Zhuhai Wanlida Electrical
Automation Co., Ltd.
http://www.zhwld.com
MLPR-220 line protection controller
user’s manual
Preparation:
Checking:
Permission:
Document No.:WLD[K]-JY-323-2014 Version: V1.05.01
Publication Date:2017/07
All rights reserved:Zhuhai Wanlida Electrical Automation Co.,Ltd
Note: The Company reserves the right to amend this statement. If a product is
inconsistent with the statement, please contact us, we will provide you with the
corresponding services.
Technical support tel.:(86)0756-3395398 Fax.:(86)0756-3395500
I
Contents
Contents
FOREWORD ............................................................................................................................................................. 1
1. PRODUCT DESCRIPTION ................................................................................................................................. 2
1.1 Scope ......................................................................................................................................................... 2
1.2 Device features ......................................................................................................................................... 2
1.3 Technical specifications and indicators ................................................................................................. 2
1.4 Device shape and model description .................................................................................................... 3
2. FUNCTIONAL DESCRIPTION ............................................................................................................................ 3
2.1 Protective functioning .............................................................................................................................. 3
2.1.1 Instantaneous over-current protection ............................................................................................... 3
2.1.2 Overcurrent protection.......................................................................................................................... 3
2.1.3 Over-load protection ............................................................................................................................. 3
2.1.4 Zero sequence current protection ....................................................................................................... 4
2.1.5 Leakage current protection .................................................................................................................. 4
2.1.6 Low voltage protection ......................................................................................................................... 4
2.1.7 Over voltage protection ........................................................................................................................ 4
2.2 Settings of protection ............................................................................................................................... 4
3. DEVICE DESCRIPTION .................................................................................................................................... 5
3.1 Indicators ................................................................................................................................................... 5
3.2 Keypad ....................................................................................................................................................... 5
3.3 Display and menu operation ................................................................................................................... 5
4. OPERATING PRINCIPLE..................................................................................................................................... 6
5. PARAMETER SETTING ...................................................................................................................................... 7
5.1 System parameter setting ....................................................................................................................... 7
5.1.1 Parameters list ....................................................................................................................................... 7
5.1.2 Setting method ...................................................................................................................................... 8
5.2 Protective setting ...................................................................................................................................... 8
5.2.1 Method of modifying protective setting .............................................................................................. 9
5.2.2 Protection ON/OFF ............................................................................................................................... 9
5.3 Analog setting ........................................................................................................................................... 9
5.4 System time ............................................................................................................................................ 10
5.5 Password setting .................................................................................................................................... 10
6. CHECK METHOD .......................................................................................................................................... 10
6.1 Preparation before check ...................................................................................................................... 10
6.1.1 Check before power is on .................................................................................................................. 10
6.1.2 Monitoring and adjusting of analog quantities ................................................................................ 10
6.1.3 View binary input ................................................................................................................................. 11
6.1.4 View binary output .............................................................................................................................. 11
6.2 Check of control function ....................................................................................................................... 11
6.2.1 Local control mode ............................................................................................................................. 11
6.2.2 Remote control mode ......................................................................................................................... 11
6.2.2.1 Communication control mode ........................................................................................................ 11
6.2.2.2 Terminal control mode ..................................................................................................................... 11
6.3 Check of protective function ................................................................................................................. 12
6.3.1 Check of instantaneous over-current protection ............................................................................. 12
6.3.2 Check of Overcurrent Protection ...................................................................................................... 12
6.3.3 Check of over load protection ........................................................................................................... 13
6.3.4 Check of zero sequence current protection .................................................................................... 13
6.3.5 Check of Residual current protection ............................................................................................... 13
6.3.6 Check of low voltage protection ........................................................................................................ 14
6.3.7 Check of over-voltage protection ...................................................................................................... 14
6.4 Check of communication function ........................................................................................................ 15
6.4.1 Check of measuring analog value .................................................................................................... 15
6.4.2 Check of remote signal upload ......................................................................................................... 15
7. PRODUCT MAINTENANCE ................................................................................................................................ 15
8. CAUTIONS ...................................................................................................................................................... 15
Appendix 1:MLPR-220 line protection controller terminal figure ......................................................... 16
Appendix Tab.1:Typical specifications of external current transformer .............................................. 17
II
Contents
Appendix Fig.1: ............................................................................................................................................. 18
III
Foreword
1. Model description
MLPR-220 line protection controller has three-phase current input of phase A,
B, C. The principle of default protection ON/OFF and settings are as follows: all
protection are off, settings being the maximum.
