4.2 Monitoring of binary input
Binary input can be monitored under the [Binary input] menu in the [Run States] menu, press
the “”, “” keys to flip over.
Binary input Binary input name Test method
terminal
B01 Common terminal of binary input - External power supply of 220V or 110V DC
(Should be connected to DC220V can be applied, connect the negative terminal
or DC110V to terminal B01, positive terminal to terminal
negative terminal of external power B02~B21, in [Binary input] menu in the
supply) [Run States], the status of binary input can be
B02 Excitation fault seen.
B03 Water ride/Thermal equipment The device also has a 24V DC supply, if
Fault it is used, terminal B22 can be connected to
B04 Rotor one point earth fault terminal B02~B21, in [Binary input] menu
12
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
B05 Input 4 in the [Run States], the status of binary input
B06 Input 5 can be seen.
B07 Input 6 Please note about the binary input voltage
B08 Input 7 upon ordering, it is set to DC220V by default.
B09 Input 8
B10 Input 9
B11 Input 10
B12 Input 11
B13 Input 12
B14 Input 13
B15 Input 14
B16 Input 15
B17 Input 16
B18 Input 17
B19 Transverse differential plate
B20 Differential protection plate
B21 Overhaul
B22 Positive terminal of internal 24V
power supply
4.3 Monitoring of binary output
Binary output can be monitored under the [Binary output] menu, press the ““, ““ keys to
flip over.
Binary output terminals Binary output name Test method
B23-B24 Trip Signal
B23-B25 Alarm Signal
A17-A18 Spare Trip Node
A19-A20 Trip Main Switch Select open and close menu, use “+”,
A21-A22 Trip Field Discharge Switch “-” key to operate and test the
Close Steam valve/Guide corresponding terminals. A29-A30
A23-A24
hydrofoil and A31-A32 are common open
A25-A26 Output 5 terminals that should close.
A27-A28 Output 6
A29-A30 Output 7
A31-A32 Output 8
13
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
5. Operation instructions
5.1 Control panel of device
320*240 matrix LCD (The LCD will go off after a period of absence of keyboard operation. the
LCD will be illuminated automatically when any key is pressed or in case of protection trip or
alarm.)
Signal indicator: run, communication, trip, alarm, fault (of the device), Backup, remote.
Key pad: , , , , Cancel, -, +, Enter, Revert
5.2 Instructions for use of key pad and LCD display
During the device’s normal operation, it will display the primary differential current data 、
device address and time in cycle. Press the “Enter” key to enter the main menu, which is a
multi-level tree menu. Press the ““, ““ keys to move the cursor to the desired entry, press the
“Enter” key to enter this entry, and press the “Cancel” key to return to the next higher level of
screen. If this screen is still a menu, continue to press the ““, ““ key to select the desired entry,
press the “Enter” key to enter the next level of screen, and press the “Cancel” key to return to the
next higher level of menu. If there is no menu screen, be sure to press the “Cancel” key to return
to the next higher level of menu. The main menu is shown at the center of the following figure,
with the corresponding submenus on both sides.
14
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
01.Run States -1/5- Main menu 05.Report Dis. -1/4-
Protection Data Trip Report Binary Input 01.Run Status Binary Report Soft Strap Event Report
Harmonic Data Print Report AD Volt. Data 02.Run Parameters
03.Setting View 06.Parameters -1/6- Comm. Setting
02.Run Param. -1/3-
Transformer Coe. Setting Zone No. 04.Setting Value B. Parameters
PROT On/Off
Clock Setting 05. Report Manage D/A Setting
Channel Coe. Language Select
06. SYS Parameters
03.Setting View-1/8- 07.Device Test 07.DeviceTest. -1/2- Percent Dif. Output Test
Instant Dif. 08.PassWord Lamp Test Trans. Dif. Diff. C Over-Limit
09.Version Info. 08.Password ...... □□□□
04.Setting Value-1/8- 10.Comm Test
Percent Dif. PROT AUTO DEV V2.00
Instant Dif. Type:MGPR-810Hc
Trans. Dif. 10.Comm test ID:□□.□□.□□
Diff. C Over-Limit Input Test CRC:□□□□□□□□ Measure Test Date:20XX-XX-XX
...... SOE Test
Note 1:For the Setting menu, see the description of each device.
