点击查看大图
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37

User's manual for MMPR-220 motor protective controller _V1.03

大小:
1MB
类型:
PDF文档
内容:
共37页
最后更新于:2019年05月21日
91
纠错
全文文本
Zhuhai Wanlida Electrical Automation Co., Ltd. http://www.zhwld.com MMPR-220 motor protective controller user’s manual Preparation: Checking: Permission: Document No.:WLD[K]-JY-450-2014 Version: V1.03.01 Publication Date:201708 All rights reserved:Zhuhai Wanlida Electrical Automation Co.,Ltd Note: The Company reserves the right to amend this statement. If a product is inconsistent with the statement, please contact us, we will provide you with the corresponding services. Technical support tel.:(86)0756-3395398 Fax.:(86)0756-3395500 I Contents Contents   FOREWORD ............................................................................................................................................................. 1  1. PRODUCT DESCRIPTION ................................................................................................................................. 2  1.1 Scope ......................................................................................................................................................... 2  1.2 Device features ......................................................................................................................................... 2  1.3 Technical specifications and indicators ................................................................................................. 2  1.4 Device shape and model description .................................................................................................... 3  2. FUNCTIONAL DESCRIPTION ............................................................................................................................ 3  2.1 Motor controlling ....................................................................................................................................... 3  2.1.1 Local/Remote controlling ..................................................................................................................... 3  2.1.2 Starting method ..................................................................................................................................... 3  2.1.3 Automatic restart function on power restores ................................................................................... 3  2.1.4 Low voltage/voltage loss restart .......................................................................................................... 3  2.2 Protective functioning .............................................................................................................................. 4  2.2.1 Acceleration protection ......................................................................................................................... 4  2.2.2 Instantaneous over-current protection ............................................................................................... 4  2.2.3 Locked rotor protection ........................................................................................................................ 4  2.2.4 Over-load protection ............................................................................................................................. 4  2.2.5 Thermal protection ................................................................................................................................ 4  2.2.6 Unbalance protection............................................................................................................................ 5  2.2.7 Zero sequence current protection ....................................................................................................... 5  2.2.8 Leakage current protection .................................................................................................................. 5  2.2.9 Open-phase protection ......................................................................................................................... 5  2.2.10 Phase sequence protection ............................................................................................................... 5  2.2.11 Under-power protection ...................................................................................................................... 5  2.2.12 Low voltage protection ....................................................................................................................... 6  2.2.13 Over voltage protection ...................................................................................................................... 6  2.2.14 Technology interlock ........................................................................................................................... 6  2.2.15 tE protection......................................................................................................................................... 6  2.3 Settings of protection ............................................................................................................................... 6  3. DEVICE DESCRIPTION .................................................................................................................................... 6  3.1 Indicators ................................................................................................................................................... 7  3.2 Keypad ....................................................................................................................................................... 7  3.3 Display and menu operation ................................................................................................................... 7  4. OPERATING PRINCIPLE..................................................................................................................................... 8  5. PARAMETER SETTING ...................................................................................................................................... 9  5.1 System parameter setting ....................................................................................................................... 9  5.1.1 Parameters list ....................................................................................................................................... 9  5.1.2 Setting method .................................................................................................................................... 10  5.2 Protective setting .................................................................................................................................... 11  5.2.1 Method of modifying protective setting ............................................................................................ 11  5.2.2 Protection ON/OFF ............................................................................................................................. 11  5.3 Analog setting ......................................................................................................................................... 12  5.4 System time ............................................................................................................................................ 12  5.5 Password setting .................................................................................................................................... 12  6. CHECK METHOD .......................................................................................................................................... 13  6.1 Preparation before check ...................................................................................................................... 13  6.1.1 Check before power is on .................................................................................................................. 13  6.1.2 Monitoring and adjusting of analog quantities ................................................................................ 13  6.1.3 View binary input ................................................................................................................................. 13  6.1.4 View binary output .............................................................................................................................. 13  6.2 Check of control function ....................................................................................................................... 13  6.2.1 Local control mode ............................................................................................................................. 15  6.2.2 Remote control mode ......................................................................................................................... 15  6.2.2.1 Communication control mode ........................................................................................................ 16  6.2.2.2 Terminal control mode ..................................................................................................................... 16  6.2.3 Automatic start control on power ...................................................................................................... 16  6.2.4 Low voltage/voltage loss restart control ........................................................................................... 