2. Quoted standards
The universal technical condition of static relay protection and safe
automechanism DL 478-2001
1
MLPR-220 line protection controller WLD[K]-JY-323-2014
1. Product description
1.1 Scope
MLPR-220 line protection controller works with external primary current transformer, mainly used
to protect lines of AC 1200V and below.
1.2 Device features
Uses high-performance 16-bit industrial microprocessors, high integration, functions strong, fast.
Three phase current, voltage AC sampling, perfect measuring and controlling functions.
Small size, under-power consumption, suitable for installation in the switchgear or on centralized
panel.
LCD display with wide temperature range.
Strong anti-interference capability: Level Ⅳ of rapid transient interference, level Ⅳ of
electrostatic discharge interference, electromagnetic interference Ⅲ radiation level, pulse
interference Ⅲ-class group.
With perfect protective function.
Remote start stop control with terminal control mode or communication control mode.
Keeps records even power is off.
4~20mA output with Optical isolation.
Equipped with Modbus-RTU communication method, remote measuring, remote signal and
remote control can be achieved through communication network and background monitor system.
1.3 Technical specifications and indicators
Rated parameters
AC voltage input:~380V(direct measuring),~100V(PT measuring).
AC current: 1~5000A.
Rate frequency:50Hz.
Power supply:AC/DC220V,AC/DC110V.
Main specifications
Accuracy: the measuring error of protective current, voltage does not exceed ±1%; the
measuring error of active power, reactive power does not exceed ±3%; the error of power factor
does not exceed ±1%; and the frequency error does not exceed ±0.02Hz.
Time delay and trip setting accuracy:
a) Trip setting accuracy: the error does not exceed ±3%, current trip setting accuracy: the error
does not exceed ±3% or ±30mA,current unbalance setting accuracy: the error does not
exceed ±3%.
b) Time delay accuracy: the error does not exceed ±100ms when time delay setting is 0s, the
error does not exceed ±25ms when time delay setting is 0.1~2s, the error does not exceed
±1% of setting when time delay setting is over 2s.
c) Time delay accuracy of Thermal protection: the error does not exceed ±100ms or ±5%;
d) Trip setting accuracy of Under-power protection: the error does not exceed ±5%; Time delay
accuracy of Under-power protection: the error does not exceed ±300ms;
4 ~ 20mA drive load: ≤ 300 Ω pure resistive load
Output contact rating:AC250V,8A.
Power consumption
Maximum power consumption ≤ 5W.
Environmental specifications
Atmospheric pressure:80kPa~110kPa(below 2000m of sea level).
Humidity:5% ~ 95%
Operating temperature:-20℃~+55℃.
Operating Environment:Does not contain materials that lead to metal corrosion or damage to the
insulation of gas and more serious mold and dust, does not contain fire explosion hazard.
2
MLPR-220 line protection controller WLD[K]-JY-323-2014
1.4 Device shape and model description
Fig.1-1 Device shape
Fig.1-2 Model description
2. Functional description
2.1 Protective functioning
2.1.1 Instantaneous over-current protection
The following setpoints are available for the instantaneous over-current protection, see
Tab.2-1.
Tab.2-1
Setting item Setting range Setting step
Instantaneous over-current setting 0.01-10(Ie) 0.01
Instantaneous over-current protection
delay 0-100(S) 0.01
2.1.2 Overcurrent protection
The following setpoints are available for the Overcurrent protection, see Tab.2-2.
Tab.2-2
Setting item Setting range Setting step
Overcurrent setting 0.01-10 (Ie) 0.01
Overcurrent protection delay 0-100(S) 0.01
2.1.3 Over-load protection
The following setpoints are available for the over-load protection, see Tab.2-3.
Tab.2-3
3
MLPR-220 line protection controller WLD[K]-JY-323-2014
Setting item Setting range Setting step
Over-load setting(A) 0.01-10(Ie) 0.01
Over-load protection delay(b) 0-100(S) 0.01
Over-load protection could act as either “alarm mode” or “trip mode”.
2.1.4 Zero sequence current protection
The following setpoints are available for the zero sequence current protection, see Tab.2-4.
Tab.2-4
Setting item Setting range Setting step
Zero sequence current setting 0.01-10(Ie) 0.01
Zero sequence current protection
delay 0-100(S) 0.01
2.1.5 Leakage current protection
The following setpoints are available for the leakage current protection, see Tab.2-5
Tab.2-5
Setting item Setting range Setting step
Leakage current protection setting 2.0-5000.0(mA) 0.1
Leakage current protection delay 0-100(S) 0.01
Leakage current protection could act as either “alarm mode” or “trip mode”.