Run Status
The [Run Status] menu contains 5 submenus, including protection data, binary input, soft
strap, harmonic data, AD voltage data. It is described as follows:
PROT Data -1/13-
Ia1 = □□□·□□ A
000.0° Secondary current value of generator side
Ib1 = □□□·□□ A
000.0°
Ic1 = □□□·□□ A Secondary current value of neutral point
000.0°
Ia2 = □□□·□□ A
000.0° Differential secondary current value
Ib2 = □□□·□□ A
000.0°
Binary Input -1/20-
Excitation Fault :□ According to "close", means Excitation Fault input is on
Water ride/Thermal equipment According to "close", means Water
Fault :□ ride/Thermal equipment Fault input is on
Rotor one point earth fault :□
Input 4 :□
Input 5 :□ Description varies with model, see corresponding terminal
...... diagram for details
Transverse differential strap :□
Differential protection strap :□
15
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
Note: In the standard configurations, the input circuit has the connection to an external
220VDC control power supply. When no DC control power supply or control system is available
on site, but a 110VDC control power supply is available, a 110VDC control power supply may be
used for direct connection through local hardware adjustment, or the 24V power supply of the
device may be used as the input power supply (when the input common terminal is +24V, terminal
number: B22, Terminal B01 is kept float). However, this must be specified upon ordering.
Soft Strap -1/8-
Percent Diff. Off
Instant Diff. Off
Trans. Diff. Off
Diff. C Over-Limit Off
CT Failure Alarm Off
......
Harmonic Data -1/10-
nd
2 : □□□·□□%
3rd : □□□·□□%
4th : □□□·□□% 2~11 harmonics for which analog channels
5th : □□□·□□%
...... have been selected in system
11th :□□□·□□%
AD Volt. Data -1/2-
AD1:□□·□□□V AD Voltage Check
AD2:□□·□□□V
Run Parameters
In the [Run Parameters] menu includes 3 submenus, including [Setting Zone No.]、[PROT
On/Off]、[Clock Setting], The screen Content is as follows:
Setting Zone No. :Range 00~07.
PROT On/Off:The device protect plate can be select in this menu.
PROT On/Off -1/8- Parameter Modify
Percent Diff.
On Off ◇Enter ◆Cancel
Press “+”, “-” keys to select the protection function On or Off. The interface will eje
ct the window as right chart show when you press the “Enter” key. Move the cursor to t
he desired position for modification by pressing the “”, “” keys. Press the “Enter” key
to complete setting, and the device will prompt modifying success or not. If the “Cance
l” key is pressed, the protect plate status setting will be cancelled and the menu will retur
n previous menu.
Clock setting:
A battery-back real-time clock is provided in the device, which can perform time adjust
16
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
remotely via the communication network or in-site time adjust in the [Time Setting] menu.
Enter this menu and press the “Enter” key, the clock will stop refreshing and a cursor will
Clock setting appear. Move the cursor to the desired position for modification
by pressing the “”, “” keys, modify to the desired value with
Date:20□□-□□-□□ the “+”, “-” keys. Press the “Enter” key to complete setting. If
Time: □□:□□:□□
the “Cancel” key is pressed, the setting will be cancelled and
the screen continues to refresh the clock.
Setting View
This meun just for query.You can’t modif the value to prevent faulty operation.
Setting Value
After entering the password, you can enter the [Setting Value] menu. See the settings
description of the protection device for the detailed description.