17  II Contents 6.3 Check of protective function ................................................................................................................. 17  6.3.1 Check of acceleration protection ...................................................................................................... 17  6.3.2 Check of instantaneous over-current protection ............................................................................. 18  6.3.3 Check of locked rotor protection ....................................................................................................... 18  6.3.4 Check of over load protection ........................................................................................................... 18  6.3.5 Check of thermal protection .............................................................................................................. 19  6.3.6 Check of unbalance protection ......................................................................................................... 20  6.3.7 Check of zero sequence current protection .................................................................................... 20  6.3.8 Check of Residual current protection ............................................................................................... 21  6.3.9 Check of open-phase protection ....................................................................................................... 22  6.3.10 Check of phase sequence protection ............................................................................................ 22  6.3.11 Check of under-power protection .................................................................................................... 23  6.3.12 Check of low voltage protection ...................................................................................................... 23  6.3.13 Check of over-voltage protection .................................................................................................... 24  6.3.14 Check of technology interlock protection ...................................................................................... 24  6.3.15 Check of tE protection ...................................................................................................................... 25  6.4 Check of communication function ........................................................................................................ 26  6.4.1 Check of measuring analog value .................................................................................................... 26  6.4.2 Check of remote signal upload ......................................................................................................... 26  7. PRODUCT MAINTENANCE ................................................................................................................................ 26  8. CAUTIONS ...................................................................................................................................................... 26  Appendix 1:MMPR-220 motor protective controller terminal figure .................................................... 27  Appendix 2:tE protection inverse characteristics table and figure ...................................................... 28  Appendix Tab.1:Typical specifications of external current transformer .............................................. 29  Appendix Fig.1:Direct start .......................................................................................................................... 30  Appendix Fig.2: Bi-directional start ................................................................................................................ 31  Appendix Fig.3: Reduced voltage start with resistor ....................................................................................... 32  Appendix Fig.4: Y/∆ 3-relay open-loop start ............................................................................................. 33  III Foreword Foreword 1. Model description MMPR-220 motor protective controller has three-phase current input of phase A, B, C. The principle of default protection ON/OFF and settings are as follows: all protection are off, settings being the maximum. 2. Quoted standards General technical conditions of digitalized motor integrated protective equipment JB/T 10613-2006 1 MMPR-220 motor protective controller WLD[K]-JY-450-2014 1. Product description 1.1 Scope MMPR-220 motor protective controller works with external primary current transformer, mainly applies to the low-voltage motor integrated controlling and protecting of AC 380V~1.2KV. The products from this series can be used in petrochemical, hydro-electric power, thermal power, smelting and water pumping station. 1.2 Device features  Uses high-performance 16-bit industrial microprocessors, high integration, functions strong, fast.  Three phase current, voltage AC sampling, perfect measuring and controlling functions.  Small size, under-power consumption, suitable for installation in the switchgear or on centralized panel.  LCD display with wide temperature range.  Strong anti-interference capability: Level Ⅳ of rapid transient interference, level Ⅳ of electrostatic discharge interference, electromagnetic interference Ⅲ radiation level, pulse interference Ⅲ-class group.  With perfect protective function, automatic start functions when power restores. All kinds of reduction voltage start control modes, two-way and two-speed start control modes.  Local start/stop switch and control mode selection switch.  Remote start stop control with terminal control mode or communication control mode.  Keeps records even power is off.  4~20mA output with Optical isolation.  Equipped with Modbus-RTU communication method, remote measuring, remote signal and remote control can be achieved through communication network and background monitor system. 1.3 Technical specifications and indicators  Rated parameters  AC voltage input:~380V(direct measuring),~100V(PT measuring).  AC current: 1~200A.  Rate frequency:50Hz.  Power supply:AC/DC220V,AC/DC110V.  Main specifications  Accuracy: the measuring error of protective current, voltage does not exceed ±1%; the measuring error of active power, reactive power does not exceed ±3%; the error of power factor does not exceed ±1%; and the frequency error does not exceed ±0.02Hz.  Time delay and trip setting accuracy: a) Trip setting accuracy: the error does not exceed ±3%, current trip setting accuracy: the error does not exceed ±3% or ±30mA,current unbalance setting accuracy: the error does not exceed ±3%. b) Time delay accuracy: the error does not exceed ±100ms when time delay setting is 0s, the error does not exceed ±25ms when time delay setting is 0.1~2s, the error does not exceed ±1% of setting when time delay setting is over 2s. c) Time delay accuracy of Thermal protection: the error does not exceed ±100ms or ±5%; d) Trip setting accuracy of Under-power protection: the error does not exceed ±5%; Time delay accuracy of Under-power protection: the error does not exceed ±300ms;   Output contact rating:AC250V,8A.  Power consumption  Maximum power consumption ≤ 5W.  Environmental specifications  Atmospheric pressure:80kPa~110kPa(below 2000m of sea level).  Humidity:5% ~ 95%  Operating temperature:-25℃~+55℃.  Operating Environment:Does not contain materials that lead to metal corrosion or damage to the insulation of gas and more serious mold and dust, does not contain fire explosion hazard. 2 MMPR-220 motor protective controller WLD[K]-JY-450-2014 1.4 Device shape and model description  Fig.1-1 Device shape MMPR-220 G:With function of leakage current. :Without function of leakage current. I:There is direct current output of 4-20mA. :There isn't direct current output of 4-20mA. C:485 communication with MODBUS agreement. :Without communication. Device model  Fig.1-2 Model description 2. Functional description 2.1 Motor controlling 2.1.1 Local/Remote controlling  Select local/remote controlling method through device menu 2.1.2 Starting method  Direct start  Decreased voltage start  Y-∆ 2-relay start  Y-∆ 3-relay start  Bi-direction start  Bi-speed start  Converter control 2.1.3 Automatic restart function on power restores  Recover mode 2.1.4 Low voltage/voltage loss restart  Immediate restart  Delay restart  Restart prohibited  Note:Shall there be any protection trips or protection trips signals not reverted, all control will not function. 3 MMPR-220 motor protective controller WLD[K]-JY-450-2014 2.2 Protective functioning 2.2.1 Acceleration protection The following setpoints are available for the acceleration protection see Tab.2-1. Tab.2-1 Setting item Setting range Setting step Rated current of motor 0.1-5000.0(A) 0.1 Start time of motor 0-600(S) 0.1 2.2.2 Instantaneous over-current protection The following setpoints are available for the instantaneous over-current protection, see Tab.2-2. Tab.2-2 Setting item Setting range Setting step Instantaneous over-current protection starting current 0.01-10(Ie) 0.01 Instantaneous over-current protection post-starting current 0.01-10(Ie) 0.01 Instantaneous over-current protection delay 0-100(S) 0.01 2.2.3 Locked rotor protection The following setpoints are available for the locked rotor protection, see Tab.2-3. Tab.2-3 Setting item Setting range Setting step Locked rotor current setting 0.01-10(Ie) 0.01 Locked rotor protection delay 0-100(S) 0.01 2.2.4 Over-load protection The following setpoints are available for the over-load protection, see Tab.2-4. Tab.2-4 Setting item Setting range Setting step Over-load setting(A) 0.01-10(Ie) 0.01 Over-load protection delay(b) 0-100(S) 0.01 Over-load protection could act as either “alarm mode” or “trip mode”. 