2.1.6 Low voltage protection
The following setpoints are available for the low voltage protection, see Tab.2-6。
Tab.2-6
Setting item Setting range Setting step
Low voltage setting 0.1-6000.0(V) 0.1
Low voltage mode 00-01 1
Low voltage protection delay 0-100(S) 0.01
2.1.7 Over voltage protection
The following setpoints are available for the over voltage protection, see Tab.2-7。
Tab.2-7
Setting item Setting range Setting step
Over voltage setting 0.1-6000V 0.1
Over voltage protection delay 0-100(S) 0.01
Over voltage protection could act as either “alarm mode” or “trip mode”.
2.2 Settings of protection
Select “Parameter” menu, set the rated current of the line and CT coefficient;
Select “Settings” menu, choose the corresponding setting item and make changes;
Select “Protection ON/OFF” menu, choose the corresponding ON/OFF control menu and
make changes.
Example: Make changes to the setpoints available for the instantaneous overcurrent protection
Select “Parameter” menu, set rated current ;
Select “Instantaneous overcurrent protection” menu, set instantaneous overcurrent
protection current, and instantaneous overcurrent protection delay;
Select “protection ON/OFF” menu, set instantaneous overcurrent protection to ON, which
means the value of instantaneous overcurrent protection is “1”.
Remark: See “5.Parameters setting” for detail information on how to make changes to settings.
4
MLPR-220 line protection controller WLD[K]-JY-323-2014
3. Device description
The control panel of MLPR-220 line protection controller is as Fig.3-1
Fig.3-1
3.1 Indicators
There are 4 indicators on the control panel of line protection controller, which are RUN, COMM,
ALARM, TRIP.
RUN: when the line protection controller is on power and running, “RUN” flashes in yellow;
COMM: when the line protection controller is communicating, “COMM” flashes in yellow;
ALARM: when parameters of the line protection controller are wrong, or alarm is on, “ALARM”
is steadily illuminated in red;
TRIP: when protection trips, “TRIP” is steadily illuminated in red.
3.2 Keypad
There are 7 buttons on the control panel of line protection controller: Close, Open/, , ,
ESC, Revert, Enter
“Close/, Open/”:When it is in cycle displaying mode, the key used to line control; when it is
in parameter modifying mode, the key used to move the cursor;
“”:Menu selecting, moving upwards or increasing the value;
“”:Menu selecting, moving downwards or decreasing the value;
“ESC”:Cancel the operation or return to the higher level menu;
“Revert”:The key used to revert signals;
“Enter”:Confirm the menu or value.
3.3 Display and menu operation
When it is in normal operating, it display IA, IB, IC, Uab, Ubc, Uca, P, Q, cosφ, F,DI,DO in cycle
and real-time, press “” “” can check every value. (IA: phase A current,I0: Residual current,I0j:
zero-sequence current, F: frequency,DI: binary input, DO: binary output)
The meaning of every menu is as follows:
View data-------- Used to view the protective data, measuring data, binary input, power
metering and device version information:
Revert--------Used to revert signals;
Setting--------Used to set and view protections and protection ON/OFF;
Parameter--------Used to set and view parameters of communication, line control, line running,
DCS, CT coefficient, power metering etc;
Events--------Used to view and delete event report and delete line operation parameter;
Time-------- Used to set and view the system time;
Password--------Used to modify system password;
5
MLPR-220 line protection controller WLD[K]-JY-323-2014
Binary output-------- Used to test the binary output;
calibration--------Used to calibrate measuring value.
4. Operating principle
The line protection controller firstly sample the three phase current of phase A,B,C and zero
sequence current I0, leakage current, voltage of phase A to phase B through current transformer,
potential transformer, then the signal is transmitted to analog-to-digital conversion, the cpu reads
the data of all channels and calculates and processes, then compare them to every settings and
find out if the line is on fault, if it is, then the corresponded relay is operated and the information is
displayed on the LCD screen. See the principle on Fig.4-1.
Fig.4-1
When it is in normal operation, it is in monitoring state, it displays three phase current, three
phase voltage, frequency, power etc. in cycle.