Report Manage
The [Report Manage] menu includes 4 submenus, including trip report, binary report, event
report and print report. Event recording includes: device self-check fault, device setting value
modification, system parameter modification and setting zone number modification, etc. Trip
report can be record for the last 50 events, binary report for 100, event report for 30 at most.
Beyond this, the latest report will overwrite the earliest one. Press the “Enter” key to enter the
corresponding [To view xx report, please enter report number: 00] menu, and enter any figure
within storage volume, press the “Enter” key to display the contents of that report. The screen is as
follows:
Report No.:□□ ↓ Report No. of this report
Year, month, day, hour, minute, second and 20□□-□□-□□ millisecond when it took place
□□:□□:□□:□□□
□□□□□□
Press key to see the specific operation value. Press and keys to flip over. Operation
values.
Action value view
Ia1 = □□□·□□ A
Ib1 = □□□·□□ A
Ic1 = □□□·□□ A
Ia2 = □□□·□□ A
Ib2 = □□□·□□ A
Ic2 = □□□·□□ A
……
System parameters
After entering the [SYS Parameters] menu, the correct password is required to enter the [SYS
Parameters] menu. It displays the following:
17
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
Parameters -1/6-
Comm. Setting
Transformer Coe.
B. Parameters
D/A Setting
Channel Coe.
Language Select
Communication Setting
Comm. setting -1/8-
NET Protocol
□□ 00:Quit;01:IEC104;02:IEC61850;
RS485 Protocol
□□ 00:Quit;01:IEC103;02:MODBUS;
RS485 Address
□□ Communication address of device 01~99
RS485 Baud rate
□□
IP Address 00:2.4KB;01:4.8KB;02:9.6KB;03:19.2KB;04:
□□□. □□□. □□□. □□□ 38.4KB;05:115.2KB
SNTP Address
□□□. □□□. □□□. □□□
K W Default For Ethernet communication □□□. □□□. □□□. □□□
Printer IP
□□□. □□□. □□□. □□□
Transformer Coefficient
TransformCoe -1/1-
CT Ratio
□□□□
Max:5000 Min:0001
It will prompt maximum value and minimum value of each parameter below the window.
Setting of basic parameters (see the description of the protection device for basic parameters)
B.Parameters: -1/6-
Rating Current
□□ Setting the CT secondary current rating 00: 5A. 01: 1A
Harmonic Channel
Setting analog quantity channels 0~11 for harmonic monitoring, select 0 □□
Wave Record to exit from the harmonic calculation function
□□
......
D/A setting
The device has two 4~20mA outputs. The DA1~DA2 adjustment factor is used to adjust the
accuracy of the channel output. The DA1~DA2 channel selection is used to select the
corresponding analog quantity channel (see the description of the protection device for specific
reference quantities). In the accuracy test, make sure the field ground is in good contact.
Otherwise the accuracy might be affected.
18
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
Channel Coefficient
The device can adjust channel coefficient by this menu to raise Sample size.
Device test
After entering the [Device Test] menu, the correct password is required to enter the [Device
Test] menu. It’s have two menu include [Output Test] and [Lamp Test].
Output Test
Enter [Output Test] menu, It displays the following:
Output Test -1/11-
Spare Trip Node Press “Enter” key
Trip Main Switch Spare Trip Node
Trip Field Discharge Switch On Off
Close Steam valve/Guide hydrofoil
Note:
Output 5 Node:A17,A18 Open
Press “Cancel” key……
Operate All
(Note: When the test is performed on the 6 protection outputs, the starting relay will be in the
“Closed” state automatically. The “+”, “-” keys are used for switching between the “Close/Open”
control.)
Lamp Test
Lamp Test
◇Light ◆Quench Used for testing Stand or fall of all LED lights.
Password
The [Password] menu is used to modify the password for entry into the Settings, System
parameters and Output Test submenus. The initial password is provided by the factory. The
universal password is “1000”.
Move the cursor to the desired position for modification by pressing the ““, “” keys,
Input password modify to the desired password with the “+”, “-” keys. Press the
0 0 0 0 “Enter” key to enter the new password setting menu as above.