2.2.5 Thermal protection The following setpoints are available for the thermal protection, see Tab.2-5. Tab.2-5 Setting item Setting range Setting step Heating time constant 0.1-6000(s) 1 Cooling time constant 0.01-100 0.01 Positive heating coefficient 0-1 0.01 Negative heating coefficient 0-10 0.01 Over-heat alarm coefficient 0.01-100(%) 0.01% Thermal protection could act as either “alarm mode” or “trip mode”. 4 MMPR-220 motor protective controller WLD[K]-JY-450-2014 2.2.6 Unbalance protection The following setpoints are available for the unbalance protection, see Tab.2-6. Tab.2-6 Setting item Setting range Setting step Unbalance setting 10.00%-60.00% 0.01% Unbalance protection delay 0-100(S) 0.01 2.2.7 Zero sequence current protection The following setpoints are available for the zero sequence current protection, see Tab.2-7. Tab.2-7 Setting item Setting range Setting step Zero sequence current setting 0.01-10(Ie) 0.01 Zero sequence current protection delay 0-100(S) 0.01 2.2.8 Leakage current protection The following setpoints are available for the leakage current protection, see Tab.2-8 Tab.2-8 Setting item Setting range Setting step Leakage current protection setting 2-5000.0(mA) 0.1 Leakage current protection delay 0-100(S) 0.01 Leakage current protection could act as either “alarm mode” or “trip mode”. 2.2.9 Open-phase protection The following setpoints are available for the open-phase protection, see Tab.2-9. Tab.2-9 Setting item Setting range Setting step Open-phase protection delay 0-100(S) 0.01 2.2.10 Phase sequence protection The following setpoints are available for the phase sequence protection, see Tab.2-10. Tab.2-10 Setting item Setting range Setting step Phase sequence protection delay 0-100(S) 0.01 2.2.11 Under-power protection The following setpoints are available for the under-power protection, see Tab.2-11. Tab.2-11 Setting item Setting range Setting step Under-power setting 0.01-600(KW) 0.01 Under-power protection delay 0-100(S) 0.01 5 MMPR-220 motor protective controller WLD[K]-JY-450-2014 2.2.12 Low voltage protection The following setpoints are available for the low voltage protection, see Tab.2-12。 Tab.2-12 Setting item Setting range Setting step Low voltage setting 0.1-6000.0(V) 0.1 Low voltage mode 00-01 1 Low voltage protection delay 0-100(S) 0.01 2.2.13 Over voltage protection The following setpoints are available for the over voltage protection, see Tab.2-13。 Tab.2-13 Setting item Setting range Setting step Over voltage setting 0.01-6000V 0.1 Over voltage protection delay 0-100(S) 0.01 Over voltage protection could act as either “alarm mode” or “trip mode”. 2.2.14 Technology interlock The following setpoints are available for the Technology interlock, see Tab.2-14. Tab.2-14 Setting item Setting range Setting step Technology interlock delay 0-100(S) 0.01 2.2.15 tE protection The following setpoints are available for the tE protection, see Tab.2-15. Tab.2-15 Setting item Setting range Setting step tE time(A) 0-100(S) 0.01 2.3 Settings of protection  Select “Settings” menu, choose the corresponding setting item and make changes;  Select “Protection ON/OFF” menu, choose the corresponding ON/OFF control menu and make changes. Example: Make changes to the setpoints available for the instantaneous overcurrent protection  Select “Settings” menu, choose “motor operating setting” menu,set rated current of motor and start time of motor;  Select “Instantaneous overcurrent protection” menu, set instantaneous overcurrent protection starting current, instantaneous overcurrent protection post-starting current and instantaneous overcurrent protection delay;  Select “protection ON/OFF” menu, set instantaneous overcurrent protection to ON, which means the value of instantaneous overcurrent protection is “1”. Remark: See “5.Parameters setting” for detail information on how to make changes to settings. 3. Device description The control panel of MMPR-220 motor protective controller is as Fig.3-1 6 MMPR-220 motor protective controller WLD[K]-JY-450-2014  Fig.3-1 3.1 Indicators There are 4 indicators on the control panel of motor protective controller, which are RUN, COMM, ALARM, TRIP. RUN: when the motor protective controller is on power and running, “RUN” flashes in yellow; COMM: when the motor protective controller is communicating, “COMM” flashes in yellow; ALARM: when parameters of the motor protective controller are wrong, or alarm is on, “ALARM” is steadily illuminated in red; TRIP: when protection trips, “TRIP” is steadily illuminated in red. 3.2 Keypad There are 7 buttons on the control panel of motor protective controller: Start I/, Start II/,  , , Cancel, Stop, Enter “Start I/, Start II/”:When it is in cycle displaying mode, the key used to start the motor, and their function varies according to the start method; when it is in parameter modifying mode, the key used to move the cursor; “”:Menu selecting, moving upwards or increasing the value; “”:Menu selecting, moving downwards or decreasing the value; “Cancel”:Cancel the operation or return to the higher level menu; “Stop”:The key used to stop the motor; “Enter”:Confirm the menu or value. 3.3 Display and menu operation When it is in normal operating, it display IA, IB, IC, Uab, Ubc, Uca, P, Q, cosφ, F, Iub,DI,DO in cycle and real-time, press “” “” can check every value. (IA: phase A current,I0: Residual current,I0j: zero-sequence current,Iub: unbalance%,F: frequency,DI: binary input, DO: binary output) The meaning of every menu is as follows: View data-------- Used to view the protective data, measuring data, binary input, power metering, motor running data and device version information: Revert--------Used to revert signals; Setting--------Used to set and view protections and protection ON/OFF; Parameter--------Used to set and view parameters of communication, motor control, DCS, CT coefficient, power metering etc; Events--------Used to view and delete event report and delete motor operation parameter; Time-------- Used to set and view the system time; Password--------Used to modify system password; Binary output-------- Used to test the binary output; calibration--------Used to calibrate measuring value. 7 MMPR-220 motor protective controller WLD[K]-JY-450-2014 4. Operating principle The motor protective controller firstly sample the three phase current of phase A,B,C and zero sequence current I0, leakage current, voltage of phase A to phase B through current transformer, potential transformer, then the signal is transmitted to analog-to-digital conversion, the cpu reads the data of all channels and calculates and processes, then compare them to every settings and find out if the motor is on fault, if it is, then the corresponded relay is operated and the information is displayed on the LCD screen. See the principle on Fig.4-1.  Fig.4-1 When it is in normal operation, it is in monitoring state, it displays three phase current, three phase voltage, frequency, power etc. in cycle. 8 MMPR-220 motor protective controller WLD[K]-JY-450-2014 5. Parameter setting 5.1 System parameter setting 5.1.1 Parameters list Category Setting name Setting range Remarks Communication address 01-99 00:2.4Kbps 01:4.8Kbps Baud rate 00-04 02:9.6Kbps Communication settings 03:19.2Kbps 04:38.4Kbps 00:No check Parity check setting 00-02 01:Odd 02:Even Remote/Local control selection 00-01 00:Remote 01:Local 00:Binary input control Remote control mode 00-02 01:Contact control 02 : Communication control 00:Direct start 01 : Decreased voltage start 02:Y-∆ 2-relay start Motor start method 00-06 03:Y-∆ 3-relay start 04:Bi-direction start 05:Bi-speed start 06:Converter control Start delay from 1—2 0.00-60.00s 00:AC Motor forward reverse method 00-02 01:AB Motor control 02:BC parameters Automatic start method 00:OFF after power on 00-01 01:Recover Effective delay of automatic start 0.00-60.00s Automatic start is prohibited after the delay Automatic start delay 0.20-60.00s Automatic start after this delay if conditions meet 00:OFF Low voltage/voltage loss restart 00-02 01:Restart immediately 02:Restart after delay Effective delay of 0.50-60.00s Automatic start is automatic restart prohibited after the delay Automatic restart delay 0.00-60.00s Automatic restart after this delay if conditions meet When should the output Control return time 0.50-10.00s contact return after starting or stopping the motor Protection return 00:Immediately return method 00-01 01:Return after revert 9 MMPR-220 motor protective controller WLD[K]-JY-450-2014 Category Setting name Setting range Remarks Instantaneous over-current and 00:No contactor zero-sequence 00-01 01:Open contactor protection output 00: IA、01:IB、02: IC、 DA channel selection 00-05 03: UAB DCS parameters 04: UBC、05: UCA setting DA coefficient 1 setting 1.000-8.500 4mA channel calibration DA coefficient 2 setting 0.100-1.000 20mA channel calibration Protective CT coefficient 0.01-500.00 CT/PT coefficients Residual current CT coefficient 0.01-50.00 setting PT coefficient 0.01-80.00 Power metering Active energy meter 0-4294967.295KWH setting Reactive energy meter 0-4294967.295WVH Display setting Display setting 0-32  “Protection return method” parameters setting note: When protection operates, the return methods of protection output are: “direct return” means the protection output returns automatically when the fault disappears. “Reverting return” means protection output returns by reverting operation and it must meet reverting conditions when the fault disappears. “Instantaneous over-current and zero-sequence protection output” parameters setting note: When instantaneous over-current or zero-sequence protection operates, the protective outputs are: “no contactor” means the protection trips on circuit breaker, not on contactor. “Contactor trip” means the protection not only trips on contactor, but also on circuit breaker. 