6
MLPR-220 line protection controller WLD[K]-JY-323-2014
5. Parameter setting
5.1 System parameter setting
5.1.1 Parameters list
Category Setting name Setting range Remarks
Communication
address 01-99
00:2.4Kbps
01:4.8Kbps
Communication Baud rate 00-04 02:9.6Kbps
settings 03:19.2Kbps
04:38.4Kbps
00:No check
Parity check setting 00-02 01:Odd
02:Even
00:Remote
Remote/Local
control selection 00-02 01:Local
02:Binary input control
00:Binary input control
Remote control
Line Control mode 00-02 01:Contact control
02:Communication control
Control return time 0.50-10.00s After Control lines, return time of the Outputs
Protection return 00-01 00:Immediately return method 01:Return after revert
Rated Current 0.1-5000.0A
Zero Seq.RCur 0. 1-5000.0A
Line running
Zero Seq.Mode 00-01 00:Calculate 01:Measure
DA channel 00-05 00: IA、01:IB、02: IC、03: UABselection
DCS 04: UBC、05: UCA
parameters DA coefficient 1
setting setting
1.000-8.500 4mA channel calibration
DA coefficient 2
setting 0.100-1.000 20mA channel calibration
Protective CT
coefficient 0.1-5000.0
CT/PT Residual current CT
coefficients coefficient
setting (Zero sequence CT
0.01-500.00
coefficient)
PT coefficient 0.01-80.00
Positive active
energy meter 0-4294967.295KWH
Power Negative active
metering energy meter
0-4294967.295KWH
setting Positive reactive energy meter 0-4294967.295WVH
Negative reactive
energy meter 0-4294967.295WVH
Display setting Display setting 0-32
“Protection return method” parameters setting note:
7
MLPR-220 line protection controller WLD[K]-JY-323-2014
When protection operates, the return methods of protection output are: “direct return” means
the protection output returns automatically when the fault disappears. “Reverting return” means
protection output returns by reverting operation and it must meet reverting conditions when the fault
disappears.
Please set the CT coefficient, and then set the rated current.
Residual current CT coefficient(Zero sequence CT coefficient) parameters setting note:
When Zero Seq.Mode is calculate, the CT coefficient is Residual current CT coefficient; When
Zero Seq.Mode is measure, the CT coefficient is Zero sequence CT coefficient.
5.1.2 Setting method
Move the cursor to “parameter” menu on main menu, press “Enter” button, to enter
“password” menu, see Fig.5-1;
Input the correct password(“0000” by default), press “Enter” button to enter parameter
setting menu;
Choose the demand parameter, press “Enter” to enter corresponding sub-menu;
Press “” and “” to choose the menu to make changes, press “Enter” button to enter and
make changes, see Fig.5-2;
Press “”, “” button to move cursor to desiring digit(the digit which is desired to modify),
press “” and “” button to increase or decrease value;
After modification, press “Enter” to Enter the modification, if “ESC” is pressed, the
modification is discarded.
Enter password COMM. setting
Device address.
0000 01
Fig.5-1 Fig.5-2
Note: When “Protection CT coefficients” or “line rated current” are being modified, please
put all protections off.
MLPR-220 line protection controller change the current to voltage signals through external
current transformer, “protective CT coefficient” should be set according to the model of the external
current transformer, the value equals to the one marks as line rated current on current transformer.
Example: The model of current transformer is “Current transformer CT-25M2 10”, primary
rated current of line is 25A, maximum range is 10 times, so the maximum current to be measured is
25×10=250. Set current transformer coefficient of menu “Current transformer coefficient” to 25.
“DCS parameters setting” Firstly, the current or voltage channel expected to transfer need
to be set, before connected to any source, set “DA coefficient 1 setting” to let “terminal 31, 32”(see
MLPR-230 line protection controller terminal figure for detail) output 4mA DC current; set “DA
coefficient 2 setting” to let “terminal 31, 32” output 20mA DC current. After setting “DCS parameter
settings”, when applying analog signal to corresponding channel, “terminal 31, 32” will output
4-20mA, See the principle on Fig.5-3.
PT ≠ 1.00
example:PT = 6.60
U 20mA:6.6×120 = 792VPT=1.00 U I
456 V PT*120 CT
OUTPUT OUTPUT OUTPUT
0 4mA 20mA 0 4mA 20mA 0 4mA 20mA
DA channel selection DA channel selection DA channel selection
:UAB、UBC、UCA :UAB、UBC、UCA :IA、IB、IC
Fig.5-3
8
MLPR-220 line protection controller WLD[K]-JY-323-2014
5.2 Protective setting
5.2.1 Method of modifying protective setting
Move the cursor to “setting”, press “Enter” button, enter password(“0000” by default) to enter
setting modification menu;
The method of modifying is the same as that of “parameter”;
Please refer to this manual “2.1 protective function” for protective settings.