Press the “Cancel” key to cancel the setting.
Version information
In the main menu, after entering the [Version Info.] menu, the Type, ID, CRC and Date of the
software will be displayed.
PROT AUTO DEV V2.00 Note: For a corresponding nonstandard model, the device’s
Type:MGPR-810Hc displayed Type does have to be changed.
ID:□□.□□.□□
CRC:□□□□□□□□
Date:20XX-XX-XX
Comm test
When debugger debug the device on-site in the case of no-accessing the actual analog electric quantity
or the input quantity, [Comm. Test] is used to do the test of the communication node of the device.
19
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
6. Check of protection function
6.1 Check of differential instantaneous over-current protection
Differential protection plate is on.
6.1.1 Check of differential instantaneous over-current operating value
Wire as the figure 6.1. D01, and D02 is machine side A phase current input. D03 and D04 is
machine side B phase current input. D05 and D026 is machine side C phase current input. D07
and D08 is the neutral A phase current input. D09 and D10 is the neutral B phase current input.
D11 and D12 is the neutral C phase current input. Input each phase current in turn, gradually
increase, until the protection has acted. Then the protection outputs of the corresponding
protection measure output sequence should be on. Write the data in the table 6.1.
MGPR-810Hc
Ia1、Ia2 D01,D07
Ia1’、Ia2’ D02,D08 B29
Ib1、Ib2 D03,D09
Power supply
Ib1’、Ib2’ D04,D10
Ic1、Ic2 D05,D11 B30
Ic1’、Ic2’ D06,D12
Figure 6-1
Table 6.1
Instantaneous over-current
Add only machine A 6 8 10
protection setting(A)
phase current, check the
Operating value
operating value
Error rate(%)
Instantaneous over-current
Add only machine B 6 8 10
protection setting (A)
phase current, check the
Operating value
operating value
Error rate(%)
Instantaneous over-current
Add only machine C 6 8 10
protection setting (A)
phase current, check the
Operating value
operating value
Error rate(%)
Instantaneous over-current
Add only the neutral 6 8 10
protection setting(A)
phase A current, check the
Operating value
operating value
Error rate(%)
20
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
Instantaneous over-current
Add only the neutral 6 8 10
protection setting (A)
phase B current, check the
Operating value
operating value
Error rate(%)
Instantaneous over-current
Add only the neutral 6 8 10
protection setting (A)
phase C current, check the
Operating value
operating value
Error rate(%)
6.1.2 Check of differential instantaneous over-current operating time
Wire as the figure 6.2. Input 1.5 times of differential instantaneous over-current value to do
the experiment, record the action time of the protection.
MGPR-810Hc
D01 B29
Current input
Device power
D02 B30
Protection
output
ms
Figure 6.2
6.2 Check of Complex percentage differential protection
Differential protection plate is on.
6.2.1 Check of differential current threshold operating value
Wire as the figure 6.1. D01, and D02 is machine side A phase current input. D03 and D04 is
machine side B phase current input. D05 and D026 is machine side C phase current input. D07
and D08 is the neutral A phase current input. D09 and D10 is the neutral B phase current input.
D11 and D12 is the neutral C phase current input. Set ratio braking point value to 5.00 A, put CT
lock exit. Input each phase current in turn, gradually increase, until the protection has acted. Then
the protection outputs of the corresponding protection measure output sequence should be on.
Write the data in the table 6.2.