5.1.2 Setting method  Move the cursor to “parameter” menu on main menu, press “Enter” button, to enter “password” menu, see Fig.5-1;  Input the correct password(“0000” by default), press “Enter” button to enter parameter setting menu;  Choose the demand parameter, press “Enter” to enter corresponding sub-menu;  Press “” and “” to choose the menu to make changes, press “Enter” button to enter and make changes, see Fig.5-2;  Press “”, “” button to move cursor to desiring digit(the digit which is desired to modify), press “” and “” button to increase or decrease value;  After modification, press “Enter” to Enter the modification, if “Cancel” is pressed, the modification is discarded. Enter password COMM. setting Device address. 0000 01 Fig.5-1 Fig.5-2  Note: When “Protection CT coefficients” or “motor rated current” are being modified, please put all protections off. MMPR-220 motor protective controller change the current to voltage signals through external current transformer, “protective CT coefficient” should be set according to the model of the external 10 MMPR-220 motor protective controller WLD[K]-JY-450-2014 current transformer, the value equals to the one marks as motor rated current on current transformer. Example: The model of current transformer is “Current transformer CT-25M2 10”, primary rated current of motor is 25A, maximum range is 10 times, so the maximum current to be measured is 25×10=250. Set current transformer coefficient of menu “Current transformer coefficient” to 25.  “DCS parameters setting” Firstly, the current or voltage channel expected to transfer need to be set, before connected to any source, set “DA coefficient 1 setting” to let “terminal 31, 32”(see MMPR-220 motor protective controller terminal figure for detail) output 4mA DC current; set “DA coefficient 2 setting” to let “terminal 31, 32” output 20mA DC current. After setting “DCS parameter settings”, when applying analog signal to corresponding channel, “terminal 31, 32” will output 4-20mA, especially when applying analog signal of value 0 it will output 4mA, when applying rated voltage or CT rated current, it will output 20mA. 5.2 Protective setting 5.2.1 Method of modifying protective setting  Move the cursor to “setting”, press “Enter” button, enter password(“0000” by default) to enter setting modification menu;  The method of modifying is the same as that of “parameter”;  Please refer to this manual “2.2 protective function” for protective settings.  The setting range and setting step in the item are set according to limit state. The range is slightly different according to the rated current of motor. 5.2.2 Protection ON/OFF  Select “protection ON/OFF” menu, press “Enter” button, enter password(“0000” by default) to enter protective setting menu;  Move the cursor to “Protection ON/OFF”, to enter protection ON/OFF menu.  Press “”, “” button to select ON or OFF, press “” and “” button to choose protection.  If the “PT signal alarm” is on, the low-voltage protection and under-power protection should be blocked with alarm signal when PT is broken. Tab.5-1 No. Protection Name Setting range 1 Acceleration protection ON, OFF 2 Instantaneous overcurrent protection ON, OFF 3 Locked rotor protection ON, OFF 4 Over load protection trip ON, OFF 5 Over load protection alarm ON, OFF 6 Thermal protection trip ON, OFF 7 Thermal protection alarm ON, OFF 8 Unbalance protection ON, OFF 9 Zero sequence current protection ON, OFF 10 Leakage current protection trip ON, OFF 11 Leakage current protection alarm ON, OFF 12 Open-phase protection ON, OFF 13 Phase sequence protection ON, OFF 14 Under-power protection ON, OFF 15 Low voltage protection ON, OFF 16 Over voltage protection trip ON, OFF 17 Over voltage protection alarm ON, OFF 11 MMPR-220 motor protective controller WLD[K]-JY-450-2014 No. Protection Name Setting range 18 Technology interlock ON, OFF 19 tE protection ON, OFF 20 PT signal alarm ON, OFF 5.3 Analog setting  Select “calibration” menu, press “Enter” button, enter password (“0000” by default) to enter analog setting menu.  Apply corresponding analog source, enter into the actual value applied.  The standard of corresponding correction value is: voltage is the rated measuring voltage, leakage current is 1000mA, three phase current is the rated current of corresponding current transformer. If the value input is too high or too low, calibration will not succeed, it will display message “Please input rated value”.  The content of “Automatic calibration” is listed in Tab.5-2. Tab.5-2 No. Parameter name Setting range remarks 1 Calibrate voltage UAB 0-9999.99V 2 Calibrate voltage UBC 0-9999.99V 3 Calibrate voltage UCA 0-9999.99V 4 Calibrate current IA 0-9999.99A 5 Calibrate current IB 0-9999.99A 6 Calibrate current IC 0-9999.99A 7 Calibrate Residual current 0-9999mA 8 Calibrate UAB<>IA 0-89.99 Calibrate After calibrate current and voltage9 UBC<>IC 0-89.99  Correct the analog channel before applying corresponding source is prohibited.  Please proofread voltage and current before UAB <> IA and UBC <> IC has been proofread correction. When proofreading UAB <> IA and UBC<>IC, the angle which has been inputted stands for two-table method measured active power. MMPR-220 can be corrected by applying the maximum current of “the scope of application”(see nameplate of external primary current transformer, model description in Fig.5-3, see App. Tab.2 for selection of transformer) marked on the primary current transformer. C T M M a x im u m m e a s u r in g s c o p e , th e v a lu e is m u lt ip le o f r a te d c u r re n t .(M a x . is 1 2 t im e s ) C o n f ig u ra t io n n u m b e r C o n f ig u ra t io n s ig n P r im a ry c u r re n t ra t in g o f m o to r C u r re n t t r a n s fo rm e r  Fig.5-3 5.4 System time  Select “time” in main menu, press “confirm” button, to enter system time menu;  Press “Enter” button in “time” menu, to do modifications;  Press “”, “” button to select corresponding parameter which is desired to modify, press “” and “” button to change the value;  After modification, press “Enter” to Enter the modification, if “Cancel” is pressed, the modification is discarded. 5.5 Password setting  Select “password” in main menu, press “Enter” button, enter password modification menu, the password is “0000” by default;  Enter old password first, press “Enter” button to enter new password modification menu, press “cancel” to exit password modification menu;  Enter new password, press “Enter” to Enter the modification, if “Cancel” is pressed, the modification is discarded. 12 MMPR-220 motor protective controller WLD[K]-JY-450-2014 6. Check Method 6.1 Preparation before check 6.1.1 Check before power is on External wiring is correct, appearance is good, plug-ins are in good contact with others. 6.1.2 Monitoring and adjusting of analog quantities Firstly set CT/PT coefficients correctly in “parameter”-“CT/PT coefficient setting” menu, apply current of phase A, B, C, leakage current ,UAB, UBC and UCA according to Tab.6-1, view the data in main cycle display through moving “” button. Apply primary current directly to the external primary current transformer. Tab.6-1 Analog name Checking method Protective phase A current Apply rated current, the variations of display should not exceed 1% Protective phase B current Apply rated current, the variations of display should not exceed 1% Protective phase C current Apply rated current, the variations of display should not exceed 1% Residual current Apply 1000mA, the variations of display should not exceed 1% Phase to phase voltage UAB Apply rated measuring voltage(380V or 100V etc.), Phase to phase voltage UBC device displays the primary voltage(secondary voltage*PT coefficients), the variations should not Phase to phase voltage UCA exceed 2%  Choose “view data” menu, press “Enter” button, enter real-time data viewing menu;  If the data displayed exceed 5% the actual value applied, correct the corresponding analog channel through “channel setting” menu. 6.1.3 View binary input  Move the cursor to “binary input” in “view data” menu, press “Enter” to enter binary input menu;  Connect rated voltage (AC, DC 220V or 110V) to COM terminal, the other to IN1~IN7, the corresponding display bit will change from “open” to “close”;  Disconnect binary input voltage, the corresponding display bit will change from “close” to “open”. 6.1.4 View binary output  Choose “binary output”, press “Enter” and enter password(“0000” by default) to view binary output in the menu;  Move the cursor to the output desired to check, press “Enter” button, enter the corresponding output check menu, select close, open to finish checking;  Or move the cursor to operate all outputs, press “Enter” button, enter operate all output menu, select close, open to finish checking.  Move the cursor to the LED or LCD desired to check, press “Enter” button, enter the corresponding LED or LCD check menu, select close, open to finish checking; 6.2 Check of control function Before checking the control function and protective function, please confirm the control mode of protective controller through “parameter”-“motor control parameter”-“motor start method”, and check correspond to the mode. The definition of control mode, binary input and output are as Tab.6-2. 