The setting range and setting step in the item are set according to limit state. The range is
slightly different according to the rated current of line.
5.2.2 Protection ON/OFF
Select “protection ON/OFF” menu, press “Enter” button, enter password(“0000” by default)
to enter protective setting menu;
Move the cursor to “Protection ON/OFF”, to enter protection ON/OFF menu.
Press “”, “” button to select ON or OFF, press “” and “” button to choose protection.
If the “PT signal alarm” is on, the low-voltage protection and under-power protection should
be blocked with alarm signal when PT is broken.
zero sequence current protection and Residual current protection can not be
used together.
Tab.5-1
No. Protection Name Setting range
1 Instantaneous overcurrent protection ON, OFF
2 Overcurrent protection ON, OFF
3 Over load protection trip ON, OFF
4 Over load protection alarm ON, OFF
5 Zero sequence current protection ON, OFF
6 Leakage current protection trip ON, OFF
7 Leakage current protection alarm ON, OFF
8 Low voltage protection ON, OFF
9 Over voltage protection trip ON, OFF
10 Over voltage protection alarm ON, OFF
11 PT signal alarm ON, OFF
5.3 Analog setting
Select “calibration” menu, press “Enter” button, enter password to enter analog setting
menu.
Apply corresponding analog source, enter into the actual value applied.
The standard of corresponding correction value is: voltage is the rated measuring voltage,
leakage current is 1000mA, three phase current is the rated current of corresponding current
transformer. If the value input is too high or too low, calibration will not succeed, it will display
message “Please input rated value”.
The content of “Automatic calibration” is listed in Tab.5-2.
Tab.5-2
No. Parameter name Setting range remarks
1 Calibrate voltage UAB 0-9999.99V
2 Calibrate voltage UBC 0-9999.99V
3 Calibrate voltage UCA 0-9999.99V
4 Calibrate current IA 0-9999.99A
5 Calibrate current IB 0-9999.99A
6 Calibrate current IC 0-9999.99A
7 Calibrate Residual current 0-9999mA Calibrate zero sequence current 0-9999.99A
8 Calibrate UAB<>IA 0-89.99
Calibrate After calibrate current and voltage9 UBC<>IC 0-89.99
Correct the analog channel before applying corresponding source is prohibited.
9
MLPR-220 line protection controller WLD[K]-JY-323-2014
Please proofread voltage and current before UAB <> IA and UBC <> IC has been proofread
correction. When proofreading UAB <> IA and UBC<>IC, the angle which has been inputted stands
for two-table method measured active power. MLPR-220 can be corrected by applying the
maximum current of “the scope of application”(see nameplate of external primary current
transformer, model description in Fig.5-3, see App. Tab.2 for selection of transformer) marked on
the primary current transformer.
Fig.5-4
5.4 System time
Select “time” in main menu, press “confirm” button, to enter system time menu;
Press “Enter” button in “time” menu, to do modifications;
Press “”, “” button to select corresponding parameter which is desired to modify, press
“” and “” button to change the value;
After modification, press “Enter” to Enter the modification, if “ESC” is pressed, the
modification is discarded.
5.5 Password setting
Select “password” in main menu, press “Enter” button, enter password modification menu,
the password is “0000” by default;
Enter old password first, press “Enter” button to enter new password modification menu,
press “ESC” to exit password modification menu;
Enter new password, press “Enter” to Enter the modification, if “ESC” is pressed, the
modification is discarded.
6. Check Method
6.1 Preparation before check
6.1.1 Check before power is on
External wiring is correct, appearance is good, plug-ins are in good contact with others.
6.1.2 Monitoring and adjusting of analog quantities
Firstly set CT/PT coefficients correctly in “parameter”-“CT/PT coefficient setting” menu, apply
current of phase A, B, C, leakage current ,UAB, UBC and UCA according to Tab.6-1, view the data
in main cycle display through moving “” button. Apply primary current directly to the external
primary current transformer.
Tab.6-1
Analog name Checking method
Protective phase A current Apply rated current, the variations of display should not exceed 1%
Protective phase B current Apply rated current, the variations of display should not exceed 1%
Protective phase C current Apply rated current, the variations of display should not exceed 1%
Residual current I0 Apply rated Residual current(rated zero sequence
(zero sequence current I0j ) current), the variations of display should not exceed 1%
Phase to phase voltage UAB Apply rated measuring voltage(380V or 100V etc.),
Phase to phase voltage UBC device displays the primary voltage(secondary voltage*PT coefficients), the variations should not
Phase to phase voltage UCA exceed 2%
Choose “view data” menu, press “Enter” button, enter real-time data viewing menu;
If the data displayed exceed 5% the actual value applied, correct the corresponding analog
10
MLPR-220 line protection controller WLD[K]-JY-323-2014
channel through “channel setting” menu.