Table 6.2
Instantaneous over-current
Add only machine A phase 6 8 10
protection setting(A)
current, check the operating
Operating value
value
Error rate(%)
Instantaneous over-current
Add only machine B phase 6 8 10
protection setting (A)
current, check the operating
Operating value
value
Error rate(%)
21
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
Instantaneous over-current
Add only machine C phase 6 8 10
protection setting (A)
current, check the operating
Operating value
value
Error rate(%)
Instantaneous over-current
Add only the neutral phase A 6 8 10
protection setting(A)
current, check the operating
Operating value
value
Error rate(%)
Instantaneous over-current
Add only the neutral phase B 6 8 10
protection setting (A)
current, check the operating
Operating value
value
Error rate(%)
Instantaneous over-current
Add only the neutral phase C 6 8 10
protection setting (A)
current, check the operating
Operating value
value
Error rate(%)
6.2.2 Check of Ratio braking coefficient
Wire as the figure 6.1. Setting the differential current threshold value to 2.00 A, the ratio
braking point to 5.00 A, and ratio braking coefficient to 0.4. Put CT lock exit.
Because the corresponding current is inverting to join, assuming that machine side current is I1,
neutral side current is I2, the differential current is Id = I1 + I2, braking current is Ir = (I1-I2), ratio
braking coefficient is K=(Id- Id0)/(Ir-Ir0). Among them: Id0: the differential current threshold
current, Ir0: the ratio braking turning point fixed value.
Table 6.3
Braking current (A) 6.00 8.00
both sides of A phase
current reverse input Real measurement K
Error rate(%) of K
Braking current (A) 6.00 8.00
both sides of B phase
current reverse input Real measurement K
Error rate(%) of K
Braking current (A) 6.00 8.00
both sides of C phase
current reverse input Real measurement K
Error rate(%) of K
6.2.3 Check of differential current operating time
Wire as the figure 6.2. Input 2 times of differential current value to do the experiment, record
the action time of the protection.
6.3 Transverse differential protection
22
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
Transverse protection palteis on.
6.3.1 Check of transverse differential protection operating value
Wire as the figure 6.3. D13 and D14 is transverse differential protection current input, set
transverse differential protection current according to table 6.4. Input current, gradually increase,
until the protection has acted. Then the protection outputs of the corresponding protection measure
output sequence should be on. Write the data in the table 6.4.
MGPR-810Hc
IH D13 B29
Device Power
IH’
D14 B30
Figure 6.3
Table 6.4
Setting value(A) 1.00 5.00 20.00
Add the actual
current Operating value(A)
Error rate (%)
6.3.2 Check of transverse differential protection operating time
When the rotor of the generator excitation loop two points happen earth fault, transverse
differential protection may be mis-operation. In order to prevent transverse differential protection
mis-operation caused by exciting circuit two points earth fault, after one-point earth in exciting
circuit, device will automatically take transverse differential protection switch to the time limit for
action in the trip. So when the device acquire the one-point earth switch signal of the excitation
circuit, transverse differential protection should act according to the setting time delay, otherwise
no time delay action.
Wire as the figure 6.4. Input 2 times of transverse differential protection current value to do the
experiment, record the action time of the protection.
MGPR-810Hc
D13 B29
Current input Power supply
D14 B30 The one-point earth
switch signal of the -KM B01 Protection
excitation circuit Output
+KM B04 ms
Figure 6.4
6.4 Check of differential over-current alarm
Set differential over-current alarm to On, add current to every side and make the differential
current exceed differential over-current setting, the device will report differential over-current
23
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
alarm and the alarm led will be lighten. When the protection has acted, the protection outputs of
the corresponding protection measure output sequence should be on.
6.5 Check of CT failure
CT failure function should be on, add single phase current which is greater than 0.1 times the
rated current, and less than the load current, then it should report CT failure and light the alarm led.
In the case of CT failure conditions, it should be block complex percentage differential protection.
6.6 Check of Non-electricity protection
6.6.1 Check of Excitation Fault
When it short circuit B01 and B02 from the external, then it should report field fail and light
the trip signal led, the protection outputs of the corresponding protection measure output sequence
should be on.
6.6.2 Check of Water ride/Thermal equipment Fault
When it short circuit B01 and B03 from the external, then it should report water
ride/thermal equipment fault and light the trip signal led, the protection outputs of the
corresponding protection measure output sequence should be on.