13 MMPR-220 motor protective controller WLD[K]-JY-450-2014 Tab.6-2 Note:Input 7 is shared with leakage current input, when ordering, please note. Note:All the inputs and outputs can be freely defined, this table is the default setting. According to project needs, the definition of each terminal there may be differences, terminals to be defined by the project needs. 14 Output Trip contactor and Trip contactor and Trip contactor and 5 stop motor stop motor Reserved Close contactor 3 Trip contactor and stop motor stop motor Output Trip circuit Trip circuit 4 Breaker Breaker Trip circuit Breaker Trip circuit Breaker Trip circuit Breaker Trip circuit Breaker Output Trip signal/alarm Trip signal/alarm Trip signal/alarm Trip signal/alarm Trip signal/alarm 3 signal signal signal signal Trip signal/alarm signal signal Output 2 Reserved Motor direct start Motor start stop 2 Motor start stop 2 Start motor 2 Start motor 2 Output 1 Start motor Motor decreased voltage start Motor start stop 1 Motor start stop 1 Start motor 1 Start motor 1 Input 7 Reserved Reserved Reserved Contactor 3 status Terminal input start 2 Reserved Input Terminal input Terminal input 6 stop stop Terminal input stop Terminal input stop Terminal input stop Terminal input stop Input Terminal input Terminal input 5 start start Terminal input start Terminal input start Terminal input start 1 Terminal input start Terminal input Input Reserved Contactor 2 Contactor 2 Contactor 2 4 Contactor 2 status status status status converter 2 Terminal input Input 3 Contactor status Contactor 1 status Contactor 1 status Contactor 1 status Contactor 1 status converter 1 Input Remote control Remote control Remote control Remote control Remote control Remote control 2 select(short\open) select(short\open) select(short\open) select(short\open) select(short\open) select(short\open) Technology Technology Technology Technology Technology Input 1 interlock(circuit interlock(circuit interlock(circuit interlock(circuit Technology interlock(circuit interlock(circuit breaker) breaker) breaker) breaker) breaker) breaker) Name of Y-∆ start 1 Y-∆ start 2 starting Direct start Decreased voltage autotransformer autotransformer Bi-spee method Soft starter control start start start Bi-direction start d start Converter control (2-relay) (3-relay) Starting method 0 1 2 3 4 5 6 code MMPR-220 motor protective controller WLD[K]-JY-450-2014 6.2.1 Local control mode  Remark: Only when it is on cycle display mode, can the motor be controlled to start or stop, it is prohibited when enter other menus, in order to avoid misoperation like starting or stopping the motor when parameters are being modified or data being viewed.  Direct start  Choose “parameter”, enter “motor control parameter” menu, select local in “remote/local selection”.  When it is on cycle display menu, press “start I/” button, see Fig.6-1.  Press “Enter” button, the terminals of OUT1 should close immediately, indicating that the motor is started.  When it is on cycle display menu, press “stop”, see Fig.6-2.  Press “confirm” button, OUT51-OUT52 should close immediately, OUT52-OUT53 should open immediately, indicating that the motor is stopped. Start motor 1 confirm Fig.6-1 Stop motor confirm Fig.6-2  Y-∆ start or autotransformer start (3-relay)  When it is on cycle display menu, press “start I/” button, see Fig.6-1.  Press “Enter” button, OUT51-OUT52 should close immediately, at the same time OUT1 should be closed, indicating that the motor is started.  After the start time set, OUT1 should open, after the signal return OUT2 should close immediately, it means the finish of Y-∆ start or autotransformer start procedure.  When it is on cycle display menu, press “stop” button, see Fig.6-2, press “Enter” button, terminals OUT2, OUT51-OUT52should open immediately, indicating that the motor is stopped.  If the motor need to be stopped during the start time with terminal OUT1, OUT51-OUT52 closed, press “stop” button, see Fig.6-2, press “Enter” button, terminal OUT1, OUT51-OUT52 should open, indicating that the motor is stopped.  Bi-direction start or bi-speed start  When it is in cycle display menu, press “start I /” button, see Fig.6-1.  Press “Enter” button, AC contactor II should be open, thus terminal OUT1 should close immediately, indicating that the motor is started forward and in speed 1.  When it is needed to change direction or speed, press “stop” button, see Fig.6-2, press “Enter” button, terminal OUT51-OUT52 should close immediately, terminal OUT52- OUT53 should open immediately, indicating that the motor is stopped.  After delayed for start delay 1-2, press “start II/”, see Fig 6-3, press “Enter” button, OUT2 should close immediately, indicating that the motor is started backward or in the other speed, AC contactor I should open during start.  If “start II/” button is press before delay for start delay 1-2, motor protective controller will not response to the operation. Motor start 2 confirm Fig.6-3 6.2.2 Remote control mode  Select remote in “remote/local selection” in menu “parameter”-“motor control parameter”, the motor protective controller will be in remote control mode;  Remote control mode is classified of terminal control and communication control. Remote control method can be selected through “remote control method” in 15 MMPR-220 motor protective controller WLD[K]-JY-450-2014 “parameter”-“motor control parameter” and IN2;  If remote control mode is “communication control”, or if remote control method is “binary input select” when IN2 is also 1, the motor protective controller is in communication start stop control mode; If remote control mode is “terminal control”, or if remote control method is “binary input select” when IN2 is 0, the motor protective controller is in terminal start stop control mode. 6.2.2.1 Communication control mode If remote control mode is “communication control”, or if remote control mode is “binary input select” when voltage existes on IN2,communication start or stop the motor can be achieved through sending order from background software to motor protective controller. 6.2.2.2 Terminal control mode If remote control mode is “terminal control”, or if remote control mode is “binary input select” when IN2 is disconnected,terminal start or stop the motor can be achieved. 【Remarks:】Please see the setting descriptions of “control input method” in this manual 5.1.1,the following examples are applied only when it’s the open contact input method in “control input signals”.  Direct start  Apply voltage between IN5 and COM, the OUT1 terminals should close immediately, indicating that the motor should start.  Apply voltage between IN6 and COM, OUT51-OUT52 should close immediately, OUT52- OUT53 should open immediately, indicating that the motor should stop.  Y-∆ start or autotransformer start (3-relay)  Apply voltage between IN5 and COM, OUT51-OUT52 should close immediately, at the same time OUT1 should be closed, indicating that the motor should start.  After the start time set, OUT1 should open, after the signal return OUT2 should close immediately, it means the finish of Y-∆ start or autotransformer start procedure.  Apply voltage between IN6 and COM, OUT2, OUT51-OUT52 should close immediately, OUT52-OUT53 should open immediately, indicating that the motor should stop.  If the motor need to be stopped during the start time with terminal OUT1, OUT51-OUT52 closed, apply voltage between IN6 and COM, terminal OUT1, OUT51-OUT52 should open, indicating that the motor should stop.  Bi-direction start  Apply voltage between IN5 and COM, OUT1 should close immediately, indicating that the motor should start, AC contactor II should open during start.  When it is needed to change direction or speed, apple voltage between IN6 and COM, terminal OUT51 - OUT52 should close immediately, terminal OUT52- OUT53 should open immediately, indicating that the motor should stop.  Apply voltage between IN7 and COM, OUT2 should close immediately, indicating that the motor is started backward or in the other speed, AC contactor I should open during start. 6.2.3 Automatic start control on power Acceleration time of motor (this parameter is in “setting”-“motor operation setting”) should be set larger than 1 second. MMPR-220 IA(IB,IC) IA(IB,IC) L IA'(IB’,IC') IA’(IB’,IC’) UA UA Power supply UB UB UC UC N  Fig.6-4  Automatic start on power mode (the corresponding parameters are in “parameter” -“motor control parameter”) should be set as “1”, which means “recover” mode, and set “automatic start 16 MMPR-220 motor protective controller WLD[K]-JY-450-2014 delay” to 2S, then start the motor, apply analog signals as in Fig.6-4, indicates that the motor has started. Cut the power supply of motor and the analog inputs, apply the power supply to the motor protective controller within “Effective delay of automatic restart(set to 10S)”, it will restart the motor after delayed for 2S. Apply analog signals as in Fig.6-4, indicates that the motor has started, stop the motor by remote control, cut the analog inputs, indicating that to stop the motor. Cut the power supply of the protective controller, then reapply the power supply to it, it won’t start the motor.  Set automatic start on power mode to “0”, which means to put automatic start on power mode OFF, the motor will not start whenever the protective controller is power off and power on again.  If the controller is power off for the time longer than the effective delay of automatic restart, the automatic start control will not function. 