6.1.3 View binary input
Move the cursor to “binary input” in “view data” menu, press “Enter” to enter binary input
menu;
Connect rated voltage (AC, DC 220V or 110V) to COM terminal, the other to IN1~IN7, the
corresponding display bit will change from “open” to “close”;
Disconnect binary input voltage, the corresponding display bit will change from “close” to
“open”.
6.1.4 View binary output
Choose “binary output”, press “Enter” and enter password(“0000” by default) to view binary
output in the menu;
Move the cursor to the output desired to check, press “Enter” button, enter the
corresponding output check menu, select close, open to finish checking;
Or move the cursor to operate all outputs, press “Enter” button, enter operate all output
menu, select close, open to finish checking.
6.2 Check of control function
6.2.1 Local control mode
Remark: Only when it is on cycle display mode, the user can push the pushbutton “Close” and
“Open” to operate the breaker, otherwise he can’t do it. After the user has operated the breaker, he
had best choose the “Remote/Local” to “remote”.
Select local in “remote/local selection” in menu “parameter”-“line control parameter”, or
select binary input control and terminals COM-IN3 disconnecting, the line protection controller will
be in local control mode;;
Under no protection operating, in the loop menu, press the pushbutton “Close”, get into the
display window shown as Fig.6-1.
Press the pushbutton “Enter”, Out1 will close immediately;
Under no protection operating, in the loop menu, press the pushbutton “Open”, get into the
display window shown as Fig.6-2.
Press the pushbutton “Enter”, Out2 will close immediately.
Close Bkr
Confirm
Fig. 6-1
Open Bkr
Confirm
Fig. 6-2
6.2.2 Remote control mode
Select remote in “remote/local selection” in menu “parameter”-“line control parameter”, or
select binary input control and Connect rated voltage (AC, DC 220V or 110V) to both sides of the
terminals COM-IN3, the line protection controller will be in remote control mode;
Remote control mode is classified of terminal control and communication control.
By menu “parameter”-“ Remote control mode” can select remote control mode.
If remote control mode is “communication control”, or if remote control method is “binary
input select” when IN4 is also 1, the line protection controller is in communication control mode; If
remote control mode is “terminal control”, or if remote control method is “binary input select” when
IN4 is 1, the line protection controller is in terminal control mode.
6.2.2.1 Communication control mode
If remote control mode is “communication control”, communication close or open the line can
be achieved through sending order from background software to line protection controller.
6.2.2.2 Terminal control mode
If remote control mode is “terminal control”, terminal close or open the line can be achieved.
11
MLPR-220 line protection controller WLD[K]-JY-323-2014
【Remarks:】Please see the setting descriptions of “control input method” in this manual 5.1.1.
Apply voltage between IN5 and COM, the OUT1 terminals should close immediately,
indicating that the breaker should close.
Apply voltage between IN6 and COM, the OUT2 terminals should close immediately,
indicating that the breaker should open.
Remark: if line protection controller has any protection operation or protection action signal is
not reverted, prohibit all control functions.
6.3 Check of protective function
Note: Ie stands for the rated current of line.
Note: when checking portective function, please make sure that the current is at the range of
0.05~1.0 of the external current transformer.
6.3.1 Check of instantaneous over-current protection
When one of the current of phase A, B, C becomes higher than the setting value and last for
the delay time set the protection operates. The operation logic of instantaneous over-current
protection is as Tab.6-2, the parameters needed for instantaneous over-current protection are in
2.1.1 this manual , Tab.2-1.
Tab.6-2
Instantaneous Instantaneous over-current protection ON
over-current Instantaneous current > Instantaneous over-current protection
protection setting current
operation logic Current time > setting delay
Wire as Fig.6-3, set instantaneous over-current protection to ON, set delay as 0 second, set
other protections to OFF;
Set according to Tab.6-3, test the actual value, and record it in the table.
When the protection operates, terminal OUT2, OUT3 should be shorted.
Tab.6-3
Instantaneous over-current protection setting current 1In 2In 5In 10In
Actual value when operates
MLPR-220
IA(IB,IC) IA(IB,IC) L
IA'(IB’,IC') IA’(IB’,IC’)
UA UA Power supply
UB UB
UC UC N
Fig.6-3
6.3.2 Check of Overcurrent Protection
When one of the current of phase A, B, C becomes higher than the setting value and last for
the delay time set the protection operates. The operation logic of Overcurrent Protection is as
Tab.6-4, the parameters needed for Overcurrent Protection are in 2.1.2 this manual , Tab.2-2.