24
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
Addendum 1: Terminal diagram of the device
I/O POWER CPU A C
Input comon
B01 point-
B02 Excitation?Fault NET1 D01 Ia1 Ia1' D02
B03 Water ride/ThermalEquipment Fault
Rotor one point D03 Ib1 Ib1' D04B04 earth Fault
B05 Input 4 D05 Ic1 Ic1' D06
B06 Input 5
B07 Input 6 D07 Ia2 Ia2' D08
B08 Input 7 NET2 D09 Ib2 Ib2' D10
B09 Input 8
B10 Input 9 D11 Ic2 Ic2' D12
B11 Input 10
B12 D13 D14Input 11 IH IH'
B13 Input 12 D15 D16
B14 Input 13
Run Light
B15 Input 14 D17 D18
B16 Input 15
D19 D20
DEBUG D21 D22
D23 D24
A17 Spare Trip Node B17 Input 16 C01 GPS-A Note:
A18 Spare Trip Node B18 Input 17 C02 GPS-B 1.Ia1, Ib1, Ic1 are
A19 Trip Main Switch B19 Transverse C03 protective currents ofdifferential plate
A20 Trip Main Switch B20 Differential
generator side.
protection plate C04 COM1A 2.Ia2, Ib2, Ic2 are
A21 Trip Field?Discharge B21 Overhaul C05 COM1BSwitch protective currents of
A22 Trip Field?Discharge B22 (+24V) C06 Shielded ground neutral point side.Switch
Close Steam 3.IH is the current ofA23 Valve/Guide hydrofoil B23 Common terminal C07 COM2A transverse
A24 Close SteamValve/Guide hydrofoil B24 Trip Signal C08 COM2B differential
A25 Output 5 B25 Alarm Signal C09 DCS1+ protection.
A26 B26 C10 DCS1- 4.COM1,COM2 are 485Output 5
interfaces;Net1,Net2
A27 Output 6 B27 Power off C11 DCS2+ are Ethernet
A28 Output 6 B28 Power off C12 DCS2- interfaces.
A29 Output 7 B29 Power 5.+24V on Power board
is not the standard
A30 Output 7 B30 Power configuration, it is
A31 Output 8 B31 used as input power
A32 Output 8 B32 Shielded ground supply only when using
internal 24V.
Figure 1 Terminal diagram of MGPR-810Hc microcomputer generator differential protection
device
25
User’s manual of MGPR-810Hc generator differential protection device WLD[K]-JY-317-2018
Addendum 2: Typical wiring diagram of the device
Ia1 Ia1'Ib1 Ib1'Ic1 Ic1' Ia2 Ia2'Ib2 Ib2'Ic2 Ic2' IH IH'
generator side curent neutral point side current transversedifferential current
AC plug-in unit
Spare Trip
Node
Trip Main
Switch
Trip Field?
Discharge Switch
MGPR-810Hc generator Close
Steam?valve/Guide
Net1 differential protection device hydrofoil
Output 5
Net2
Output 6
Debugging port Output 7
Output 8
COM1A
COM1B
Power plug-in unit
Shielded ground
COM2A
COM2B
DCSOut1+
DCSOut1-
DCSOut2+
DCSOut2-
Figure 2 Typical wiring diagram of MGPR-810Hc generator differential protection device
26
CPU plug-in unit
Input common
KM Transverseterminal- differential plate
KM Excitation?fault Differentialprotection plate
Water ride/Thermal?
equipment Fault Overhaul
Rotor one point 24V+
earth fault
Signal common
Input 4
terminal
Input 5 Trip Signal
Input 6 Alarm Signal
Input 7
Input 8 Power off
Input 9 Power off
Input 10 Power+
Input 11 Power-
Input 12
Input 13 Shielded ground
Input 14 Shielded
ground
Input 15
Input 16
Input 17
I/O plug-in unit