6.2.4 Low voltage/voltage loss restart control  Set low voltage/voltage loss restart to “1”, which means “immediate restart” of low voltage/voltage loss restart is ON, indicating that if the voltage falls within 0.5S, take inertia into account, the rotating speed of motor will not fall much, direct restart motor is allowed. If the voltage falls for longer than 0.5S but shorter than “effective delay of automatic restart”, the device will restart the motor according to the restart delay. Set low voltage/voltage loss restart to “2”, which means “restart after delay” of low voltage/voltage loss restart is ON, indicating that if the voltage falls within “restart efficient delay”, the device will start the motor according to “restart delay” after the voltage recovery; set low voltage/voltage loss restart to “0”, which means low voltage/voltage loss restart is OFF(the parameter is set in system parameter setting menu).  Wire as Fig.6-4, set low voltage/voltage loss restart to ON(choose “immediate restart”), set low voltage setting to 300V, set motor acceleration time to over 2S according to practical use, set restart efficient delay to 5S, set restart delay to 2S, then start the motor.  Decrease the voltage to below 300V, cut the power of motor(for example, let low voltage protection trips the motor by motor protective controller or cut the voltage and current and other analog signals manually).  Reapply the voltage to normal value, if it is within 0.1 s~0.5s, the motor protective controller will start the motor immediately.  If it is within 0.5s~5s , the motor protective controller will restart the motor after delayed for 2S.  If it is longer than restart effective delay(5S), restart of the motor will be prohibited by the motor protective controller. If low voltage/voltage loss restart is set to “0”, which means low voltage/voltage loss restart is OFF. 6.3 Check of protective function  Note: Ie stands for the rated current of motor, Pe stands for the rated power of motor.  Note: when checking portective function, please make sure that the current is at the range of 0.05~1.0 of the external current transformer. 6.3.1 Check of acceleration protection If the motor dose not finish starting within the given start time, the protection operates. The operation logic is as Tab.6-3, the parameters needed for acceleration protection are in 2.2.1 this manual , Tab.2-1. Tab.6-3 Acceleration protection ON Acceleration protection operation logic Starting time > start time of motor The largest phase current of motor > 1.2Ie  Wire as Fig.6-4, set acceleration protection to ON;  Set start time of motor as Tab.6-4, apply 1.2 times rated current until it trips, record the time of acceleration protection operates;  When the protection operates, terminal OUT3, OUT51-OUT52 should be shorted, terminal OUT52-OUT53should be opened;  If the start mode of motor protective controller is 3, the terminal which will be close is OUT3; the terminal which will be open are OUT1、OUT51-OUT52. Tab.6-4 Acceleration protection time(S) 5 10 20 40 Actual time tested (S) 17 MMPR-220 motor protective controller WLD[K]-JY-450-2014 6.3.2 Check of instantaneous over-current protection When one of the current of phase A, B, C becomes higher than the setting value and last for the delay time set the protection operates; the setting of start time or post-start time can be set independently. The operation logic of instantaneous over current protection is as Tab.6-5, the parameters needed for instantaneous over-current protection are in 2.2.2 this manual, Tab.2-2. Tab.6-5 Instantaneous Instantaneous over-current protection ON over-current Instantaneous current > Instantaneous over-current protection protection setting current operation logic Current time > setting delay  Wire as Fig.6-4, set instantaneous over-current protection to ON, set delay as 0 second, set other protections to OFF;  Set as Tab.6-6, record the time of instantaneous over-current protection operates, record it on the table; When “Instantaneous over-current and zero-sequence protection output” (in tab. 5.1.1) is 0:  When the protection operates, terminal OUT3, OUT4 should be shorted. When “Instantaneous over-current and zero-sequence protection output” (in tab. 5.1.1) is 1:  When the protection operates, terminal OUT3, OUT4, OUT51-OUT52 should be shorted and OUT52-OUT53 should be opened.  If the start mode of motor protective controller is 3, the terminal which will be closed is OUT3, OUT4, the opened terminals are OUT1, OUT51-OUT52 when starting and OUT2, OUT51-OUT52 after starting. Tab.6-6 Starting current setting (Ie) 1Ie 2Ie 5Ie 10Ie Starting current post-setting (Ie) Actual value when operates 6.3.3 Check of locked rotor protection Locked-rotor protection is automatically blocked during the start of motor, and enabled after motor started, if actual current is higher than set current of locked-rotor and last for set delay time, the protection operates. The operation logic of locked-rotor protection is as Tab.6-7, the parameters needed for locked-rotor protection are in 2.2.3 this manual , Tab.2-3. Tab.6-7 Motor has been started successfully Locked rotor protection is ON Locked rotor operation logic Locked rotor current > locked rotor current setting Locked rotor time > locked rotor delay setting  Wire as Fig.6-4, set locked rotor protection to ON, set locked rotor delay to 0S, set other protections to OFF.  When the protection operates, terminal OUT3, OUT51-OUT52 should be shorted, terminal OUT52-OUT53should be opened.  If the start mode of motor protective controller is 3, the terminal which will be close is OUT3; the terminal which will be open are OUT2、OUT51-OUT52. Tab.6-8 Locked rotor current setting (Ie) 2.0Ie 3.0Ie 4.0Ie Actual value when operates 6.3.4 Check of over load protection When actual current is over the over load current setting and last over setting delay, the protection operates. The operation logic of over load protection is as Tab.6-9, the parameters needed for locked rotor protection are in 2.2.4 this manual , Tab.2-4. 18 MMPR-220 motor protective controller WLD[K]-JY-450-2014 Tab.6-9 Over load protection is ON Motor starts. Over load protection operation logic Over load current > over load current setting Over load time > over load delay setting  Wire as Fig.6-4, set over load protection to ON, set over load delay to 0S, set other protections to OFF.  Set according to Tab.6-10, test the actual value, and record it in the table.  If over load protection is in alarm mode  When it operates, terminal OUT3 should be shorted, when fault current is cut, alarm revert, OUT3 should be opened.  If over load protection is in trip mode  When the protection operates, terminal OUT3, OUT51-OUT52 should be shorted, terminal OUT52-OUT53 should be opened.  If the start mode of motor protective controller is 3, the terminal which will be close is OUT3; the terminal which will be open are OUT2, OUT51- OUT52. Tab.6-10 Over load current setting (Ie) 1Ie 2Ie 3Ie Actual value when operates 6.3.5 Check of thermal protection Over heating is an important cause of motor damage, especially the over heading produced by negative sequence current in rotor, the operation logic of thermal protection, according to ANSI/UL 2111-2002 Standard for Overheating Protection for Motors, is as follows:  t  1 K (I / I )2  K (I / I )2 1.052 1 1 e 2 2 e In the equation:t —— protection operation time(S); τ1—— motor overheat time constant(S),correspond to the over load ability of the motor; I1—— actual positive sequence of current when the motor is operating(A); I2—— actual negative sequence of current when the motor is operating(A); Ie——thermal protection pickup current( this is the secondary value of current transformer correspond to the motor actual rated current); K1——positive heating coefficient of motor, it can be set from 0~1 during start, and the setting step is 0.01, used to ignore start current, it will automatically change to 1 after start; K2——negative heating coefficient of motor, it can be set from 0~10, and the setting step is 0.01, normally it can be set to 6. Thermal protection can be set to alarm and/or trip mode, there are individual control words that can be either set to ON or OFF. Thermal alarm is a predicting signal, it can be set between 50%~100% of trip value with setting step of 1%. When the motor is tripped for overheat, the terminal of output relay of device will remain close, the device will cool the motor according to the cooling time constant, after the motor has cooled down to 40% of trip value the output relay will return, which will permit the motor to restart. In some emergency circumstances that the motor must be restart, enter “signal revert” menu to revert the output relay.  Remark:In order to maintain the precision, 3 phase current should be applied to do this test. If motor start mode is bi-direction start, K2 should be set to 0. The operation logic of thermal protection is as Tab.6-11, for the details of the parameters for thermal protection, refer to this manual 2.2.5 Tab.2-5. Tab.6-11 Thermal protection ON Thermal protection operation logic Operates as inverse time according to the equation above.  Wire as Fig.6-4, set thermal protection to ON, and other protections to OFF. Set K1=1, K2=0. 19 MMPR-220 motor protective controller WLD[K]-JY-450-2014  Set motor overheat time constant τ1 according to Tab.6-12, apply current. When the current reach 1.05Ie it starts to do inverse accumulation of heat calculations, the higher the current, the faster it trips.  