Tab.6-4
Overcurrent Overcurrent Protection ON
Protection Overcurrent current > Overcurrent Protection setting current
operation logic Current time > setting delay
Wire as Fig.6-3, set Overcurrent Protection to ON, set delay as 0 second, set other
protections to OFF;
Set according to Tab.6-5, test the actual value, and record it in the table.
When the protection operates, terminal OUT2, OUT3 should be shorted.
12
MLPR-220 line protection controller WLD[K]-JY-323-2014
Tab.6-5
Overcurrent Protection setting current 2.0Ie 3.0Ie 4.0Ie
Actual value when operates
6.3.3 Check of over load protection
When actual current is over the over load current setting and last over setting delay, the
protection operates. The operation logic of over load protection is as Tab.6-6, the parameters
needed for locked rotor protection are in 2.1.3 this manual , Tab.2-3.
Tab.6-6
Over load protection is ON
Over load protection
operation logic Over load current > over load current setting Over load time > over load delay setting
Wire as Fig.6-3, set over load protection to ON, set over load delay to 0S, set other
protections to OFF.
Set according to Tab.6-7, test the actual value, and record it in the table.
If over load protection is in alarm mode
When it operates, terminal OUT3 should be shorted and “ALARM” is illuminated in red,
when fault current is cut, alarm revert, OUT3 should be opened and turns off the “ALARM”.
If over load protection is in trip mode
When the protection operates, terminal OUT2, OUT3 should be shorted,.
If over load protection is in trip mode, alarm mode blocked.
Tab.6-7
Over load current setting (Ie) 1Ie 2Ie 3Ie
Actual value when operates
6.3.4 Check of zero sequence current protection
When the zero sequence current is higher than the setting and last for the delay setting it
operates. The operating logic of zero sequence protection is as Tab.6-8, for the details of
parameters needed for zero sequence current protection please refer to this manual 2.1.4 Tab.2-4.
Tab.6-8
Zero sequence current protection is ON
Zero sequence current
protection operation logic Zero sequence current > zero sequence current setting
Zero sequence current time > zero sequence delay setting
Remark:in order to maintain the correctness of calculation, 3 phase current should be
applied to do this test.
Wire as Fig.6-3, set zero sequence current protection to ON, set other protection to OFF. Set
zero sequence current delay to 0S.
Set the zero sequence current setting according to Tab.6-9, test the actual value, and record
it in the table.
When the protection operates, terminal OUT2, OUT3 should be shorted.
Tab.6-9
Zero sequence current protection setting (Ie) 2 Ie 5 Ie 10 Ie 15 Ie
Actual value when operates
6.3.5 Check of Residual current protection
When “Zero Seq.Mode” in “Measure” mode, the protection is blocked; When the Residual
current is higher than the setting and last for the delay setting, it operates. The operating logic of
Residual current protection is as Tab.6-10, for the details of parameters needed for Residual current
protection please refer to this manual 2.1.5 Tab.2-5.
Tab.6-10
Residual sequence current protection is ON
Residual current protection operation logic Residual current > Residual current setting
Residual current time > Residual current delay setting
Apply Residual current as Fig.6-4 wire as Fig.6-3, set Residual current protection to ON, set
other protection to OFF. Set leakage current delay to 0S.
Set the Residual current setting according to Tab.6-11, test the actual value, and record it in
the table.
13
MLPR-220 line protection controller WLD[K]-JY-323-2014
If Residual current protection is in alarm mode
When it operates, terminal OUT3 should be shorted and “ALARM” is illuminated in red,
when fault current is cut, alarm revert, OUT3 should be opened and turns off the “ALARM”.
If Residual current protection is in trip mode, the alarm mode is blocked
When the protection operates, terminal OUT2, OUT3 should be shorted.
MLPR-220
I0
I0 L
I0' I0’ N
Fig. 6-4
Tab.6-11
Residual current
protection setting (mA) 100 500 1000 5000
Actual value when
operates
6.3.6 Check of low voltage protection
When the current is higher than 0.1Ie time of rated current of line, and the line voltage drops
below the setting from normal value and last for the delay setting, it operates. If PT alarm is on, the
protection is blocked when PT is broken. When the voltage and current drop at the same time, the
low-voltage protection also operates after the delay.The operating logic of low voltage protection is
as Tab.6-12, for the details of parameters needed for low voltage protection please refer to this
manual 2.1.6 Tab.2-6.
Tab.6-12
Low-voltage protection is on.
Low-voltage protection logic Voltage < setting of low-voltage protection
Low-voltage protection delay > time-delayed
setting
Wire as Fig.6-3, set Low-voltage protection to ON, set over load delay to 0S, set other
protections to OFF.
Set the low-voltage setpoint as Tab.6-13, measure the operational value and then keep a
record in the table.
When the protection operates, terminal OUT2, OUT3 should be shorted.
If PT coefficients is1, the default rating voltage is 380V; if PT coefficients larger than 1, the
rating voltage is 100V × PT coefficients.
Tab.6-13
Low-voltage protection setting(V) 200 250 300 350
Operational value
6.3.7 Check of over-voltage protection
When the current is higher than 0.1Ie time of rated current of line, and bus voltage is higher
than the setting, and meets the time-delayed value, the protection operates. The operation logic of
over-voltage protection is as Tab.6-14. The needed parameters of over-voltage protection are
provided in the Tab. 2-7 of this manual 2.1.7.
Tab.6-14
Over-voltage protection is on.
Over-voltage protection operational logic Over-voltage > over-voltage protection setting
Over-voltage protection delay > time-delayed
setting
Wire as Fig.6-3, set over-voltage protection to ON, set over load delay to 0S, set other
protections to OFF.
14
MLPR-220 line protection controller WLD[K]-JY-323-2014
Set according to Tab.6-15, test the actual value, and record it in the table.
If over-voltage protection is in alarm mode
When it operates, terminal OUT3 should be shorted and “ALARM” is illuminated in red,
when fault current is cut, alarm revert, OUT3 should be opened and turns off the “ALARM”.
If over-voltage protection is in trip mode
When the protection operates, terminal OUT2, OUT3 should be shorted,.
If over-voltage protection is in trip mode, alarm mode blocked.
Tab.6-15
Over-voltage alarm setting (V) 400 420 440 460
The operational value
6.4 Check of communication function
6.4.1 Check of measuring analog value
Current of phase A, B, C, leakage current, zero sequence current, phase to phase voltage
UAB, UBC, active power, reactive power, power coefficient can be transmitted to background
monitor system through communication port.
6.4.2 Check of remote signal upload
All protection information, binary change information can be transmitted to background monitor
system through communication port.
7. Product maintenance
Please contact the manufacturer to deal with.
8. Cautions
Please refer to the label of the device for the details of the voltage of line protection controller,
please be sure about the voltage and the power supply terminals, the internal components may be
damaged if the wiring method is not correct.
When doing checking of the line protection controller, please don’t apply high current for long.
Terminal “shielding ground” should be firmly connected to ground.
Non-professionals should not disassemble the line protection controller.
15
MLPR-220 line protection controller WLD[K]-JY-323-2014
Appendix 1:MLPR-220 line protection controller terminal figure
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Output 3 Output 5(13,14 are
Power supply 3 Output 1 Output 2 (Protection Output 4(
(Closing (Opening means ground operated /
(remote the Power Supply
) output output Device output Failure closed ) ) )
Failure terminals) )
MLPR-220 line protection controller terminal definitions
Ua Ub Uc Ia Ib Ic In
15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
N ote: Input 7 is shared with leakage current / zero sequence current input. When ordering, please mention that
w hich function is used.
16
COMM. B
COMM. A
DC output -
DC output +
Signal input COM
Input 1(Breaker state)
Input 2(Reserve)
Input 3(Remote / Local)
Input 4(Remote control
mode)
Input 5(Close breaker)
Input 6(Open breaker)
Input 7 (leakage current /
zero sequence current)
Appendix Tab.1:Typical specifications of external current transformer
Typical specifications of external current transformer
No. Specifications of current transformer Power of line
transformer hole maximum
diameter measuring range
1 1A <0.5KW ∮20mm 10X
2 5A 0.5~2.5KW ∮20mm 10X
3 12A 2.5~6.0KW ∮20mm 10X
4 25A 6.0~12.5KW ∮30mm 10X
5 50A 12.5~25KW ∮30mm 10X
6 100A 25~50KW ∮30mm 10X
7 200A 50~100KW ∮30mm 10X
The specifications of external current transformer above are the rated current of the corresponding
line, the maximum measuring range is 10X. If the rated current of the line is too high, a combination of 1A
and 5A external current transformer and the primary high-capacity current transformer can be used.
17
Appendix Fig.1:
18