If thermal protection is in alarm mode  When it operates, terminal OUT3 should be shorted, when fault current is cut, alarm revert, OUT3 should be opened.  If thermal protection is in trip mode  When the protection operates, terminal OUT3, OUT51-OUT52 should be shorted, terminal OUT52-OUT53 should be opened.  If the start mode of motor protective controller is 3, the terminal which will be close is OUT3; the terminal which will be open are OUT1、OUT51-OUT52 during start; OUT2, OUT51- OUT52 after start. Tab.6-12 Current applied (Ie) 1.2Ie 1.5Ie 2.0Ie τ1 = 5 τ1 = 20 τ1 = 100 6.3.6 Check of unbalance protection Calculate the maximum difference of average current of 3 phase and the phase current, divide by the average current of 3 phase we get the unbalance(%), if it is higher than the setting and last for the setting delay, it operates. 3-phase average current- maximum Unbalance% (minimum) single-phase current = ×100% 3-phase average current  Remark:In order to prevent from possible malfunction when closed asynchronously, it is recommended that the delay of unbalance protection to be longer than 1S. The operation logic of unbalance protection is as Tab.6-13, for the details of the parameters needed for unbalance protection, please refer to this manual 2.2.6 Tab.2-6. Tab.6-13 Unbalance Unbalance protection ON protection Unbalance > unbalance setting operation logic Unbalance time > unbalance delay  Wire as Fig.6-4, set unbalance protection to ON, set unbalance delay to 0S, set other protections to OFF.  Set unbalance protection setting according to Tab.6-14, test the actual value, and record it in the table.  When the protection operates, terminal OUT3, OUT51-OUT52 should be shorted, terminal OUT52-OUT53 should be opened.  If the start mode of motor protective controller is 3, the terminal which will be close is OUT3; the terminal which will be open are OUT1、OUT51-OUT52 during start; OUT2, OUT51- OUT52 after start. Tab.6-14 Unbalance setting 15% 30% 40% 50% 60% Current of phase B (Ie) 1.0Ie 1.0 Ie 1.0 Ie 1.0 Ie 1.0 Ie Current of phase C (Ie) 1.0 Ie 1.0 Ie 1.0 Ie 1.0 Ie 1.0 Ie Current of phase A (Ie) ideal operating value 1.24 Ie 1.53 Ie 1.75 Ie 2.00 Ie 2.29 Ie Current of phase A (Ie) actual operating value 6.3.7 Check of zero sequence current protection The zero sequence current is calculated using 3 phase current, when the zero sequence 20 MMPR-220 motor protective controller WLD[K]-JY-450-2014 current is higher than the setting and last for the delay setting it operates. The operating logic of zero sequence protection is as Tab.6-15, for the details of parameters needed for zero sequence current protection please refer to this manual 2.2.7 Tab.2-7. Tab.6-15 Zero sequence current protection is ON Zero sequence current protection operation Zero sequence current > zero sequence current logic setting Zero sequence current time > zero sequence delay setting  Remark:in order to maintain the correctness of calculation, 3 phase current should be applied to do this test.  Wire as Fig.6-4, set zero sequence current protection to ON, set other protection to OFF. Set zero sequence current delay to 0S.  Set the zero sequence current setting according to Tab.6-16, test the actual value, and record it in the table. When “Instantaneous over-current and zero-sequence protection output” (in tab. 5.1.1) is 0:  When the protection operates, terminal OUT3, OUT4 should be shorted. When “Instantaneous over-current and zero-sequence protection output” (in tab. 5.1.1) is 1:  When the protection operates, terminal OUT3, OUT4, OUT51-OUT52 should be shorted and OUT52-OUT53 should be opened.  If the start mode of motor protective controller is 3, the terminal which will be closed is OUT3, OUT4, the opened terminals are OUT1, OUT51-OUT52 when starting and OUT2, OUT51-OUT52 after starting. Tab.6-16 Zero sequence current protection setting (Ie) 2 Ie 5 Ie 10 Ie 15 Ie Actual value when operates 6.3.8 Check of Residual current protection When the Residual current is higher than the setting and last for the delay setting, it operates. The operating logic of Residual current protection is as Tab.6-17, for the details of parameters needed for Residual current protection please refer to this manual 2.2.8 Tab.2-8. Tab.6-17 Residual sequence current protection is ON Residual current protection operation Residual current > Residual current setting logic Residual current time > Residual current delay setting  Apply Residual current as Fig.6-5, wire as Fig.6-4, set Residual current protection to ON, set other protection to OFF. Set leakage current delay to 0S.  Set the Residual current setting according to Tab.6-18, test the actual value, and record it in the table.  If Residual current protection is in alarm mode  When it operates, terminal OUT3 should be shorted, when fault current is cut, alarm revert, OUT3 should be opened.  If Residual current protection is in trip mode  When the protection operates, terminal OUT3, OUT51-OUT52 should be shorted, terminal OUT52-OUT53 should be opened.  If the start mode of motor protective controller is 3, the terminal which will be closed is OUT3; the terminal which will be open are OUT1、OUT51-OUT52 during start; OUT2, OUT51- OUT52 after start. 21 MMPR-220 motor protective controller WLD[K]-JY-450-2014 MMPR-220 I0 I0 L I0' I0’ N  Fig. 6-5 Tab.6-18 Residual current protection setting (mA) 100 500 1000 5000 Actual value when operates 6.3.9 Check of open-phase protection When one of the phase current is lower than 5% of rated current, at the same time either of the other two phase current is higher than 15% of rated current, and last for the setting delay, it operates. The operation logic of open-phase protection is as Tab.6-19, for the details of the parameters needed for open-phase protection, please refer to this manual 2.2.9 Tab.2-9.  Remark:in order to maintain the correctness of calculation, 3 phase current should be applied to do this test. Tab.6-19 Open-phase protection is ON Open-phase protection One of the phase current is lower than 10% of Ie, operation at the same time either of the other two phase current logic is higher than 30% of Ie Open-phase time > open-phase delay setting  Wire as Fig.6-4, set open-phase protection to ON, set other protection to OFF. Set open-phase delay to 0S.  When one of the phase current is lower than 5% of rated current, at the same time either of the other two phase current is higher than 15% of rated current, it operates.  When the protection operates, terminal OUT3, OUT51-OUT52 should be shorted, terminal OUT52-OUT53 should be opened.  If the start mode of motor protective controller is 3, the terminal which will be close is OUT3; the terminal which will be open are OUT1、OUT51-OUT52 during start; OUT2, OUT51- OUT52 after start. 6.3.10 Check of phase sequence protection When the motor is in the wrong phase sequence, and last for the setting delay the protection operates. When the start mode of motor is bi-direction, the protection should be put OFF. The operation logic of phase sequence protection is as Tab.6-20, for the details of the parameters needed for open-phase protection, please refer to this manual 2.2.10 Tab.2-10.  Remark:in order to maintain the correctness of calculation, 3 phase current should be applied to do this test. Tab.6-20 Phase Phase sequence protection is ON sequence Negative sequence current > 0.5 protection of rated current operation Phase sequence time > phase logic sequence delay setting  Wire as Fig.6-4, set phase sequence protection to ON, set other protection to OFF. Set phase sequence delay to 0S. 22 MMPR-220 motor protective controller WLD[K]-JY-450-2014  Exchange current of phase A, C, the protection operates.  When the protection operates, terminal OUT3, OUT51-OUT52 should be shorted, terminal OUT52-OUT53 should be opened.  If the start mode of motor protective controller is 3, the terminal which will be close is OUT3; the terminal which will be open are OUT1、OUT51-OUT52 during start; OUT2, OUT51- OUT52 after start. 6.3.11 Check of under-power protection When the power is lower than the setting value and last for the setting delay, the protection operates. If the PT alarm is on, the protection should be blocked when PT is broken. The operation logic of under-power protection is as Tab.6-21, for the details of the parameters needed for open-phase protection, please refer to this manual 2.2.11 Tab.2-11.  Remark:in order to maintain the correctness of calculation, phase current IA, IC, UAB and UBC should be applied to do this test. Tab.6-21 Under-power protection is ON Under-power protection operation logic Power < Under-power setting Under-power time > under-power delay setting  Wire as Fig.6-4, apply current IA, IC, voltage UAB, UBC, set phase sequence protection to ON, set other protection to OFF. Set under-power delay to 0S.  Set the under-power setting according to Tab.6-22, test the actual value, and record it in the table.  When the protection operates, terminal OUT3, OUT51-OUT52 should be shorted, terminal OUT52-OUT53 should be opened.  If the start mode of motor protective controller is 3, the terminal which will be close is OUT3; the terminal which will be open are OUT1、OUT51-OUT52 during start; OUT2, OUT51- OUT52 after start. Tab.6-22 Under-power protection setting(KW) 0.2Pe 0.3Pe 0.5Pe Actual value when operates 6.3.12 Check of low voltage protection When the start current is higher than 0.1 time of rated current of motor, if it reaches the setting, the protection operates. If PT alarm is on, the protection is blocked when PT is broken. When the voltage and current drop at the same time, the low-voltage protection also operates after the delay. The operational logic of low-voltage protection is as 6-23. The needed parameters of low-voltage protection are provided in the Tab.2-12 of this manual 2.2.12. Tab.6-23 Low-voltage protection is on. Voltage < setting of low-voltage protection(over Low-voltage protection logic 20V) Low-voltage protection delay > time-delayed setting  Wire as Fig.6-4, set the start time of motor as 0S, set the low-voltage protection to ON, set the time-delayed value as 0S, other protections are off. Feed the current of any phase(Larger than 0.1 Ie).  Set the low-voltage setpoint as Tab.6-24, measure the operational value and then keep a record in the table.  When the protection operates, measuring terminals OUT3、OUT51-OUT52 should be connected, and OUT52-OUT53 should be separate. If the start mode of motor protective controller is 3, when the protection operates, OUT3 should be closed, and OUT1、OUT51-OUT52 should be closed during start, OUT2、OUT51-OUT52 be open after start. Tab.6-24 23 MMPR-220 motor protective controller WLD[K]-JY-450-2014 Low-voltage protection setting(V) 200 250 300 350 Operational value 6.3.13 Check of over-voltage protection When the start current is higher than 0.1 time of rated current of motor, bus voltage is higher than the setting, and meets the time-delayed value, the protection operates. The operation logic of over-voltage protection is as Tab.6-25. The needed parameters of over-voltage protection are provided in the Tab. 2-13 of this manual 2.2.13. Tab.6-25 Over-voltage protection is on. Over-voltage protection operational logic Over-voltage > over-voltage protection setting Over-voltage protection delay > time-delayed setting  Wire as Fig.6-4, setting the over-voltage delay as 0S, other protections are off. (The value is higher than 0.1 Ie).  Setting the over-voltage value as Tab.6-26, measuring the operational value, and keeping a record in the table.  If over-voltage protection is the alarm mode,  When the protection operates, measuring terminals OUT3 is connected, when the fault is cut, alarm signal reverts, the terminal OUT3 is open.  If over-voltage protection is the trip mode,  When the protection operates, measuring terminals OUT3、OUT51-OUT52 should be closed, and the terminals OUT52-OUT53 should be open.  If the start mode of motor protective controller is 3, the terminal which will be closed is OUT3; the terminal which will be open are OUT1、OUT51- OUT52 during start, OUT2、OUT51- OUT52 after start. Tab.6-26 Over-voltage alarm setting (V) 400 420 440 460 The operational value 6.3.14 Check of technology interlock protection According to the customers’ need of the external protection input, if the input is effective and reaches to the time-delay, the motor protective controller operates. Operational logic is as Tab. 6-27,The needed parameters of technology interlock protection are provided in the Tab. 2-14 of this manual 2.2.14.  Wire as Fig.6-4, set the technology interlock protection to ON, set the time-delayed value as 0S. Other protections are off. According to Fig.6-6, feed the rated voltage between the port of COM and IN3, the protection operates.  When the protection operates, the measuring terminals OUT3、OUT51-OUT52 should be close, and OUT52-OUT53 should be open.  If the start mode of motor protective controller is 3, the terminal which will be closed is OUT3; the terminal which will be open are OUT1、OUT51- OUT52 during start, OUT2、OUT51- OUT52 after start. Tab.6-27 technology interlock protection is ON. technology interlock operational logic technology interlock protection signal input technology interlock delay > time-delayed setting 24 MMPR-220 motor protective controller WLD[K]-JY-450-2014 MMPR-220 IN1 L U Power supply COM N  Fig.6-6 6.3.15 Check of tE protection When the motor is starting, the tE protection blocks automatically, when start is completed, it is automatically to ON. tE protection is designed towards the increased safety mode motor. According with the provision of increased safety mode motor protection in Electrical apparatus for explosive gas atmospheres-Part 3: Increased safety “e” (GB 3836.3-2000). In order to avoid the motor reaching to the limited temperature, the motor protective controller should cut off the power supply of motor in period of tE. tE: the time between locked rotor current applied and limited temperature it reaches. tE protection operational logic is as Tab.6-28, The needed parameters of tE protection are provided in the Tab.2-15 of this manual 2.2.15. Tab.6-28 Motor starts. tE protection operational tE protection is ON. logic It operates in the mode of inverse time, according to the character curve above.  Wire as Fig.6-4, set the tE protection to ON and other protections to OFF. When 7 times of rated current is set, the permitted locked rotor time is 5S.(i.e. “tE time” in menu of “protection setting”).  Feed the operational current according to Tab.6-29, measure the operational time of inverse time. Keep a record in the table.  When the protection operates, the measuring terminals OUT3、OUT51-OUT52 should be closed, and OUT52-OUT53 should be open.  If the start mode of motor protective controller is 3, when the protection operates, the terminal which will be closed is OUT3, and the terminals which will be open are OUT2、 OUT51-OUT52. Tab.6-29 tE time Current input (Ie) 3Ie 4 Ie 6 Ie 7 Ie Normal operational delay (S) 16.80 9.30 5.00 4.00 4S Actual operational delay (S) Normal operational delay (S) 20.00 12.00 6.00 5.00 5S Actual operational delay (S) Normal operational delay (S) 24.00 14.80 7.70 6.00 6S Actual operational delay (S) 25 MMPR-220 motor protective controller WLD[K]-JY-450-2014 Notes: This product is a non-explosion-proof product, it must not be installed and wired in the explosion sites. When this product is used as tE protection for increased safety explosion-proof motor, all of the parameters of this product should be set manually by professionals, automatic setting must not be used.  When this product is used as tE protection for increased safety explosion-proof motor, the rated current IN of the increased safety explosion-proof motor being controlled must not exceed the maximum current of its model.  When this product is used as tE protection for increased safety explosion-proof motor, the tE time must not exceed 1.7 times of the corresponding increased safety explosion-proof motor(see motor label). 6.4 Check of communication function 6.4.1 Check of measuring analog value Current of phase A, B, C, zero sequence current, phase to phase voltage UAB, UBC, active power, reactive power, power coefficient can be transmitted to background monitor system through communication port. 6.4.2 Check of remote signal upload All protection information, binary change information can be transmitted to background monitor system through communication port. 7. Product maintenance Please contact the manufacturer to deal with. 8. Cautions  Please refer to the label of the device for the details of the voltage of motor protective controller, please be sure about the voltage and the power supply terminals, the internal components may be damaged if the wiring method is not correct.  When doing checking of the motor protective controller, please don’t apply high current for long.  Terminal “shielding ground” should be firmly connected to ground.  Non-professionals should not disassemble the motor protective controller. 26 MMPR-220 motor protective controller WLD[K]-JY-450-2014 Appendix 1:MMPR-220 motor protective controller terminal figure 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Output 5(12,13 are Power supply 3 the trip output open ( means ground Output 1 Output 2 Output 3 Output 4 terminals;13,14 ) are the trip output closed terminals) MMPR-220 motor protective controller terminal definitions Ua Ub Uc Ia Ib Ic In 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 N ote: Input 7 is shared with leakage current input. When ordering, please mention that which function is used. 27 COMM. B COMM. A DC output - DC output + Signal input COM Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 (leakage current) Appendix 2:tE protection inverse characteristics table and figure 28 30 tE(s) IA/IN 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.2 7.5 8.0 Operation time 17.60 13.10 10.10 8.20 7.00 6.10 5.30 4.80 4.40 4.40 4.40 4.40 25 20 ①.The curve is the figure 3 of item 5.1.4.3 in GB 3836.3-2000. ②.The action curve of tE protection 15 10 5 IA/IN 0 2 4 6 8 10 Appendix Tab.1:Typical specifications of external current transformer Typical specifications of external current transformer No. Specifications of Power of motor transformer hole maximum current transformer diameter measuring range 1 1A <0.5KW ∮20mm 10X 2 5A 0.5~2.5KW ∮20mm 10X 3 12A 2.5~6.0KW ∮20mm 10X 4 25A 6.0~12.5KW ∮20mm、∮30mm 10X 5 50A 12.5~25KW ∮20mm、∮30mm 10X 6 100A 25~50KW ∮20mm、∮30mm 10X 7 200A 50~100KW ∮20mm、∮30mm 10X The specifications of external current transformer above are the rated current of the corresponding motors, the maximum measuring range is 10X. If the capacity of the motor is too high, a combination of 1A and 5A external current transformer and the primary high-capacity current transformer can be used. 29 Appendix Fig.1:Direct start 30 Appendix Fig.2: Bi-directional start 31 Appendix Fig.3: Reduced voltage start with resistor 32 Appendix Fig.4: Y/∆ 3-relay open-loop start 33
样本库微信小程序

微信扫一扫,手机找样本

© 2025 样本库 京ICP备17018997号-1

想要解决产品营销和销售难题?

不妨试试样本通
了解更多